SEVD-2026-160-03
Vulnerability from csaf_se - Published: 2026-06-09 07:00 - Updated: 2026-06-09 07:00CWE-476 NULL Pointer Dereference vulnerability exists that could cause a denial-of-service condition, rendering the device’s HMI and configuration functionality unavailable when malformed requests are received over exposed network interfaces.
| Product | Identifier | Version | Remediation |
|---|---|---|---|
|
PowerLogic™ version 0.2.003.001.000
Schneider Electric / PowerLogic™ P7
|
0.2.003.001.000 |
| Product | Identifier | Version | Remediation |
|---|---|---|---|
|
PowerLogic™ P7 version 0.2.003.001.000 and prior
Schneider Electric / PowerLogic™ P7
|
vers:intdot/<=0.2.003.001.000 |
Vendor Fix
Mitigation
|
CWE-78 Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could allow unauthorized execution of commands with elevated privileges, impacting system integrity, confidentiality, and availability when a privileged authenticated user interacts with a vulnerable network-exposed service.
| Product | Identifier | Version | Remediation |
|---|---|---|---|
|
PowerLogic™ version 0.2.003.001.000
Schneider Electric / PowerLogic™ P7
|
0.2.003.001.000 |
| Product | Identifier | Version | Remediation |
|---|---|---|---|
|
PowerLogic™ P7 version 0.2.003.001.000 and prior
Schneider Electric / PowerLogic™ P7
|
vers:intdot/<=0.2.003.001.000 |
Vendor Fix
Mitigation
|
CWE-617 Reachable Assertion vulnerability exists that could allow an authenticated attacker to trigger a denial-of-service condition, impacting system availability when a specially crafted request is sent to a vulnerable network-exposed service.
| Product | Identifier | Version | Remediation |
|---|---|---|---|
|
PowerLogic™ version 0.2.003.001.000
Schneider Electric / PowerLogic™ P7
|
0.2.003.001.000 |
| Product | Identifier | Version | Remediation |
|---|---|---|---|
|
PowerLogic™ P7 version 0.2.003.001.000 and prior
Schneider Electric / PowerLogic™ P7
|
vers:intdot/<=0.2.003.001.000 |
Vendor Fix
Mitigation
|
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Public",
"tlp": {
"label": "WHITE"
}
},
"lang": "en-US",
"notes": [
{
"category": "general",
"text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
"title": "General Security Recommendations"
},
{
"category": "general",
"text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
"title": "For More Information"
},
{
"category": "legal_disclaimer",
"text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
"title": "LEGAL DISCLAIMER"
},
{
"category": "general",
"text": "At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.\n\nWe provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.\n\nWe are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.\n\nwww.se.com ",
"title": "About Schneider Electric"
},
{
"category": "summary",
"text": "Schneider Electric is aware of a vulnerability in its PowerLogic\u2122 P7 product. \r\nThe PowerLogic\u2122 P7 is a protection and control platform designed for complex and advanced electrical \r\nnetwork applications.\r\nFailure to apply the remediation provided below may risk unauthorized execution of privileged commands or \r\nloss of HMI operability and configuration functionality, which could result in loss of control over system \r\noperations and disruption of critical services.",
"title": "Overview"
},
{
"category": "other",
"text": "The severity of vulnerabilities was calculated using the CVSS Base metrics for 4.0 ([CVSS v4.0](https://www.first.org/cvss/calculator/4.0)). CVSS v3.1 \nwill be still evaluated until the adoption of CVSS v4.0 by the industry. The severity was calculated without \nincorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as \nthe presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer\u0027s environment."
},
{
"category": "other",
"text": "Customers should use appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric\u0027s [Customer Care Center](https://www.se.com/us/en/work/support/contacts.jsp) if you need assistance removing a patch."
}
],
"publisher": {
"category": "vendor",
"contact_details": "cpcert@se.com",
"name": "Schneider Electric CPCERT",
"namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
},
"references": [
{
"category": "self",
"summary": "Multiple Vulnerabilities on PowerLogic\u2122 P7 - SEVD-2026-160-03 PDF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2026-160-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2026-160-03.pdf"
},
{
"category": "self",
"summary": "Multiple Vulnerabilities on PowerLogic\u2122 P7 - SEVD-2026-160-03 CSAF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2026-160-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2026-160-03.json"
},
{
"category": "external",
"summary": "Recommended Cybersecurity Best Practices",
"url": "https://www.se.com/ww/en/download/document/7EN52-0390"
}
],
"title": "Multiple Vulnerabilities on PowerLogic\u2122 P7",
"tracking": {
"current_release_date": "2026-06-09T07:00:00.000Z",
"generator": {
"date": "2026-05-29T00:00:00Z",
"engine": {
"name": "Schneider Electric CSAF Generator",
"version": "1.2"
}
},
"id": "SEVD-2026-160-03",
"initial_release_date": "2026-06-09T07:00:00.000Z",
"revision_history": [
{
"date": "2026-06-09T07:00:00.000Z",
"number": "1.0.0",
"summary": "Original Release"
}
],
"status": "final",
"version": "1.0.0"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "vers:intdot/\u003c=0.2.003.001.000",
"product": {
"name": "PowerLogic\u2122 P7 version 0.2.003.001.000 and prior",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "PowerLogic\u2122 P7"
},
{
"branches": [
{
"category": "product_version",
"name": "0.2.003.001.000",
"product": {
"name": "PowerLogic\u2122 version 0.2.003.001.000",
"product_id": "2"
}
}
],
"category": "product_name",
"name": "PowerLogic\u2122 P7"
}
],
"category": "vendor",
"name": "Schneider Electric"
}
]
},
"vulnerabilities": [
{
"acknowledgments": [
{
"organization": "Cytrics"
}
],
"cve": "CVE-2026-9716",
"cwe": {
"id": "CWE-476",
"name": "NULL Pointer Dereference"
},
"notes": [
{
"category": "description",
"text": "CWE-476 NULL Pointer Dereference vulnerability exists that could cause a denial-of-service condition, \r\nrendering the device\u2019s HMI and configuration functionality unavailable when malformed requests are received \r\nover exposed network interfaces.",
"title": "CVE Description"
},
{
"category": "details",
"text": "CVSS v4.0 Base Score 8.7 | High | [CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N](https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N)",
"title": "CVSS v4.0 Base Score"
}
],
"product_status": {
"fixed": [
"2"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Version V02.004.001 of PowerLogicTM P7 includes a fix for this vulnerability\r\nand is available for download here:\r\n\u2022 Contact Schneider Electric\u2019s Customer Care Center to download \r\nthis firmware.\r\n\u2022 Reboot needed: Yes",
"product_ids": [
"1"
],
"restart_required": {
"category": "service"
}
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided above, they should immediately apply the following \r\nmitigations to reduce the risk of exploit:\r\n\u2022 Restrict network access to P7 service endpoints (ports 8080 and 3702)\r\n\u2022 Monitor and alert on anomalous SOAP requests targeting wsApp\r\n\u2022 Limit administrative access and apply least privilege principles for all \r\nusers interacting with P7.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2026-9716"
},
{
"acknowledgments": [
{
"organization": "Cytrics"
}
],
"cve": "CVE-2026-9717",
"cwe": {
"id": "CWE-78",
"name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
},
"notes": [
{
"category": "description",
"text": "CWE-78 Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027) vulnerability \r\nexists that could allow unauthorized execution of commands with elevated privileges, impacting system \r\nintegrity, confidentiality, and availability when a privileged authenticated user interacts with a vulnerable \r\nnetwork-exposed service.",
"title": "CVE Description"
},
{
"category": "details",
"text": "CVSS v4.0 Base Score 8.6 | High | [CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N](https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N)",
"title": "CVSS v4.0 Base Score"
}
],
"product_status": {
"fixed": [
"2"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Version V02.004.001 of PowerLogicTM P7 includes a fix for this vulnerability\r\nand is available for download here:\r\n\u2022 Contact Schneider Electric\u2019s Customer Care Center to download \r\nthis firmware.\r\n\u2022 Reboot needed: Yes",
"product_ids": [
"1"
],
"restart_required": {
"category": "service"
}
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided above, they should immediately apply the following \r\nmitigations to reduce the risk of exploit:\r\n\u2022 Restrict network access to P7 service endpoints (ports 8080 and 3702)\r\n\u2022 Monitor and alert on anomalous SOAP requests targeting wsApp\r\n\u2022 Limit administrative access and apply least privilege principles for all \r\nusers interacting with P7.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.2,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "HIGH",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2026-9717"
},
{
"acknowledgments": [
{
"organization": "Cytrics"
}
],
"cve": "CVE-2026-9718",
"cwe": {
"id": "CWE-617",
"name": "Reachable Assertion"
},
"notes": [
{
"category": "description",
"text": "CWE-617 Reachable Assertion vulnerability exists that could allow an authenticated attacker to trigger a \r\ndenial-of-service condition, impacting system availability when a specially crafted request is sent to a \r\nvulnerable network-exposed service.",
"title": "CVE Description"
},
{
"category": "details",
"text": "CVSS v4.0 Base Score 6.9 | Medium | [CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N](https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N)",
"title": "CVSS v4.0 Base Score"
}
],
"product_status": {
"fixed": [
"2"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Version V02.004.001 of PowerLogicTM P7 includes a fix for this vulnerability\r\nand is available for download here:\r\n\u2022 Contact Schneider Electric\u2019s Customer Care Center to download \r\nthis firmware.\r\n\u2022 Reboot needed: Yes",
"product_ids": [
"1"
],
"restart_required": {
"category": "service"
}
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided above, they should immediately apply the following \r\nmitigations to reduce the risk of exploit:\r\n\u2022 Restrict network access to P7 service endpoints (ports 8080 and 3702)\r\n\u2022 Monitor and alert on anomalous SOAP requests targeting wsApp\r\n\u2022 Limit administrative access and apply least privilege principles for all \r\nusers interacting with P7.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 4.9,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "HIGH",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2026-9718"
}
]
}
Sightings
| Author | Source | Type | Date | Other |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.