SEVD-2020-315-06
Vulnerability from csaf_se - Published: 2020-11-10 00:00 - Updated: 2020-12-08 00:00Summary
Easergy T300
Notes
General Security Recommendations
We strongly recommend the following industry cybersecurity best practices.
https://www.se.com/us/en/download/document/7EN52-0390/
* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
* Place all controllers in locked cabinets and never leave them in the “Program” mode.
* Never connect programming software to any network other than the network intended for that device.
* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.
For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.
For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.
We provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.
We are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.
www.se.com
Overview
Schneider Electric is aware of a vulnerability in its Easergy T300 RTU (Remote Terminal Unit).
The Easergy T300 is a modular platform for medium voltage and low voltage public distribution
network management.
Failure to apply the remediation provided below may allow unauthorized access to the internal
product LAN (local area network).
December 2020 Update: Additional CVEs have been added to this disclosure (marked in red).
No additional action is required for customers who have already followed the remediation
instructions provided below.
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Public",
"tlp": {
"label": "WHITE"
}
},
"lang": "en-US",
"notes": [
{
"category": "general",
"text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
"title": "General Security Recommendations"
},
{
"category": "general",
"text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
"title": "For More Information"
},
{
"category": "legal_disclaimer",
"text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
"title": "LEGAL DISCLAIMER"
},
{
"category": "general",
"text": "At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.\n\nWe provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.\n\nWe are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.\n\nwww.se.com ",
"title": "About Schneider Electric"
},
{
"category": "summary",
"text": "Schneider Electric is aware of a vulnerability in its Easergy T300 RTU (Remote Terminal Unit). \r\nThe Easergy T300 is a modular platform for medium voltage and low voltage public distribution \r\nnetwork management. \r\nFailure to apply the remediation provided below may allow unauthorized access to the internal \r\nproduct LAN (local area network). \r\nDecember 2020 Update: Additional CVEs have been added to this disclosure (marked in red). \r\nNo additional action is required for customers who have already followed the remediation \r\ninstructions provided below.",
"title": "Overview"
}
],
"publisher": {
"category": "vendor",
"contact_details": "cpcert@se.com",
"name": "Schneider Electric CPCERT",
"namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
},
"references": [
{
"category": "self",
"summary": "Easergy T300 - SEVD-2020-315-06 PDF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2020-315-06\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2020-315-06_Easergy_T300_Security_Notification_V2.0.pdf"
},
{
"category": "self",
"summary": "Easergy T300 - SEVD-2020-315-06 CSAF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2020-315-06\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2020-315-06.json"
},
{
"category": "external",
"summary": "Recommended Cybersecurity Best Practices",
"url": "https://www.se.com/us/en/download/document/7EN52-0390/"
}
],
"title": "Easergy T300",
"tracking": {
"current_release_date": "2020-12-08T00:00:00.000Z",
"generator": {
"date": "2020-12-08T00:00:00Z",
"engine": {
"name": "Schneider Electric CSAF Generator",
"version": "1.2"
}
},
"id": "SEVD-2020-315-06",
"initial_release_date": "2020-11-10T00:00:00.000Z",
"revision_history": [
{
"date": "2020-11-10T00:00:00.000Z",
"number": "1.0.0",
"summary": "Original Release"
},
{
"date": "2020-12-08T00:00:00.000Z",
"number": "2.0.0",
"summary": "Added the following CVEs: CVE-2020-28215, \r\nCVE-2020-28216, CVE-2020-28217, CVE-2020-\r\n28218. Updated CWE for CVE-2020-7561. (page \r\n1-2)."
}
],
"status": "final",
"version": "2.0.0"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c=2.7",
"product": {
"name": "Schneider Electric Easergy T300 2.7 and older",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "Easergy T300"
},
{
"branches": [
{
"category": "product_version",
"name": "2.7.1",
"product": {
"name": "Schneider Electric Easergy T300 V2.7.1",
"product_id": "2"
}
}
],
"category": "product_name",
"name": "Easergy T300"
}
],
"category": "vendor",
"name": "Schneider Electric"
}
]
},
"vulnerabilities": [
{
"acknowledgments": [
{
"names": [
"Evgeniy Druzhinin",
"Ilya Karpov"
],
"organization": "Rostelecom-Solar"
}
],
"cve": "CVE-2020-7561",
"cwe": {
"id": "CWE-306",
"name": "Missing Authentication for Critical Function"
},
"notes": [
{
"category": "description",
"text": "CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause a \r\nwide range of problems, including information exposure, denial of service, and command \r\nexecution when access to a resource from an attacker is not restricted or incorrectly restricted.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"2"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Customers are strongly encouraged to upgrade to V2.7.1 available from the Schneider Electric \r\nCustomer Care Center. Alternatively, they may disable port forwarding in the product firewall.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
},
"url": "https://www.se.com/us/en/work/support/"
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 10,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "LOW",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "CHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:H/A:H",
"version": "3.0"
},
"products": [
"1"
]
}
],
"title": "CVE-2020-7561"
},
{
"acknowledgments": [
{
"names": [
"Evgeniy Druzhinin",
"Ilya Karpov"
],
"organization": "Rostelecom-Solar"
}
],
"cve": "CVE-2020-28215",
"cwe": {
"id": "CWE-862",
"name": "Missing Authorization"
},
"notes": [
{
"category": "description",
"text": "CWE-862: Missing Authorization vulnerability exists that could cause a wide range of \r\nproblems, including information exposures, denial of service, and arbitrary code \r\nexecution when access control checks are not applied consistently.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"2"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Customers are strongly encouraged to upgrade to V2.7.1 available from the Schneider Electric \r\nCustomer Care Center. Alternatively, they may disable port forwarding in the product firewall.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
},
"url": "https://www.se.com/us/en/work/support/"
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "HIGH",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.7,
"baseSeverity": "HIGH",
"confidentialityImpact": "LOW",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:H/A:H",
"version": "3.0"
},
"products": [
"1"
]
}
],
"title": "CVE-2020-28215"
},
{
"cve": "CVE-2020-28216",
"cwe": {
"id": "CWE-311",
"name": "Missing Encryption of Sensitive Data"
},
"notes": [
{
"category": "description",
"text": "CWE-311: Missing Encryption of Sensitive Data vulnerability exists that would allow an \r\nattacker to read network traffic over HTTP protocol.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"2"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Customers are strongly encouraged to upgrade to V2.7.1 available from the Schneider Electric \r\nCustomer Care Center. Alternatively, they may disable port forwarding in the product firewall.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
},
"url": "https://www.se.com/us/en/work/support/"
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "PHYSICAL",
"availabilityImpact": "HIGH",
"baseScore": 7.6,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "CHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:P/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H",
"version": "3.0"
},
"products": [
"1"
]
}
],
"title": "CVE-2020-28216"
},
{
"cve": "CVE-2020-28217",
"cwe": {
"id": "CWE-311",
"name": "Missing Encryption of Sensitive Data"
},
"notes": [
{
"category": "description",
"text": "CWE-311: Missing Encryption of Sensitive Data vulnerability exists that would allow an \r\nattacker to read network traffic over IEC60870-5-104 protocol.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"2"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Customers are strongly encouraged to upgrade to V2.7.1 available from the Schneider Electric \r\nCustomer Care Center. Alternatively, they may disable port forwarding in the product firewall.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
},
"url": "https://www.se.com/us/en/work/support/"
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "PHYSICAL",
"availabilityImpact": "LOW",
"baseScore": 6.7,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "CHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:P/AC:L/PR:N/UI:N/S:C/C:L/I:H/A:L",
"version": "3.0"
},
"products": [
"1"
]
}
],
"title": "CVE-2020-28217"
},
{
"cve": "CVE-2020-28218",
"cwe": {
"id": "CWE-1021",
"name": "Improper Restriction of Rendered UI Layers or Frames"
},
"notes": [
{
"category": "description",
"text": "CWE-1021: Improper Restriction of Rendered UI Layers or Frames vulnerability exists that \r\nwould allow an attacker to trick a user into initiating an unintended action.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"2"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Customers are strongly encouraged to upgrade to V2.7.1 available from the Schneider Electric \r\nCustomer Care Center. Alternatively, they may disable port forwarding in the product firewall.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
},
"url": "https://www.se.com/us/en/work/support/"
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "HIGH",
"attackVector": "LOCAL",
"availabilityImpact": "LOW",
"baseScore": 6.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "CHANGED",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.0/AV:L/AC:H/PR:N/UI:R/S:C/C:N/I:H/A:L",
"version": "3.0"
},
"products": [
"1"
]
}
],
"title": "CVE-2020-28218"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.