ICSA-26-113-03

Vulnerability from csaf_cisa - Published: 2026-04-23 06:00 - Updated: 2026-04-23 06:00
Summary
Milesight Cameras
Notes
Legal Notice and Terms of Use: This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).
Risk evaluation: Successful exploitation of these vulnerabilities could crash the device being accessed or allow remote code execution.
Critical infrastructure sectors: Commercial Facilities
Countries/areas deployed: Worldwide
Company headquarters location: China
Recommended Practices: CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities.
Recommended Practices: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
Recommended Practices: Locate control system networks and remote devices behind firewalls and isolating them from business networks.
Recommended Practices: When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
Recommended Practices: CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices: CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices: CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Recommended Practices: Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices: Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices: CISA also recommends users take the following measures to protect themselves from social engineering attacks:
Recommended Practices: Do not click web links or open attachments in unsolicited email messages.
Recommended Practices: Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Recommended Practices: Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
Recommended Practices: No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
CWE-639 - Authorization Bypass Through User-Controlled Key
Affected products
Product Identifier Version Remediation
Milesight MS-Cxx63-PD: <=51.7.0.77-r12
Milesight / MS-Cxx63-PD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx64-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx64-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx73-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx73-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx75-xxPD: <=51.7.0.77-r12
Milesight / MS-Cxx75-xxPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx83-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx83-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx74-PA: <=3x.8.0.3-r11
Milesight / MS-Cxx74-PA
<=3x.8.0.3-r11
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C8477-HPG1: <=63.8.0.4-r3
Milesight / MS-C8477-HPG1
<=63.8.0.4-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C8477-PC: <=48.8.0.4-r3
Milesight / MS-C8477-PC
<=48.8.0.4-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5321-FPE: <=62.8.0.4-r5
Milesight / MS-C5321-FPE
<=62.8.0.4-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx72-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx62-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx62-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx52-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx52-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx66-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxGPE: <=61.8.0.5-r2
Milesight / MS-Cxx66-xxxGPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx61-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx61-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx67-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx67-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx71-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx71-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx41-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx41-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx76-PE: <=61.8.0.5-r2
Milesight / MS-Cxx76-PE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx65-PE: <=61.8.0.5-r2
Milesight / MS-Cxx65-PE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx66-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx62-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx62-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx72-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx31-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx31-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx68-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx68-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx72-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx72-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-NxE: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-NxE
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxC: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxC
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxE: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxE
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxG: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxG
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxH: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxH
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxT: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxT
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PMC8266-FPE: <=PO_61.8.0.4_LPR
Milesight / PMC8266-FPE
<=PO_61.8.0.4_LPR
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PMC8266-FGPE: <=PO_61.8.0.4_LPR
Milesight / PMC8266-FGPE
<=PO_61.8.0.4_LPR
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PM3322-E: <=PI_61.8.0.3_LPR-r3
Milesight / PM3322-E
<=PI_61.8.0.3_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS5366-X12RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-RFIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-RFIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-RFIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-RFIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIWG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIWG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIWG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIWG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5510-GVH: <=T_47.8.0.4_LPR-r7
Milesight / TS5510-GVH
<=T_47.8.0.4_LPR-r7
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5510-GH: <=T_47.8.0.4_LPR-r6
Milesight / TS5510-GH
<=T_47.8.0.4_LPR-r6
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5511-GVH: <=T_47.8.0.4_LPR-r6
Milesight / TS5511-GVH
<=T_47.8.0.4_LPR-r6
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2966-X12TPE: <=T_61.8.0.4_LPR-r3
Milesight / TS2966-X12TPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12PE: <=T_61.8.0.4_LPR-r3
Milesight / TS5366-X12PE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4PE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4PE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2966-X12TVPE: <=T_61.8.0.4_LPR-r3
Milesight / TS2966-X12TVPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RVPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RVPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12VPE: <=T_61.8.0.4_LPR-r3
Milesight / TS5366-X12VPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4VPE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4VPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4441-X36RPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4441-X36RPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4441-X36RE: <=T_61.8.0.4_LPR-r3
Milesight / TS4441-X36RE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RWE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RWE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4WE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4WE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2964-RFLPC: <=T_45.8.0.3-r9
Milesight / MS-C2964-RFLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2972-RFLPC: <=T_45.8.0.3-r9
Milesight / MS-C2972-RFLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-RFLWPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-RFLWPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TVPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TGPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TGPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2841-X36TPC: <=T_45.8.0.3-r9
Milesight / TS2841-X36TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2841-X36TPC/W: <=T_45.8.0.3-r9
Milesight / TS2841-X36TPC/W
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2867-X5TPC: <=T_45.8.0.3-r9
Milesight / TS2867-X5TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2961-X12TPC: <=T_45.8.0.3-r9
Milesight / TS2961-X12TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-FPC/P: <=T_45.8.0.3-r9
Milesight / TS8266-FPC/P
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-X12RLPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-X12RLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-X12RLVPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-X12RLVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5366-X12LPC: <=T_45.8.0.3-r9
Milesight / MS-C5366-X12LPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5366-X12LVPC: <=T_45.8.0.3-r9
Milesight / MS-C5366-X12LVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5361-X12LPC: <=T_45.8.0.3-r9
Milesight / MS-C5361-X12LPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxxGOPC: <=45.8.0.2-AIoT-r4
Milesight / MS-Cxx66-xxxxGOPC
<=45.8.0.2-AIoT-r4
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight SC211: <=C_21.1.0.8-r4
Milesight / SC211
<=C_21.1.0.8-r4
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight SP111: <=52.8.0.4-r5
Milesight / SP111
<=52.8.0.4-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-RFIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx66-RFIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-RFIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx72-RFIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-FIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx66-FIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-FIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx72-FIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
CWE-798 - Use of Hard-coded Credentials
Affected products
Product Identifier Version Remediation
Milesight MS-Cxx63-PD: <=51.7.0.77-r12
Milesight / MS-Cxx63-PD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx64-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx64-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx73-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx73-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx75-xxPD: <=51.7.0.77-r12
Milesight / MS-Cxx75-xxPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx83-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx83-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx74-PA: <=3x.8.0.3-r11
Milesight / MS-Cxx74-PA
<=3x.8.0.3-r11
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C8477-HPG1: <=63.8.0.4-r3
Milesight / MS-C8477-HPG1
<=63.8.0.4-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C8477-PC: <=48.8.0.4-r3
Milesight / MS-C8477-PC
<=48.8.0.4-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5321-FPE: <=62.8.0.4-r5
Milesight / MS-C5321-FPE
<=62.8.0.4-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx72-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx62-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx62-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx52-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx52-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx66-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxGPE: <=61.8.0.5-r2
Milesight / MS-Cxx66-xxxGPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx61-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx61-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx67-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx67-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx71-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx71-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx41-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx41-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx76-PE: <=61.8.0.5-r2
Milesight / MS-Cxx76-PE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx65-PE: <=61.8.0.5-r2
Milesight / MS-Cxx65-PE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx66-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx62-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx62-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx72-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx31-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx31-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx68-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx68-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx72-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx72-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-NxE: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-NxE
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxC: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxC
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxE: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxE
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxG: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxG
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxH: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxH
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxT: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxT
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PMC8266-FPE: <=PO_61.8.0.4_LPR
Milesight / PMC8266-FPE
<=PO_61.8.0.4_LPR
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PMC8266-FGPE: <=PO_61.8.0.4_LPR
Milesight / PMC8266-FGPE
<=PO_61.8.0.4_LPR
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PM3322-E: <=PI_61.8.0.3_LPR-r3
Milesight / PM3322-E
<=PI_61.8.0.3_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS5366-X12RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-RFIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-RFIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-RFIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-RFIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIWG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIWG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIWG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIWG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5510-GVH: <=T_47.8.0.4_LPR-r7
Milesight / TS5510-GVH
<=T_47.8.0.4_LPR-r7
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5510-GH: <=T_47.8.0.4_LPR-r6
Milesight / TS5510-GH
<=T_47.8.0.4_LPR-r6
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5511-GVH: <=T_47.8.0.4_LPR-r6
Milesight / TS5511-GVH
<=T_47.8.0.4_LPR-r6
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2966-X12TPE: <=T_61.8.0.4_LPR-r3
Milesight / TS2966-X12TPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12PE: <=T_61.8.0.4_LPR-r3
Milesight / TS5366-X12PE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4PE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4PE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2966-X12TVPE: <=T_61.8.0.4_LPR-r3
Milesight / TS2966-X12TVPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RVPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RVPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12VPE: <=T_61.8.0.4_LPR-r3
Milesight / TS5366-X12VPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4VPE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4VPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4441-X36RPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4441-X36RPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4441-X36RE: <=T_61.8.0.4_LPR-r3
Milesight / TS4441-X36RE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RWE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RWE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4WE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4WE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2964-RFLPC: <=T_45.8.0.3-r9
Milesight / MS-C2964-RFLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2972-RFLPC: <=T_45.8.0.3-r9
Milesight / MS-C2972-RFLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-RFLWPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-RFLWPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TVPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TGPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TGPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2841-X36TPC: <=T_45.8.0.3-r9
Milesight / TS2841-X36TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2841-X36TPC/W: <=T_45.8.0.3-r9
Milesight / TS2841-X36TPC/W
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2867-X5TPC: <=T_45.8.0.3-r9
Milesight / TS2867-X5TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2961-X12TPC: <=T_45.8.0.3-r9
Milesight / TS2961-X12TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-FPC/P: <=T_45.8.0.3-r9
Milesight / TS8266-FPC/P
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-X12RLPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-X12RLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-X12RLVPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-X12RLVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5366-X12LPC: <=T_45.8.0.3-r9
Milesight / MS-C5366-X12LPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5366-X12LVPC: <=T_45.8.0.3-r9
Milesight / MS-C5366-X12LVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5361-X12LPC: <=T_45.8.0.3-r9
Milesight / MS-C5361-X12LPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxxGOPC: <=45.8.0.2-AIoT-r4
Milesight / MS-Cxx66-xxxxGOPC
<=45.8.0.2-AIoT-r4
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight SC211: <=C_21.1.0.8-r4
Milesight / SC211
<=C_21.1.0.8-r4
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight SP111: <=52.8.0.4-r5
Milesight / SP111
<=52.8.0.4-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-RFIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx66-RFIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-RFIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx72-RFIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-FIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx66-FIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-FIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx72-FIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
CWE-321 - Use of Hard-coded Cryptographic Key
Affected products
Product Identifier Version Remediation
Milesight MS-Cxx63-PD: <=51.7.0.77-r12
Milesight / MS-Cxx63-PD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx64-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx64-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx73-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx73-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx75-xxPD: <=51.7.0.77-r12
Milesight / MS-Cxx75-xxPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx83-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx83-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx74-PA: <=3x.8.0.3-r11
Milesight / MS-Cxx74-PA
<=3x.8.0.3-r11
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C8477-HPG1: <=63.8.0.4-r3
Milesight / MS-C8477-HPG1
<=63.8.0.4-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C8477-PC: <=48.8.0.4-r3
Milesight / MS-C8477-PC
<=48.8.0.4-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5321-FPE: <=62.8.0.4-r5
Milesight / MS-C5321-FPE
<=62.8.0.4-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx72-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx62-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx62-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx52-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx52-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx66-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxGPE: <=61.8.0.5-r2
Milesight / MS-Cxx66-xxxGPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx61-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx61-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx67-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx67-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx71-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx71-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx41-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx41-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx76-PE: <=61.8.0.5-r2
Milesight / MS-Cxx76-PE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx65-PE: <=61.8.0.5-r2
Milesight / MS-Cxx65-PE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx66-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx62-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx62-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx72-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx31-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx31-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx68-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx68-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx72-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx72-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-NxE: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-NxE
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxC: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxC
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxE: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxE
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxG: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxG
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxH: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxH
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxT: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxT
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PMC8266-FPE: <=PO_61.8.0.4_LPR
Milesight / PMC8266-FPE
<=PO_61.8.0.4_LPR
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PMC8266-FGPE: <=PO_61.8.0.4_LPR
Milesight / PMC8266-FGPE
<=PO_61.8.0.4_LPR
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PM3322-E: <=PI_61.8.0.3_LPR-r3
Milesight / PM3322-E
<=PI_61.8.0.3_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS5366-X12RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-RFIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-RFIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-RFIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-RFIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIWG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIWG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIWG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIWG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5510-GVH: <=T_47.8.0.4_LPR-r7
Milesight / TS5510-GVH
<=T_47.8.0.4_LPR-r7
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5510-GH: <=T_47.8.0.4_LPR-r6
Milesight / TS5510-GH
<=T_47.8.0.4_LPR-r6
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5511-GVH: <=T_47.8.0.4_LPR-r6
Milesight / TS5511-GVH
<=T_47.8.0.4_LPR-r6
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2966-X12TPE: <=T_61.8.0.4_LPR-r3
Milesight / TS2966-X12TPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12PE: <=T_61.8.0.4_LPR-r3
Milesight / TS5366-X12PE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4PE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4PE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2966-X12TVPE: <=T_61.8.0.4_LPR-r3
Milesight / TS2966-X12TVPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RVPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RVPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12VPE: <=T_61.8.0.4_LPR-r3
Milesight / TS5366-X12VPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4VPE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4VPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4441-X36RPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4441-X36RPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4441-X36RE: <=T_61.8.0.4_LPR-r3
Milesight / TS4441-X36RE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RWE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RWE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4WE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4WE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2964-RFLPC: <=T_45.8.0.3-r9
Milesight / MS-C2964-RFLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2972-RFLPC: <=T_45.8.0.3-r9
Milesight / MS-C2972-RFLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-RFLWPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-RFLWPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TVPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TGPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TGPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2841-X36TPC: <=T_45.8.0.3-r9
Milesight / TS2841-X36TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2841-X36TPC/W: <=T_45.8.0.3-r9
Milesight / TS2841-X36TPC/W
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2867-X5TPC: <=T_45.8.0.3-r9
Milesight / TS2867-X5TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2961-X12TPC: <=T_45.8.0.3-r9
Milesight / TS2961-X12TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-FPC/P: <=T_45.8.0.3-r9
Milesight / TS8266-FPC/P
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-X12RLPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-X12RLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-X12RLVPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-X12RLVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5366-X12LPC: <=T_45.8.0.3-r9
Milesight / MS-C5366-X12LPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5366-X12LVPC: <=T_45.8.0.3-r9
Milesight / MS-C5366-X12LVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5361-X12LPC: <=T_45.8.0.3-r9
Milesight / MS-C5361-X12LPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxxGOPC: <=45.8.0.2-AIoT-r4
Milesight / MS-Cxx66-xxxxGOPC
<=45.8.0.2-AIoT-r4
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight SC211: <=C_21.1.0.8-r4
Milesight / SC211
<=C_21.1.0.8-r4
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight SP111: <=52.8.0.4-r5
Milesight / SP111
<=52.8.0.4-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-RFIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx66-RFIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-RFIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx72-RFIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-FIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx66-FIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-FIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx72-FIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
CWE-78 - Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection')
Affected products
Product Identifier Version Remediation
Milesight MS-Cxx63-PD: <=51.7.0.77-r12
Milesight / MS-Cxx63-PD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx64-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx64-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx73-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx73-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx75-xxPD: <=51.7.0.77-r12
Milesight / MS-Cxx75-xxPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx83-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx83-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx74-PA: <=3x.8.0.3-r11
Milesight / MS-Cxx74-PA
<=3x.8.0.3-r11
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C8477-HPG1: <=63.8.0.4-r3
Milesight / MS-C8477-HPG1
<=63.8.0.4-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C8477-PC: <=48.8.0.4-r3
Milesight / MS-C8477-PC
<=48.8.0.4-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5321-FPE: <=62.8.0.4-r5
Milesight / MS-C5321-FPE
<=62.8.0.4-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx72-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx62-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx62-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx52-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx52-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx66-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxGPE: <=61.8.0.5-r2
Milesight / MS-Cxx66-xxxGPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx61-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx61-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx67-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx67-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx71-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx71-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx41-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx41-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx76-PE: <=61.8.0.5-r2
Milesight / MS-Cxx76-PE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx65-PE: <=61.8.0.5-r2
Milesight / MS-Cxx65-PE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx66-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx62-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx62-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx72-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx31-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx31-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx68-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx68-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx72-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx72-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-NxE: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-NxE
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxC: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxC
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxE: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxE
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxG: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxG
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxH: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxH
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxT: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxT
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PMC8266-FPE: <=PO_61.8.0.4_LPR
Milesight / PMC8266-FPE
<=PO_61.8.0.4_LPR
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PMC8266-FGPE: <=PO_61.8.0.4_LPR
Milesight / PMC8266-FGPE
<=PO_61.8.0.4_LPR
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PM3322-E: <=PI_61.8.0.3_LPR-r3
Milesight / PM3322-E
<=PI_61.8.0.3_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS5366-X12RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-RFIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-RFIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-RFIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-RFIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIWG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIWG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIWG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIWG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5510-GVH: <=T_47.8.0.4_LPR-r7
Milesight / TS5510-GVH
<=T_47.8.0.4_LPR-r7
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5510-GH: <=T_47.8.0.4_LPR-r6
Milesight / TS5510-GH
<=T_47.8.0.4_LPR-r6
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5511-GVH: <=T_47.8.0.4_LPR-r6
Milesight / TS5511-GVH
<=T_47.8.0.4_LPR-r6
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2966-X12TPE: <=T_61.8.0.4_LPR-r3
Milesight / TS2966-X12TPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12PE: <=T_61.8.0.4_LPR-r3
Milesight / TS5366-X12PE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4PE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4PE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2966-X12TVPE: <=T_61.8.0.4_LPR-r3
Milesight / TS2966-X12TVPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RVPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RVPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12VPE: <=T_61.8.0.4_LPR-r3
Milesight / TS5366-X12VPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4VPE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4VPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4441-X36RPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4441-X36RPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4441-X36RE: <=T_61.8.0.4_LPR-r3
Milesight / TS4441-X36RE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RWE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RWE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4WE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4WE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2964-RFLPC: <=T_45.8.0.3-r9
Milesight / MS-C2964-RFLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2972-RFLPC: <=T_45.8.0.3-r9
Milesight / MS-C2972-RFLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-RFLWPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-RFLWPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TVPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TGPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TGPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2841-X36TPC: <=T_45.8.0.3-r9
Milesight / TS2841-X36TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2841-X36TPC/W: <=T_45.8.0.3-r9
Milesight / TS2841-X36TPC/W
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2867-X5TPC: <=T_45.8.0.3-r9
Milesight / TS2867-X5TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2961-X12TPC: <=T_45.8.0.3-r9
Milesight / TS2961-X12TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-FPC/P: <=T_45.8.0.3-r9
Milesight / TS8266-FPC/P
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-X12RLPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-X12RLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-X12RLVPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-X12RLVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5366-X12LPC: <=T_45.8.0.3-r9
Milesight / MS-C5366-X12LPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5366-X12LVPC: <=T_45.8.0.3-r9
Milesight / MS-C5366-X12LVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5361-X12LPC: <=T_45.8.0.3-r9
Milesight / MS-C5361-X12LPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxxGOPC: <=45.8.0.2-AIoT-r4
Milesight / MS-Cxx66-xxxxGOPC
<=45.8.0.2-AIoT-r4
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight SC211: <=C_21.1.0.8-r4
Milesight / SC211
<=C_21.1.0.8-r4
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight SP111: <=52.8.0.4-r5
Milesight / SP111
<=52.8.0.4-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-RFIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx66-RFIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-RFIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx72-RFIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-FIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx66-FIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-FIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx72-FIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
CWE-122 - Heap-based Buffer Overflow
Affected products
Product Identifier Version Remediation
Milesight MS-Cxx63-PD: <=51.7.0.77-r12
Milesight / MS-Cxx63-PD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx64-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx64-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx73-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx73-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx75-xxPD: <=51.7.0.77-r12
Milesight / MS-Cxx75-xxPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx83-xPD: <=51.7.0.77-r12
Milesight / MS-Cxx83-xPD
<=51.7.0.77-r12
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx74-PA: <=3x.8.0.3-r11
Milesight / MS-Cxx74-PA
<=3x.8.0.3-r11
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C8477-HPG1: <=63.8.0.4-r3
Milesight / MS-C8477-HPG1
<=63.8.0.4-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C8477-PC: <=48.8.0.4-r3
Milesight / MS-C8477-PC
<=48.8.0.4-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5321-FPE: <=62.8.0.4-r5
Milesight / MS-C5321-FPE
<=62.8.0.4-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx72-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx62-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx62-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx52-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx52-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx66-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxGPE: <=61.8.0.5-r2
Milesight / MS-Cxx66-xxxGPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx61-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx61-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx67-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx67-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx71-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx71-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx41-xxxPE: <=61.8.0.5-r2
Milesight / MS-Cxx41-xxxPE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx76-PE: <=61.8.0.5-r2
Milesight / MS-Cxx76-PE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx65-PE: <=61.8.0.5-r2
Milesight / MS-Cxx65-PE
<=61.8.0.5-r2
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx66-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx62-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx62-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-xxxG1: <=63.8.0.5-r3
Milesight / MS-Cxx72-xxxG1
<=63.8.0.5-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx31-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx31-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx68-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx68-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-CQxx72-xxxG1: <=CQ_63.8.0.5-r1
Milesight / MS-CQxx72-xxxG1
<=CQ_63.8.0.5-r1
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-NxE: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-NxE
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxC: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxC
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxE: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxE
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxG: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxG
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxH: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxH
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Nxxxx-xxT: <=7x.9.0.19-r5
Milesight / MS-Nxxxx-xxT
<=7x.9.0.19-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PMC8266-FPE: <=PO_61.8.0.4_LPR
Milesight / PMC8266-FPE
<=PO_61.8.0.4_LPR
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PMC8266-FGPE: <=PO_61.8.0.4_LPR
Milesight / PMC8266-FGPE
<=PO_61.8.0.4_LPR
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight PM3322-E: <=PI_61.8.0.3_LPR-r3
Milesight / PM3322-E
<=PI_61.8.0.3_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS5366-X12RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-RFIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-RFIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-RFIVPG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-RFIVPG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RIWG1: <=T_63.8.0.4_LPR-r3
Milesight / TS4466-X4RIWG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4RIWG1: <=T_63.8.0.4_LPR-r3
Milesight / TS8266-X4RIWG1
<=T_63.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5510-GVH: <=T_47.8.0.4_LPR-r7
Milesight / TS5510-GVH
<=T_47.8.0.4_LPR-r7
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5510-GH: <=T_47.8.0.4_LPR-r6
Milesight / TS5510-GH
<=T_47.8.0.4_LPR-r6
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5511-GVH: <=T_47.8.0.4_LPR-r6
Milesight / TS5511-GVH
<=T_47.8.0.4_LPR-r6
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2966-X12TPE: <=T_61.8.0.4_LPR-r3
Milesight / TS2966-X12TPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12PE: <=T_61.8.0.4_LPR-r3
Milesight / TS5366-X12PE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4PE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4PE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2966-X12TVPE: <=T_61.8.0.4_LPR-r3
Milesight / TS2966-X12TVPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RVPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RVPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS5366-X12VPE: <=T_61.8.0.4_LPR-r3
Milesight / TS5366-X12VPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4VPE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4VPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4441-X36RPE: <=T_61.8.0.4_LPR-r3
Milesight / TS4441-X36RPE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4441-X36RE: <=T_61.8.0.4_LPR-r3
Milesight / TS4441-X36RE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS4466-X4RWE: <=T_61.8.0.4_LPR-r3
Milesight / TS4466-X4RWE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-X4WE: <=T_61.8.0.4_LPR-r3
Milesight / TS8266-X4WE
<=T_61.8.0.4_LPR-r3
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2964-RFLPC: <=T_45.8.0.3-r9
Milesight / MS-C2964-RFLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2972-RFLPC: <=T_45.8.0.3-r9
Milesight / MS-C2972-RFLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-RFLWPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-RFLWPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TVPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2866-X4TGPC: <=T_45.8.0.3-r9
Milesight / TS2866-X4TGPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2841-X36TPC: <=T_45.8.0.3-r9
Milesight / TS2841-X36TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2841-X36TPC/W: <=T_45.8.0.3-r9
Milesight / TS2841-X36TPC/W
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2867-X5TPC: <=T_45.8.0.3-r9
Milesight / TS2867-X5TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS2961-X12TPC: <=T_45.8.0.3-r9
Milesight / TS2961-X12TPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight TS8266-FPC/P: <=T_45.8.0.3-r9
Milesight / TS8266-FPC/P
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-X12RLPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-X12RLPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C2966-X12RLVPC: <=T_45.8.0.3-r9
Milesight / MS-C2966-X12RLVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5366-X12LPC: <=T_45.8.0.3-r9
Milesight / MS-C5366-X12LPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5366-X12LVPC: <=T_45.8.0.3-r9
Milesight / MS-C5366-X12LVPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-C5361-X12LPC: <=T_45.8.0.3-r9
Milesight / MS-C5361-X12LPC
<=T_45.8.0.3-r9
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-xxxxGOPC: <=45.8.0.2-AIoT-r4
Milesight / MS-Cxx66-xxxxGOPC
<=45.8.0.2-AIoT-r4
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight SC211: <=C_21.1.0.8-r4
Milesight / SC211
<=C_21.1.0.8-r4
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight SP111: <=52.8.0.4-r5
Milesight / SP111
<=52.8.0.4-r5
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-RFIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx66-RFIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-RFIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx72-RFIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx66-FIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx66-FIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
Milesight MS-Cxx72-FIPKG1: <=63.8.0.4-r1-NX
Milesight / MS-Cxx72-FIPKG1
<=63.8.0.4-r1-NX
Mitigation fix
Vendor Fix
Mitigation fix
Mitigation fix
References
URL Category
https://raw.githubusercontent.com/cisagov/CSAF/de… self
https://www.cisa.gov/news-events/ics-advisories/i… self
https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-… external
https://www.cisa.gov/resources-tools/resources/ic… external
https://www.cisa.gov/sites/default/files/publicat… external
https://www.cisa.gov/topics/industrial-control-systems external
https://www.cisa.gov/uscert/sites/default/files/p… external
https://www.cisa.gov/uscert/ncas/tips/ST04-014 external
https://www.cisa.gov/news-events/ics-alerts/ics-a… external
https://www.cisa.gov/sites/default/files/recommen… external
https://www.cisa.gov/news-events/news/targeted-cy… external
https://www.cisa.gov/secure-our-world/teach-emplo… external
https://www.cisa.gov/news-events/news/avoiding-so… external
https://cwe.mitre.org/data/definitions/639.html external
https://www.cve.org/CVERecord?id=CVE-2026-28747 external
https://www.first.org/cvss/calculator/3.1#CVSS:3.… external
https://www.first.org/cvss/calculator/4.0#CVSS:4.… external
https://cwe.mitre.org/data/definitions/798.html external
https://www.cve.org/CVERecord?id=CVE-2026-27785 external
https://www.first.org/cvss/calculator/3.1#CVSS:3.… external
https://www.first.org/cvss/calculator/4.0#CVSS:4.… external
https://cwe.mitre.org/data/definitions/1394.html external
https://www.cve.org/CVERecord?id=CVE-2026-32644 external
https://www.first.org/cvss/calculator/3.1#CVSS:3.… external
https://www.first.org/cvss/calculator/4.0#CVSS:4.… external
https://cwe.mitre.org/data/definitions/78.html external
https://www.cve.org/CVERecord?id=CVE-2026-32649 external
https://www.first.org/cvss/calculator/3.1#CVSS:3.… external
https://www.first.org/cvss/calculator/4.0#CVSS:4.… external
https://cwe.mitre.org/data/definitions/122.html external
https://www.cve.org/CVERecord?id=CVE-2026-20766 external
https://www.first.org/cvss/calculator/3.1#CVSS:3.… external
https://www.first.org/cvss/calculator/4.0#CVSS:4.… external
Acknowledgments
Souvik Kandar

{
  "document": {
    "acknowledgments": [
      {
        "names": [
          "Souvik Kandar"
        ],
        "summary": "reported these vulnerabilities to CISA"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://www.cisa.gov/news-events/news/traffic-light-protocol-tlp-definitions-and-usage"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "legal_disclaimer",
        "text": "This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy \u0026 Use policy (https://www.cisa.gov/privacy-policy).",
        "title": "Legal Notice and Terms of Use"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of these vulnerabilities could crash the device being accessed or allow remote code execution.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Commercial Facilities",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "China",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Locate control system networks and remote devices behind firewalls and isolating them from business networks.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks:",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Do not click web links or open attachments in unsolicited email messages.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.",
        "title": "Recommended Practices"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "central@cisa.dhs.gov",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-26-113-03 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2026/icsa-26-113-03.json"
      },
      {
        "category": "self",
        "summary": "ICSA Advisory ICSA-26-113-03 - Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-26-113-03"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/topics/industrial-control-systems"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/secure-our-world/teach-employees-avoid-phishing"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/news-events/news/avoiding-social-engineering-and-phishing-attacks"
      }
    ],
    "title": "Milesight Cameras",
    "tracking": {
      "current_release_date": "2026-04-23T06:00:00.000000Z",
      "generator": {
        "date": "2026-04-22T15:22:25.851285Z",
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-26-113-03",
      "initial_release_date": "2026-04-23T06:00:00.000000Z",
      "revision_history": [
        {
          "date": "2026-04-23T06:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "Initial Publication"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=51.7.0.77-r12",
                "product": {
                  "name": "Milesight MS-Cxx63-PD: \u003c=51.7.0.77-r12",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx63-PD"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=51.7.0.77-r12",
                "product": {
                  "name": "Milesight MS-Cxx64-xPD: \u003c=51.7.0.77-r12",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx64-xPD"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=51.7.0.77-r12",
                "product": {
                  "name": "Milesight MS-Cxx73-xPD: \u003c=51.7.0.77-r12",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx73-xPD"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=51.7.0.77-r12",
                "product": {
                  "name": "Milesight MS-Cxx75-xxPD: \u003c=51.7.0.77-r12",
                  "product_id": "CSAFPID-0004"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx75-xxPD"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=51.7.0.77-r12",
                "product": {
                  "name": "Milesight MS-Cxx83-xPD: \u003c=51.7.0.77-r12",
                  "product_id": "CSAFPID-0005"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx83-xPD"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=3x.8.0.3-r11",
                "product": {
                  "name": "Milesight MS-Cxx74-PA: \u003c=3x.8.0.3-r11",
                  "product_id": "CSAFPID-0006"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx74-PA"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=63.8.0.4-r3",
                "product": {
                  "name": "Milesight MS-C8477-HPG1: \u003c=63.8.0.4-r3",
                  "product_id": "CSAFPID-0007"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-C8477-HPG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=48.8.0.4-r3",
                "product": {
                  "name": "Milesight MS-C8477-PC: \u003c=48.8.0.4-r3",
                  "product_id": "CSAFPID-0008"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-C8477-PC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=62.8.0.4-r5",
                "product": {
                  "name": "Milesight MS-C5321-FPE: \u003c=62.8.0.4-r5",
                  "product_id": "CSAFPID-0009"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-C5321-FPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=61.8.0.5-r2",
                "product": {
                  "name": "Milesight MS-Cxx72-xxxPE: \u003c=61.8.0.5-r2",
                  "product_id": "CSAFPID-0010"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx72-xxxPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=61.8.0.5-r2",
                "product": {
                  "name": "Milesight MS-Cxx62-xxxPE: \u003c=61.8.0.5-r2",
                  "product_id": "CSAFPID-0011"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx62-xxxPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=61.8.0.5-r2",
                "product": {
                  "name": "Milesight MS-Cxx52-xxxPE: \u003c=61.8.0.5-r2",
                  "product_id": "CSAFPID-0012"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx52-xxxPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=61.8.0.5-r2",
                "product": {
                  "name": "Milesight MS-Cxx66-xxxPE: \u003c=61.8.0.5-r2",
                  "product_id": "CSAFPID-0013"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx66-xxxPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=61.8.0.5-r2",
                "product": {
                  "name": "Milesight MS-Cxx66-xxxGPE: \u003c=61.8.0.5-r2",
                  "product_id": "CSAFPID-0014"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx66-xxxGPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=61.8.0.5-r2",
                "product": {
                  "name": "Milesight MS-Cxx61-xxxPE: \u003c=61.8.0.5-r2",
                  "product_id": "CSAFPID-0015"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx61-xxxPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=61.8.0.5-r2",
                "product": {
                  "name": "Milesight MS-Cxx67-xxxPE: \u003c=61.8.0.5-r2",
                  "product_id": "CSAFPID-0016"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx67-xxxPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=61.8.0.5-r2",
                "product": {
                  "name": "Milesight MS-Cxx71-xxxPE: \u003c=61.8.0.5-r2",
                  "product_id": "CSAFPID-0017"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx71-xxxPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=61.8.0.5-r2",
                "product": {
                  "name": "Milesight MS-Cxx41-xxxPE: \u003c=61.8.0.5-r2",
                  "product_id": "CSAFPID-0018"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx41-xxxPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=61.8.0.5-r2",
                "product": {
                  "name": "Milesight MS-Cxx76-PE: \u003c=61.8.0.5-r2",
                  "product_id": "CSAFPID-0019"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx76-PE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=61.8.0.5-r2",
                "product": {
                  "name": "Milesight MS-Cxx65-PE: \u003c=61.8.0.5-r2",
                  "product_id": "CSAFPID-0020"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx65-PE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=63.8.0.5-r3",
                "product": {
                  "name": "Milesight MS-Cxx66-xxxG1: \u003c=63.8.0.5-r3",
                  "product_id": "CSAFPID-0021"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx66-xxxG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=63.8.0.5-r3",
                "product": {
                  "name": "Milesight MS-Cxx62-xxxG1: \u003c=63.8.0.5-r3",
                  "product_id": "CSAFPID-0022"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx62-xxxG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=63.8.0.5-r3",
                "product": {
                  "name": "Milesight MS-Cxx72-xxxG1: \u003c=63.8.0.5-r3",
                  "product_id": "CSAFPID-0023"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx72-xxxG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=CQ_63.8.0.5-r1",
                "product": {
                  "name": "Milesight MS-CQxx31-xxxG1: \u003c=CQ_63.8.0.5-r1",
                  "product_id": "CSAFPID-0024"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-CQxx31-xxxG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=CQ_63.8.0.5-r1",
                "product": {
                  "name": "Milesight MS-CQxx68-xxxG1: \u003c=CQ_63.8.0.5-r1",
                  "product_id": "CSAFPID-0025"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-CQxx68-xxxG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=CQ_63.8.0.5-r1",
                "product": {
                  "name": "Milesight MS-CQxx72-xxxG1: \u003c=CQ_63.8.0.5-r1",
                  "product_id": "CSAFPID-0026"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-CQxx72-xxxG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=7x.9.0.19-r5",
                "product": {
                  "name": "Milesight MS-Nxxxx-NxE: \u003c=7x.9.0.19-r5",
                  "product_id": "CSAFPID-0027"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Nxxxx-NxE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=7x.9.0.19-r5",
                "product": {
                  "name": "Milesight MS-Nxxxx-xxC: \u003c=7x.9.0.19-r5",
                  "product_id": "CSAFPID-0028"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Nxxxx-xxC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=7x.9.0.19-r5",
                "product": {
                  "name": "Milesight MS-Nxxxx-xxE: \u003c=7x.9.0.19-r5",
                  "product_id": "CSAFPID-0029"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Nxxxx-xxE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=7x.9.0.19-r5",
                "product": {
                  "name": "Milesight MS-Nxxxx-xxG: \u003c=7x.9.0.19-r5",
                  "product_id": "CSAFPID-0030"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Nxxxx-xxG"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=7x.9.0.19-r5",
                "product": {
                  "name": "Milesight MS-Nxxxx-xxH: \u003c=7x.9.0.19-r5",
                  "product_id": "CSAFPID-0031"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Nxxxx-xxH"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=7x.9.0.19-r5",
                "product": {
                  "name": "Milesight MS-Nxxxx-xxT: \u003c=7x.9.0.19-r5",
                  "product_id": "CSAFPID-0032"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Nxxxx-xxT"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=PO_61.8.0.4_LPR",
                "product": {
                  "name": "Milesight PMC8266-FPE: \u003c=PO_61.8.0.4_LPR",
                  "product_id": "CSAFPID-0033"
                }
              }
            ],
            "category": "product_name",
            "name": "PMC8266-FPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=PO_61.8.0.4_LPR",
                "product": {
                  "name": "Milesight PMC8266-FGPE: \u003c=PO_61.8.0.4_LPR",
                  "product_id": "CSAFPID-0034"
                }
              }
            ],
            "category": "product_name",
            "name": "PMC8266-FGPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=PI_61.8.0.3_LPR-r3",
                "product": {
                  "name": "Milesight PM3322-E: \u003c=PI_61.8.0.3_LPR-r3",
                  "product_id": "CSAFPID-0035"
                }
              }
            ],
            "category": "product_name",
            "name": "PM3322-E"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_63.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS4466-X4RIPG1: \u003c=T_63.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0036"
                }
              }
            ],
            "category": "product_name",
            "name": "TS4466-X4RIPG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_63.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS5366-X12RIPG1: \u003c=T_63.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0037"
                }
              }
            ],
            "category": "product_name",
            "name": "TS5366-X12RIPG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_63.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS8266-X4RIPG1: \u003c=T_63.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0038"
                }
              }
            ],
            "category": "product_name",
            "name": "TS8266-X4RIPG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_63.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS4466-X4RIVPG1: \u003c=T_63.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0039"
                }
              }
            ],
            "category": "product_name",
            "name": "TS4466-X4RIVPG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_63.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS4466-RFIVPG1: \u003c=T_63.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0040"
                }
              }
            ],
            "category": "product_name",
            "name": "TS4466-RFIVPG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_63.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS8266-X4RIVPG1: \u003c=T_63.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0041"
                }
              }
            ],
            "category": "product_name",
            "name": "TS8266-X4RIVPG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_63.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS8266-RFIVPG1: \u003c=T_63.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0042"
                }
              }
            ],
            "category": "product_name",
            "name": "TS8266-RFIVPG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_63.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS4466-X4RIWG1: \u003c=T_63.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0043"
                }
              }
            ],
            "category": "product_name",
            "name": "TS4466-X4RIWG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_63.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS8266-X4RIWG1: \u003c=T_63.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0044"
                }
              }
            ],
            "category": "product_name",
            "name": "TS8266-X4RIWG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_47.8.0.4_LPR-r7",
                "product": {
                  "name": "Milesight TS5510-GVH: \u003c=T_47.8.0.4_LPR-r7",
                  "product_id": "CSAFPID-0045"
                }
              }
            ],
            "category": "product_name",
            "name": "TS5510-GVH"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_47.8.0.4_LPR-r6",
                "product": {
                  "name": "Milesight TS5510-GH: \u003c=T_47.8.0.4_LPR-r6",
                  "product_id": "CSAFPID-0046"
                }
              }
            ],
            "category": "product_name",
            "name": "TS5510-GH"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_47.8.0.4_LPR-r6",
                "product": {
                  "name": "Milesight TS5511-GVH: \u003c=T_47.8.0.4_LPR-r6",
                  "product_id": "CSAFPID-0047"
                }
              }
            ],
            "category": "product_name",
            "name": "TS5511-GVH"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_61.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS2966-X12TPE: \u003c=T_61.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0048"
                }
              }
            ],
            "category": "product_name",
            "name": "TS2966-X12TPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_61.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS4466-X4RPE: \u003c=T_61.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0049"
                }
              }
            ],
            "category": "product_name",
            "name": "TS4466-X4RPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_61.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS5366-X12PE: \u003c=T_61.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0050"
                }
              }
            ],
            "category": "product_name",
            "name": "TS5366-X12PE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_61.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS8266-X4PE: \u003c=T_61.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0051"
                }
              }
            ],
            "category": "product_name",
            "name": "TS8266-X4PE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_61.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS2966-X12TVPE: \u003c=T_61.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0052"
                }
              }
            ],
            "category": "product_name",
            "name": "TS2966-X12TVPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_61.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS4466-X4RVPE: \u003c=T_61.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0053"
                }
              }
            ],
            "category": "product_name",
            "name": "TS4466-X4RVPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_61.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS5366-X12VPE: \u003c=T_61.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0054"
                }
              }
            ],
            "category": "product_name",
            "name": "TS5366-X12VPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_61.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS8266-X4VPE: \u003c=T_61.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0055"
                }
              }
            ],
            "category": "product_name",
            "name": "TS8266-X4VPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_61.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS4441-X36RPE: \u003c=T_61.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0056"
                }
              }
            ],
            "category": "product_name",
            "name": "TS4441-X36RPE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_61.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS4441-X36RE: \u003c=T_61.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0057"
                }
              }
            ],
            "category": "product_name",
            "name": "TS4441-X36RE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_61.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS4466-X4RWE: \u003c=T_61.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0058"
                }
              }
            ],
            "category": "product_name",
            "name": "TS4466-X4RWE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_61.8.0.4_LPR-r3",
                "product": {
                  "name": "Milesight TS8266-X4WE: \u003c=T_61.8.0.4_LPR-r3",
                  "product_id": "CSAFPID-0059"
                }
              }
            ],
            "category": "product_name",
            "name": "TS8266-X4WE"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight MS-C2964-RFLPC: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0060"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-C2964-RFLPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight MS-C2972-RFLPC: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0061"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-C2972-RFLPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight MS-C2966-RFLWPC: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0062"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-C2966-RFLWPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight TS2866-X4TPC: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0063"
                }
              }
            ],
            "category": "product_name",
            "name": "TS2866-X4TPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight TS2866-X4TVPC: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0064"
                }
              }
            ],
            "category": "product_name",
            "name": "TS2866-X4TVPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight TS2866-X4TGPC: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0065"
                }
              }
            ],
            "category": "product_name",
            "name": "TS2866-X4TGPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight TS2841-X36TPC: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0066"
                }
              }
            ],
            "category": "product_name",
            "name": "TS2841-X36TPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight TS2841-X36TPC/W: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0067"
                }
              }
            ],
            "category": "product_name",
            "name": "TS2841-X36TPC/W"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight TS2867-X5TPC: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0068"
                }
              }
            ],
            "category": "product_name",
            "name": "TS2867-X5TPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight TS2961-X12TPC: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0069"
                }
              }
            ],
            "category": "product_name",
            "name": "TS2961-X12TPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight TS8266-FPC/P: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0070"
                }
              }
            ],
            "category": "product_name",
            "name": "TS8266-FPC/P"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight MS-C2966-X12RLPC: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0071"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-C2966-X12RLPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight MS-C2966-X12RLVPC: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0072"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-C2966-X12RLVPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight MS-C5366-X12LPC: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0073"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-C5366-X12LPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight MS-C5366-X12LVPC: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0074"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-C5366-X12LVPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=T_45.8.0.3-r9",
                "product": {
                  "name": "Milesight MS-C5361-X12LPC: \u003c=T_45.8.0.3-r9",
                  "product_id": "CSAFPID-0075"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-C5361-X12LPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=45.8.0.2-AIoT-r4",
                "product": {
                  "name": "Milesight MS-Cxx66-xxxxGOPC: \u003c=45.8.0.2-AIoT-r4",
                  "product_id": "CSAFPID-0076"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx66-xxxxGOPC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=C_21.1.0.8-r4",
                "product": {
                  "name": "Milesight SC211: \u003c=C_21.1.0.8-r4",
                  "product_id": "CSAFPID-0077"
                }
              }
            ],
            "category": "product_name",
            "name": "SC211"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=52.8.0.4-r5",
                "product": {
                  "name": "Milesight SP111: \u003c=52.8.0.4-r5",
                  "product_id": "CSAFPID-0078"
                }
              }
            ],
            "category": "product_name",
            "name": "SP111"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=63.8.0.4-r1-NX",
                "product": {
                  "name": "Milesight MS-Cxx66-RFIPKG1: \u003c=63.8.0.4-r1-NX",
                  "product_id": "CSAFPID-0079"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx66-RFIPKG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=63.8.0.4-r1-NX",
                "product": {
                  "name": "Milesight MS-Cxx72-RFIPKG1: \u003c=63.8.0.4-r1-NX",
                  "product_id": "CSAFPID-0080"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx72-RFIPKG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=63.8.0.4-r1-NX",
                "product": {
                  "name": "Milesight MS-Cxx66-FIPKG1: \u003c=63.8.0.4-r1-NX",
                  "product_id": "CSAFPID-0081"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx66-FIPKG1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=63.8.0.4-r1-NX",
                "product": {
                  "name": "Milesight MS-Cxx72-FIPKG1: \u003c=63.8.0.4-r1-NX",
                  "product_id": "CSAFPID-0082"
                }
              }
            ],
            "category": "product_name",
            "name": "MS-Cxx72-FIPKG1"
          }
        ],
        "category": "vendor",
        "name": "Milesight"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2026-28747",
      "cwe": {
        "id": "CWE-639",
        "name": "Authorization Bypass Through User-Controlled Key"
      },
      "notes": [
        {
          "category": "summary",
          "text": "A weak key generation vulnerability exists in specific firmware versions of Milesight AIOT cameras.",
          "title": "Vulnerability Summary"
        },
        {
          "category": "details",
          "text": "SSVCv2/E:P/A:Y/2026-04-22T06:00:00.000000Z",
          "title": "SSVC"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009",
          "CSAFPID-0010",
          "CSAFPID-0011",
          "CSAFPID-0012",
          "CSAFPID-0013",
          "CSAFPID-0014",
          "CSAFPID-0015",
          "CSAFPID-0016",
          "CSAFPID-0017",
          "CSAFPID-0018",
          "CSAFPID-0019",
          "CSAFPID-0020",
          "CSAFPID-0021",
          "CSAFPID-0022",
          "CSAFPID-0023",
          "CSAFPID-0024",
          "CSAFPID-0025",
          "CSAFPID-0026",
          "CSAFPID-0027",
          "CSAFPID-0028",
          "CSAFPID-0029",
          "CSAFPID-0030",
          "CSAFPID-0031",
          "CSAFPID-0032",
          "CSAFPID-0033",
          "CSAFPID-0034",
          "CSAFPID-0035",
          "CSAFPID-0036",
          "CSAFPID-0037",
          "CSAFPID-0038",
          "CSAFPID-0039",
          "CSAFPID-0040",
          "CSAFPID-0041",
          "CSAFPID-0042",
          "CSAFPID-0043",
          "CSAFPID-0044",
          "CSAFPID-0045",
          "CSAFPID-0046",
          "CSAFPID-0047",
          "CSAFPID-0048",
          "CSAFPID-0049",
          "CSAFPID-0050",
          "CSAFPID-0051",
          "CSAFPID-0052",
          "CSAFPID-0053",
          "CSAFPID-0054",
          "CSAFPID-0055",
          "CSAFPID-0056",
          "CSAFPID-0057",
          "CSAFPID-0058",
          "CSAFPID-0059",
          "CSAFPID-0060",
          "CSAFPID-0061",
          "CSAFPID-0062",
          "CSAFPID-0063",
          "CSAFPID-0064",
          "CSAFPID-0065",
          "CSAFPID-0066",
          "CSAFPID-0067",
          "CSAFPID-0068",
          "CSAFPID-0069",
          "CSAFPID-0070",
          "CSAFPID-0071",
          "CSAFPID-0072",
          "CSAFPID-0073",
          "CSAFPID-0074",
          "CSAFPID-0075",
          "CSAFPID-0076",
          "CSAFPID-0077",
          "CSAFPID-0078",
          "CSAFPID-0079",
          "CSAFPID-0080",
          "CSAFPID-0081",
          "CSAFPID-0082"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "cwe.mitre.org",
          "url": "https://cwe.mitre.org/data/definitions/639.html"
        },
        {
          "category": "external",
          "summary": "www.cve.org",
          "url": "https://www.cve.org/CVERecord?id=CVE-2026-28747"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:A/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:A/AC:H/AT:P/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Milesight advises all users to update their device to the latest firmware versions of PE/PC/PA found at https://www.milesight.com/support/download/firmware. ",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "https://www.milesight.com/support/download/firmware"
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx63-PD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx64-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx73-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx75-xxPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0004"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx83-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0005"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx74-PA: 3x.8.0.3-r11 and prior versions: Update to 3x.8.0.3-r13",
          "product_ids": [
            "CSAFPID-0006"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C8477-HPG1: 63.8.0.4-r3 and prior versions: Update to 63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0007"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C8477-PC: 48.8.0.4-r3 and prior versions: Update to 48.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0008"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5321-FPE: 62.8.0.4-r5 and prior versions: Update to 62.8.0.4-r6",
          "product_ids": [
            "CSAFPID-0009"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0010"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx62-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0011"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx52-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0012"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0013"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxGPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0014"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx61-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0015"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx67-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0016"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx71-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0017"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx41-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0018"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx76-PE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0019"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx65-PE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0020"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxG1: 63.8.0.5-r3 and prior versions: Update to 63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0021"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx62-xxxG1: 63.8.0.5-r3 and prior versions: Update to    63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0022"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-xxxG1: 63.8.0.5-r3 and prior versions: Update to 63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0023"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx31-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0024"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx68-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0025"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx72-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0026"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-NxE: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0027"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxC: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0028"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxE: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0029"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxG: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0030"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxH: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0031"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxT: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0032"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PMC8266-FPE: PO_61.8.0.4_LPR and prior versions: Update to PO_61.8.0.4-r1",
          "product_ids": [
            "CSAFPID-0033"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PMC8266-FGPE: PO_61.8.0.4_LPR and prior versions: Update to PO_61.8.0.4-r1",
          "product_ids": [
            "CSAFPID-0034"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PM3322-E: PI_61.8.0.3_LPR-r3 and prior versions: Update to PI_61.8.0.3-r5",
          "product_ids": [
            "CSAFPID-0035"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0036"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0037"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0038"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0039"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-RFIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0040"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0041"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-RFIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0042"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIWG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0043"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIWG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0044"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5510-GVH: T_47.8.0.4_LPR-r7 and prior versions: Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0045"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5510-GH: T_47.8.0.4_LPR-r6 and prior versions    : Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0046"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5511-GVH: T_47.8.0.4_LPR-r6 and prior versions: Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0047"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2966-X12TPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0048"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0049"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12PE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0050"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4PE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0051"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2966-X12TVPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0052"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RVPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0053"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12VPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0054"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4VPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0055"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4441-X36RPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0056"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4441-X36RE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0057"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RWE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0058"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4WE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0059"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2964-RFLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0060"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2972-RFLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0061"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-RFLWPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0062"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0063"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0064"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TGPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0065"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2841-X36TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0066"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2841-X36TPC/W: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0066",
            "CSAFPID-0067"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2867-X5TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0068"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2961-X12TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0069"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-FPC/P: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0070"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-X12RLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0071"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-X12RLVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0072"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5366-X12LPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0073"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5366-X12LVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0074"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5361-X12LPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0075"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxxGOPC    : 45.8.0.2-AIoT-r4 and prior versions: Update to 45.8.0.2-AIoT-r5",
          "product_ids": [
            "CSAFPID-0076"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "SC211: C_21.1.0.8-r4 and prior versions: Update to C_21.1.0.8-r5",
          "product_ids": [
            "CSAFPID-0077"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "SP111: 52.8.0.4-r5 and prior versions: Update to 52.8.0.4-r6",
          "product_ids": [
            "CSAFPID-0078"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-RFIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0079"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-RFIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0080"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-FIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0081"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-FIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0082"
          ]
        },
        {
          "category": "mitigation",
          "details": "Milesight asks all users to report potential security vulnerabilities to security@milesight.com.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "mailto:security@milesight.com"
        },
        {
          "category": "mitigation",
          "details": "Learn more: Milesight Vulnerability Reporting Policy",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "https://www.milesight.com/legal/vulnerability-report"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.1,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:A/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2026-27785",
      "cwe": {
        "id": "CWE-798",
        "name": "Use of Hard-coded Credentials"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Specific firmware versions of Milesight AIOT camera firmware contain hard-coded credentials.",
          "title": "Vulnerability Summary"
        },
        {
          "category": "details",
          "text": "SSVCv2/E:P/A:Y/2026-04-22T06:00:00.000000Z",
          "title": "SSVC"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009",
          "CSAFPID-0010",
          "CSAFPID-0011",
          "CSAFPID-0012",
          "CSAFPID-0013",
          "CSAFPID-0014",
          "CSAFPID-0015",
          "CSAFPID-0016",
          "CSAFPID-0017",
          "CSAFPID-0018",
          "CSAFPID-0019",
          "CSAFPID-0020",
          "CSAFPID-0021",
          "CSAFPID-0022",
          "CSAFPID-0023",
          "CSAFPID-0024",
          "CSAFPID-0025",
          "CSAFPID-0026",
          "CSAFPID-0027",
          "CSAFPID-0028",
          "CSAFPID-0029",
          "CSAFPID-0030",
          "CSAFPID-0031",
          "CSAFPID-0032",
          "CSAFPID-0033",
          "CSAFPID-0034",
          "CSAFPID-0035",
          "CSAFPID-0036",
          "CSAFPID-0037",
          "CSAFPID-0038",
          "CSAFPID-0039",
          "CSAFPID-0040",
          "CSAFPID-0041",
          "CSAFPID-0042",
          "CSAFPID-0043",
          "CSAFPID-0044",
          "CSAFPID-0045",
          "CSAFPID-0046",
          "CSAFPID-0047",
          "CSAFPID-0048",
          "CSAFPID-0049",
          "CSAFPID-0050",
          "CSAFPID-0051",
          "CSAFPID-0052",
          "CSAFPID-0053",
          "CSAFPID-0054",
          "CSAFPID-0055",
          "CSAFPID-0056",
          "CSAFPID-0057",
          "CSAFPID-0058",
          "CSAFPID-0059",
          "CSAFPID-0060",
          "CSAFPID-0061",
          "CSAFPID-0062",
          "CSAFPID-0063",
          "CSAFPID-0064",
          "CSAFPID-0065",
          "CSAFPID-0066",
          "CSAFPID-0067",
          "CSAFPID-0068",
          "CSAFPID-0069",
          "CSAFPID-0070",
          "CSAFPID-0071",
          "CSAFPID-0072",
          "CSAFPID-0073",
          "CSAFPID-0074",
          "CSAFPID-0075",
          "CSAFPID-0076",
          "CSAFPID-0077",
          "CSAFPID-0078",
          "CSAFPID-0079",
          "CSAFPID-0080",
          "CSAFPID-0081",
          "CSAFPID-0082"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "cwe.mitre.org",
          "url": "https://cwe.mitre.org/data/definitions/798.html"
        },
        {
          "category": "external",
          "summary": "www.cve.org",
          "url": "https://www.cve.org/CVERecord?id=CVE-2026-27785"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Milesight advises all users to update their device to the latest firmware versions of PE/PC/PA found at https://www.milesight.com/support/download/firmware. ",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "https://www.milesight.com/support/download/firmware"
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx63-PD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx64-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx73-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx75-xxPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0004"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx83-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0005"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx74-PA: 3x.8.0.3-r11 and prior versions: Update to 3x.8.0.3-r13",
          "product_ids": [
            "CSAFPID-0006"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C8477-HPG1: 63.8.0.4-r3 and prior versions: Update to 63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0007"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C8477-PC: 48.8.0.4-r3 and prior versions: Update to 48.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0008"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5321-FPE: 62.8.0.4-r5 and prior versions: Update to 62.8.0.4-r6",
          "product_ids": [
            "CSAFPID-0009"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0010"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx62-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0011"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx52-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0012"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0013"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxGPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0014"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx61-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0015"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx67-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0016"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx71-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0017"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx41-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0018"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx76-PE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0019"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx65-PE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0020"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxG1: 63.8.0.5-r3 and prior versions: Update to 63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0021"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx62-xxxG1: 63.8.0.5-r3 and prior versions: Update to    63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0022"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-xxxG1: 63.8.0.5-r3 and prior versions: Update to 63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0023"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx31-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0024"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx68-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0025"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx72-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0026"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-NxE: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0027"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxC: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0028"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxE: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0029"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxG: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0030"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxH: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0031"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxT: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0032"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PMC8266-FPE: PO_61.8.0.4_LPR and prior versions: Update to PO_61.8.0.4-r1",
          "product_ids": [
            "CSAFPID-0033"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PMC8266-FGPE: PO_61.8.0.4_LPR and prior versions: Update to PO_61.8.0.4-r1",
          "product_ids": [
            "CSAFPID-0034"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PM3322-E: PI_61.8.0.3_LPR-r3 and prior versions: Update to PI_61.8.0.3-r5",
          "product_ids": [
            "CSAFPID-0035"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0036"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0037"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0038"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0039"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-RFIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0040"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0041"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-RFIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0042"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIWG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0043"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIWG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0044"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5510-GVH: T_47.8.0.4_LPR-r7 and prior versions: Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0045"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5510-GH: T_47.8.0.4_LPR-r6 and prior versions    : Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0046"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5511-GVH: T_47.8.0.4_LPR-r6 and prior versions: Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0047"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2966-X12TPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0048"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0049"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12PE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0050"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4PE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0051"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2966-X12TVPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0052"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RVPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0053"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12VPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0054"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4VPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0055"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4441-X36RPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0056"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4441-X36RE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0057"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RWE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0058"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4WE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0059"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2964-RFLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0060"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2972-RFLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0061"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-RFLWPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0062"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0063"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0064"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TGPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0065"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2841-X36TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0066"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2841-X36TPC/W: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0066",
            "CSAFPID-0067"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2867-X5TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0068"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2961-X12TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0069"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-FPC/P: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0070"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-X12RLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0071"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-X12RLVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0072"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5366-X12LPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0073"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5366-X12LVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0074"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5361-X12LPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0075"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxxGOPC    : 45.8.0.2-AIoT-r4 and prior versions: Update to 45.8.0.2-AIoT-r5",
          "product_ids": [
            "CSAFPID-0076"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "SC211: C_21.1.0.8-r4 and prior versions: Update to C_21.1.0.8-r5",
          "product_ids": [
            "CSAFPID-0077"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "SP111: 52.8.0.4-r5 and prior versions: Update to 52.8.0.4-r6",
          "product_ids": [
            "CSAFPID-0078"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-RFIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0079"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-RFIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0080"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-FIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0081"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-FIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0082"
          ]
        },
        {
          "category": "mitigation",
          "details": "Milesight asks all users to report potential security vulnerabilities to security@milesight.com.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "mailto:security@milesight.com"
        },
        {
          "category": "mitigation",
          "details": "Learn more: Milesight Vulnerability Reporting Policy",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "https://www.milesight.com/legal/vulnerability-report"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.8,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2026-32644",
      "cwe": {
        "id": "CWE-321",
        "name": "Use of Hard-coded Cryptographic Key"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Specific firmware versions of Milesight AIOT cameras use SSL certificates with default private keys.",
          "title": "Vulnerability Summary"
        },
        {
          "category": "details",
          "text": "SSVCv2/E:P/A:Y/2026-04-22T06:00:00.000000Z",
          "title": "SSVC"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009",
          "CSAFPID-0010",
          "CSAFPID-0011",
          "CSAFPID-0012",
          "CSAFPID-0013",
          "CSAFPID-0014",
          "CSAFPID-0015",
          "CSAFPID-0016",
          "CSAFPID-0017",
          "CSAFPID-0018",
          "CSAFPID-0019",
          "CSAFPID-0020",
          "CSAFPID-0021",
          "CSAFPID-0022",
          "CSAFPID-0023",
          "CSAFPID-0024",
          "CSAFPID-0025",
          "CSAFPID-0026",
          "CSAFPID-0027",
          "CSAFPID-0028",
          "CSAFPID-0029",
          "CSAFPID-0030",
          "CSAFPID-0031",
          "CSAFPID-0032",
          "CSAFPID-0033",
          "CSAFPID-0034",
          "CSAFPID-0035",
          "CSAFPID-0036",
          "CSAFPID-0037",
          "CSAFPID-0038",
          "CSAFPID-0039",
          "CSAFPID-0040",
          "CSAFPID-0041",
          "CSAFPID-0042",
          "CSAFPID-0043",
          "CSAFPID-0044",
          "CSAFPID-0045",
          "CSAFPID-0046",
          "CSAFPID-0047",
          "CSAFPID-0048",
          "CSAFPID-0049",
          "CSAFPID-0050",
          "CSAFPID-0051",
          "CSAFPID-0052",
          "CSAFPID-0053",
          "CSAFPID-0054",
          "CSAFPID-0055",
          "CSAFPID-0056",
          "CSAFPID-0057",
          "CSAFPID-0058",
          "CSAFPID-0059",
          "CSAFPID-0060",
          "CSAFPID-0061",
          "CSAFPID-0062",
          "CSAFPID-0063",
          "CSAFPID-0064",
          "CSAFPID-0065",
          "CSAFPID-0066",
          "CSAFPID-0067",
          "CSAFPID-0068",
          "CSAFPID-0069",
          "CSAFPID-0070",
          "CSAFPID-0071",
          "CSAFPID-0072",
          "CSAFPID-0073",
          "CSAFPID-0074",
          "CSAFPID-0075",
          "CSAFPID-0076",
          "CSAFPID-0077",
          "CSAFPID-0078",
          "CSAFPID-0079",
          "CSAFPID-0080",
          "CSAFPID-0081",
          "CSAFPID-0082"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "cwe.mitre.org",
          "url": "https://cwe.mitre.org/data/definitions/1394.html"
        },
        {
          "category": "external",
          "summary": "www.cve.org",
          "url": "https://www.cve.org/CVERecord?id=CVE-2026-32644"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Milesight advises all users to update their device to the latest firmware versions of PE/PC/PA found at https://www.milesight.com/support/download/firmware. ",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "https://www.milesight.com/support/download/firmware"
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx63-PD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx64-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx73-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx75-xxPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0004"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx83-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0005"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx74-PA: 3x.8.0.3-r11 and prior versions: Update to 3x.8.0.3-r13",
          "product_ids": [
            "CSAFPID-0006"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C8477-HPG1: 63.8.0.4-r3 and prior versions: Update to 63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0007"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C8477-PC: 48.8.0.4-r3 and prior versions: Update to 48.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0008"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5321-FPE: 62.8.0.4-r5 and prior versions: Update to 62.8.0.4-r6",
          "product_ids": [
            "CSAFPID-0009"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0010"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx62-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0011"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx52-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0012"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0013"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxGPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0014"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx61-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0015"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx67-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0016"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx71-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0017"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx41-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0018"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx76-PE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0019"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx65-PE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0020"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxG1: 63.8.0.5-r3 and prior versions: Update to 63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0021"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx62-xxxG1: 63.8.0.5-r3 and prior versions: Update to    63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0022"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-xxxG1: 63.8.0.5-r3 and prior versions: Update to 63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0023"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx31-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0024"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx68-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0025"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx72-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0026"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-NxE: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0027"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxC: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0028"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxE: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0029"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxG: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0030"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxH: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0031"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxT: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0032"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PMC8266-FPE: PO_61.8.0.4_LPR and prior versions: Update to PO_61.8.0.4-r1",
          "product_ids": [
            "CSAFPID-0033"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PMC8266-FGPE: PO_61.8.0.4_LPR and prior versions: Update to PO_61.8.0.4-r1",
          "product_ids": [
            "CSAFPID-0034"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PM3322-E: PI_61.8.0.3_LPR-r3 and prior versions: Update to PI_61.8.0.3-r5",
          "product_ids": [
            "CSAFPID-0035"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0036"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0037"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0038"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0039"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-RFIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0040"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0041"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-RFIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0042"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIWG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0043"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIWG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0044"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5510-GVH: T_47.8.0.4_LPR-r7 and prior versions: Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0045"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5510-GH: T_47.8.0.4_LPR-r6 and prior versions    : Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0046"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5511-GVH: T_47.8.0.4_LPR-r6 and prior versions: Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0047"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2966-X12TPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0048"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0049"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12PE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0050"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4PE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0051"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2966-X12TVPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0052"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RVPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0053"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12VPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0054"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4VPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0055"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4441-X36RPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0056"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4441-X36RE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0057"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RWE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0058"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4WE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0059"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2964-RFLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0060"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2972-RFLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0061"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-RFLWPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0062"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0063"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0064"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TGPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0065"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2841-X36TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0066"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2841-X36TPC/W: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0066",
            "CSAFPID-0067"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2867-X5TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0068"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2961-X12TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0069"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-FPC/P: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0070"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-X12RLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0071"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-X12RLVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0072"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5366-X12LPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0073"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5366-X12LVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0074"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5361-X12LPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0075"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxxGOPC    : 45.8.0.2-AIoT-r4 and prior versions: Update to 45.8.0.2-AIoT-r5",
          "product_ids": [
            "CSAFPID-0076"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "SC211: C_21.1.0.8-r4 and prior versions: Update to C_21.1.0.8-r5",
          "product_ids": [
            "CSAFPID-0077"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "SP111: 52.8.0.4-r5 and prior versions: Update to 52.8.0.4-r6",
          "product_ids": [
            "CSAFPID-0078"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-RFIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0079"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-RFIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0080"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-FIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0081"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-FIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0082"
          ]
        },
        {
          "category": "mitigation",
          "details": "Milesight asks all users to report potential security vulnerabilities to security@milesight.com.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "mailto:security@milesight.com"
        },
        {
          "category": "mitigation",
          "details": "Learn more: Milesight Vulnerability Reporting Policy",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "https://www.milesight.com/legal/vulnerability-report"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2026-32649",
      "cwe": {
        "id": "CWE-78",
        "name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "A command injection vulnerability exists in the web server of specific firmware versions of Milesight cameras.",
          "title": "Vulnerability Summary"
        },
        {
          "category": "details",
          "text": "SSVCv2/E:P/A:Y/2026-04-22T06:00:00.000000Z",
          "title": "SSVC"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009",
          "CSAFPID-0010",
          "CSAFPID-0011",
          "CSAFPID-0012",
          "CSAFPID-0013",
          "CSAFPID-0014",
          "CSAFPID-0015",
          "CSAFPID-0016",
          "CSAFPID-0017",
          "CSAFPID-0018",
          "CSAFPID-0019",
          "CSAFPID-0020",
          "CSAFPID-0021",
          "CSAFPID-0022",
          "CSAFPID-0023",
          "CSAFPID-0024",
          "CSAFPID-0025",
          "CSAFPID-0026",
          "CSAFPID-0027",
          "CSAFPID-0028",
          "CSAFPID-0029",
          "CSAFPID-0030",
          "CSAFPID-0031",
          "CSAFPID-0032",
          "CSAFPID-0033",
          "CSAFPID-0034",
          "CSAFPID-0035",
          "CSAFPID-0036",
          "CSAFPID-0037",
          "CSAFPID-0038",
          "CSAFPID-0039",
          "CSAFPID-0040",
          "CSAFPID-0041",
          "CSAFPID-0042",
          "CSAFPID-0043",
          "CSAFPID-0044",
          "CSAFPID-0045",
          "CSAFPID-0046",
          "CSAFPID-0047",
          "CSAFPID-0048",
          "CSAFPID-0049",
          "CSAFPID-0050",
          "CSAFPID-0051",
          "CSAFPID-0052",
          "CSAFPID-0053",
          "CSAFPID-0054",
          "CSAFPID-0055",
          "CSAFPID-0056",
          "CSAFPID-0057",
          "CSAFPID-0058",
          "CSAFPID-0059",
          "CSAFPID-0060",
          "CSAFPID-0061",
          "CSAFPID-0062",
          "CSAFPID-0063",
          "CSAFPID-0064",
          "CSAFPID-0065",
          "CSAFPID-0066",
          "CSAFPID-0067",
          "CSAFPID-0068",
          "CSAFPID-0069",
          "CSAFPID-0070",
          "CSAFPID-0071",
          "CSAFPID-0072",
          "CSAFPID-0073",
          "CSAFPID-0074",
          "CSAFPID-0075",
          "CSAFPID-0076",
          "CSAFPID-0077",
          "CSAFPID-0078",
          "CSAFPID-0079",
          "CSAFPID-0080",
          "CSAFPID-0081",
          "CSAFPID-0082"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "cwe.mitre.org",
          "url": "https://cwe.mitre.org/data/definitions/78.html"
        },
        {
          "category": "external",
          "summary": "www.cve.org",
          "url": "https://www.cve.org/CVERecord?id=CVE-2026-32649"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:H/UI:R/S:U/C:H/I:H/A:H"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Milesight advises all users to update their device to the latest firmware versions of PE/PC/PA found at https://www.milesight.com/support/download/firmware. ",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "https://www.milesight.com/support/download/firmware"
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx63-PD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx64-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx73-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx75-xxPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0004"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx83-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0005"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx74-PA: 3x.8.0.3-r11 and prior versions: Update to 3x.8.0.3-r13",
          "product_ids": [
            "CSAFPID-0006"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C8477-HPG1: 63.8.0.4-r3 and prior versions: Update to 63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0007"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C8477-PC: 48.8.0.4-r3 and prior versions: Update to 48.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0008"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5321-FPE: 62.8.0.4-r5 and prior versions: Update to 62.8.0.4-r6",
          "product_ids": [
            "CSAFPID-0009"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0010"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx62-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0011"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx52-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0012"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0013"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxGPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0014"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx61-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0015"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx67-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0016"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx71-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0017"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx41-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0018"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx76-PE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0019"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx65-PE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0020"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxG1: 63.8.0.5-r3 and prior versions: Update to 63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0021"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx62-xxxG1: 63.8.0.5-r3 and prior versions: Update to    63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0022"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-xxxG1: 63.8.0.5-r3 and prior versions: Update to 63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0023"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx31-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0024"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx68-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0025"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx72-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0026"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-NxE: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0027"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxC: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0028"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxE: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0029"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxG: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0030"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxH: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0031"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxT: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0032"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PMC8266-FPE: PO_61.8.0.4_LPR and prior versions: Update to PO_61.8.0.4-r1",
          "product_ids": [
            "CSAFPID-0033"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PMC8266-FGPE: PO_61.8.0.4_LPR and prior versions: Update to PO_61.8.0.4-r1",
          "product_ids": [
            "CSAFPID-0034"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PM3322-E: PI_61.8.0.3_LPR-r3 and prior versions: Update to PI_61.8.0.3-r5",
          "product_ids": [
            "CSAFPID-0035"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0036"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0037"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0038"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0039"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-RFIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0040"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0041"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-RFIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0042"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIWG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0043"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIWG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0044"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5510-GVH: T_47.8.0.4_LPR-r7 and prior versions: Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0045"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5510-GH: T_47.8.0.4_LPR-r6 and prior versions    : Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0046"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5511-GVH: T_47.8.0.4_LPR-r6 and prior versions: Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0047"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2966-X12TPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0048"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0049"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12PE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0050"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4PE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0051"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2966-X12TVPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0052"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RVPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0053"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12VPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0054"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4VPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0055"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4441-X36RPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0056"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4441-X36RE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0057"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RWE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0058"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4WE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0059"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2964-RFLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0060"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2972-RFLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0061"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-RFLWPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0062"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0063"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0064"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TGPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0065"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2841-X36TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0066"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2841-X36TPC/W: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0066",
            "CSAFPID-0067"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2867-X5TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0068"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2961-X12TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0069"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-FPC/P: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0070"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-X12RLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0071"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-X12RLVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0072"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5366-X12LPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0073"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5366-X12LVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0074"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5361-X12LPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0075"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxxGOPC    : 45.8.0.2-AIoT-r4 and prior versions: Update to 45.8.0.2-AIoT-r5",
          "product_ids": [
            "CSAFPID-0076"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "SC211: C_21.1.0.8-r4 and prior versions: Update to C_21.1.0.8-r5",
          "product_ids": [
            "CSAFPID-0077"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "SP111: 52.8.0.4-r5 and prior versions: Update to 52.8.0.4-r6",
          "product_ids": [
            "CSAFPID-0078"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-RFIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0079"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-RFIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0080"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-FIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0081"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-FIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0082"
          ]
        },
        {
          "category": "mitigation",
          "details": "Milesight asks all users to report potential security vulnerabilities to security@milesight.com.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "mailto:security@milesight.com"
        },
        {
          "category": "mitigation",
          "details": "Learn more: Milesight Vulnerability Reporting Policy",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "https://www.milesight.com/legal/vulnerability-report"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 6.8,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:R/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2026-20766",
      "cwe": {
        "id": "CWE-122",
        "name": "Heap-based Buffer Overflow"
      },
      "notes": [
        {
          "category": "summary",
          "text": "An out-of-bounds memory access vulnerability exists in specific firmware versions of Milesight AIOT cameras.",
          "title": "Vulnerability Summary"
        },
        {
          "category": "details",
          "text": "SSVCv2/E:P/A:Y/2026-04-22T06:00:00.000000Z",
          "title": "SSVC"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009",
          "CSAFPID-0010",
          "CSAFPID-0011",
          "CSAFPID-0012",
          "CSAFPID-0013",
          "CSAFPID-0014",
          "CSAFPID-0015",
          "CSAFPID-0016",
          "CSAFPID-0017",
          "CSAFPID-0018",
          "CSAFPID-0019",
          "CSAFPID-0020",
          "CSAFPID-0021",
          "CSAFPID-0022",
          "CSAFPID-0023",
          "CSAFPID-0024",
          "CSAFPID-0025",
          "CSAFPID-0026",
          "CSAFPID-0027",
          "CSAFPID-0028",
          "CSAFPID-0029",
          "CSAFPID-0030",
          "CSAFPID-0031",
          "CSAFPID-0032",
          "CSAFPID-0033",
          "CSAFPID-0034",
          "CSAFPID-0035",
          "CSAFPID-0036",
          "CSAFPID-0037",
          "CSAFPID-0038",
          "CSAFPID-0039",
          "CSAFPID-0040",
          "CSAFPID-0041",
          "CSAFPID-0042",
          "CSAFPID-0043",
          "CSAFPID-0044",
          "CSAFPID-0045",
          "CSAFPID-0046",
          "CSAFPID-0047",
          "CSAFPID-0048",
          "CSAFPID-0049",
          "CSAFPID-0050",
          "CSAFPID-0051",
          "CSAFPID-0052",
          "CSAFPID-0053",
          "CSAFPID-0054",
          "CSAFPID-0055",
          "CSAFPID-0056",
          "CSAFPID-0057",
          "CSAFPID-0058",
          "CSAFPID-0059",
          "CSAFPID-0060",
          "CSAFPID-0061",
          "CSAFPID-0062",
          "CSAFPID-0063",
          "CSAFPID-0064",
          "CSAFPID-0065",
          "CSAFPID-0066",
          "CSAFPID-0067",
          "CSAFPID-0068",
          "CSAFPID-0069",
          "CSAFPID-0070",
          "CSAFPID-0071",
          "CSAFPID-0072",
          "CSAFPID-0073",
          "CSAFPID-0074",
          "CSAFPID-0075",
          "CSAFPID-0076",
          "CSAFPID-0077",
          "CSAFPID-0078",
          "CSAFPID-0079",
          "CSAFPID-0080",
          "CSAFPID-0081",
          "CSAFPID-0082"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "cwe.mitre.org",
          "url": "https://cwe.mitre.org/data/definitions/122.html"
        },
        {
          "category": "external",
          "summary": "www.cve.org",
          "url": "https://www.cve.org/CVERecord?id=CVE-2026-20766"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Milesight advises all users to update their device to the latest firmware versions of PE/PC/PA found at https://www.milesight.com/support/download/firmware. ",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "https://www.milesight.com/support/download/firmware"
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx63-PD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx64-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx73-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx75-xxPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0004"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx83-xPD: 51.7.0.77-r12 and prior versions: Update to 51.7.0.77-r13",
          "product_ids": [
            "CSAFPID-0005"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx74-PA: 3x.8.0.3-r11 and prior versions: Update to 3x.8.0.3-r13",
          "product_ids": [
            "CSAFPID-0006"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C8477-HPG1: 63.8.0.4-r3 and prior versions: Update to 63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0007"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C8477-PC: 48.8.0.4-r3 and prior versions: Update to 48.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0008"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5321-FPE: 62.8.0.4-r5 and prior versions: Update to 62.8.0.4-r6",
          "product_ids": [
            "CSAFPID-0009"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0010"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx62-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0011"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx52-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0012"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0013"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxGPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0014"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx61-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0015"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx67-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0016"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx71-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0017"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx41-xxxPE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0018"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx76-PE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0019"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx65-PE: 61.8.0.5-r2 and prior versions: Update to 61.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0020"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxG1: 63.8.0.5-r3 and prior versions: Update to 63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0021"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx62-xxxG1: 63.8.0.5-r3 and prior versions: Update to 63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0022"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-xxxG1: 63.8.0.5-r3 and prior versions: Update to 63.8.0.5-r4",
          "product_ids": [
            "CSAFPID-0023"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx31-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0024"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx68-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0025"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-CQxx72-xxxG1: CQ_63.8.0.5-r1 and prior versions: Update to CQ_63.8.0.5-r2",
          "product_ids": [
            "CSAFPID-0026"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-NxE: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0027"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxC: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0028"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxE: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0029"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxG: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0030"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxH: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0031"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Nxxxx-xxT: 7x.9.0.19-r5 and prior versions: Update to 7x.9.0.19-r6",
          "product_ids": [
            "CSAFPID-0032"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PMC8266-FPE: PO_61.8.0.4_LPR and prior versions: Update to PO_61.8.0.4-r1",
          "product_ids": [
            "CSAFPID-0033"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PMC8266-FGPE: PO_61.8.0.4_LPR and prior versions: Update to PO_61.8.0.4-r1",
          "product_ids": [
            "CSAFPID-0034"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "PM3322-E: PI_61.8.0.3_LPR-r3 and prior versions: Update to PI_61.8.0.3-r5",
          "product_ids": [
            "CSAFPID-0035"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0036"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0037"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0038"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0039"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-RFIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0040"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0041"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-RFIVPG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0042"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RIWG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0043"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4RIWG1: T_63.8.0.4_LPR-r3 and prior versions: Update to T_63.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0044"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5510-GVH: T_47.8.0.4_LPR-r7 and prior versions: Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0045"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5510-GH: T_47.8.0.4_LPR-r6 and prior versions: Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0046"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5511-GVH: T_47.8.0.4_LPR-r6 and prior versions: Update to T_47.8.0.4-r8",
          "product_ids": [
            "CSAFPID-0047"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2966-X12TPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0048"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0049"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12PE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0050"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4PE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0051"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2966-X12TVPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0052"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RVPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0053"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS5366-X12VPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0054"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4VPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0055"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4441-X36RPE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0056"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4441-X36RE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0057"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS4466-X4RWE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0058"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-X4WE: T_61.8.0.4_LPR-r3 and prior versions: Update to T_61.8.0.4-r4",
          "product_ids": [
            "CSAFPID-0059"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2964-RFLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0060"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2972-RFLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0061"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-RFLWPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0062"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0063"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0064"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2866-X4TGPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0065"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2841-X36TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0066"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2841-X36TPC/W: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0066",
            "CSAFPID-0067"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2867-X5TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0068"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS2961-X12TPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0069"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "TS8266-FPC/P: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0070"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-X12RLPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0071"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C2966-X12RLVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0072"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5366-X12LPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0073"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5366-X12LVPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0074"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-C5361-X12LPC: T_45.8.0.3-r9 and prior versions: Update to T_45.8.0.3-r10",
          "product_ids": [
            "CSAFPID-0075"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-xxxxGOPC: 45.8.0.2-AIoT-r4 and prior versions: Update to 45.8.0.2-AIoT-r5",
          "product_ids": [
            "CSAFPID-0076"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "SC211: C_21.1.0.8-r4 and prior versions: Update to C_21.1.0.8-r5",
          "product_ids": [
            "CSAFPID-0077"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "SP111: 52.8.0.4-r5 and prior versions: Update to 52.8.0.4-r6",
          "product_ids": [
            "CSAFPID-0078"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-RFIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0079"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-RFIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0080"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx66-FIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0081"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "MS-Cxx72-FIPKG1: 63.8.0.4-r1-NX and prior versions: Update to 63.8.0.5-r2-NX",
          "product_ids": [
            "CSAFPID-0082"
          ]
        },
        {
          "category": "mitigation",
          "details": "Milesight asks all users to report potential security vulnerabilities to security@milesight.com.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "mailto:security@milesight.com"
        },
        {
          "category": "mitigation",
          "details": "Learn more: Milesight Vulnerability Reporting Policy",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ],
          "url": "https://www.milesight.com/legal/vulnerability-report"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.8,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010",
            "CSAFPID-0011",
            "CSAFPID-0012",
            "CSAFPID-0013",
            "CSAFPID-0014",
            "CSAFPID-0015",
            "CSAFPID-0016",
            "CSAFPID-0017",
            "CSAFPID-0018",
            "CSAFPID-0019",
            "CSAFPID-0020",
            "CSAFPID-0021",
            "CSAFPID-0022",
            "CSAFPID-0023",
            "CSAFPID-0024",
            "CSAFPID-0025",
            "CSAFPID-0026",
            "CSAFPID-0027",
            "CSAFPID-0028",
            "CSAFPID-0029",
            "CSAFPID-0030",
            "CSAFPID-0031",
            "CSAFPID-0032",
            "CSAFPID-0033",
            "CSAFPID-0034",
            "CSAFPID-0035",
            "CSAFPID-0036",
            "CSAFPID-0037",
            "CSAFPID-0038",
            "CSAFPID-0039",
            "CSAFPID-0040",
            "CSAFPID-0041",
            "CSAFPID-0042",
            "CSAFPID-0043",
            "CSAFPID-0044",
            "CSAFPID-0045",
            "CSAFPID-0046",
            "CSAFPID-0047",
            "CSAFPID-0048",
            "CSAFPID-0049",
            "CSAFPID-0050",
            "CSAFPID-0051",
            "CSAFPID-0052",
            "CSAFPID-0053",
            "CSAFPID-0054",
            "CSAFPID-0055",
            "CSAFPID-0056",
            "CSAFPID-0057",
            "CSAFPID-0058",
            "CSAFPID-0059",
            "CSAFPID-0060",
            "CSAFPID-0061",
            "CSAFPID-0062",
            "CSAFPID-0063",
            "CSAFPID-0064",
            "CSAFPID-0065",
            "CSAFPID-0066",
            "CSAFPID-0067",
            "CSAFPID-0068",
            "CSAFPID-0069",
            "CSAFPID-0070",
            "CSAFPID-0071",
            "CSAFPID-0072",
            "CSAFPID-0073",
            "CSAFPID-0074",
            "CSAFPID-0075",
            "CSAFPID-0076",
            "CSAFPID-0077",
            "CSAFPID-0078",
            "CSAFPID-0079",
            "CSAFPID-0080",
            "CSAFPID-0081",
            "CSAFPID-0082"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Forecast uses a logistic model when the trend is rising, or an exponential decay model when the trend is falling. Fitted via linearized least squares.

Sightings

Author Source Type Date Other

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.

Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…