SEVD-2025-252-02

Vulnerability from csaf_se - Published: 2025-09-09 04:00 - Updated: 2025-09-09 04:00
Summary
Saitel DR & Saitel DP Remote Terminal Unit

Notes

General Security Recommendations
We strongly recommend the following industry cybersecurity best practices. https://www.se.com/us/en/download/document/7EN52-0390/ * Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. * Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. * Place all controllers in locked cabinets and never leave them in the “Program” mode. * Never connect programming software to any network other than the network intended for that device. * Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. * Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. * Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. * When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices https://www.se.com/us/en/download/document/7EN52-0390/ document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. For further information related to cybersecurity in Schneider Electric's products, visit the company's cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
Schneider's purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and sustainability for all. We call this Life Is On. Our mission is to be the trusted partner in Sustainability and Efficiency. We are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart industries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep domain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation, software and services, delivering digital twins to enable profitable growth for our customers. We are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries to ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our meaningful purpose of a sustainable future for all. www.se.com
Overview
Schneider Electric is aware of vulnerabilities in its Saitel DR & Saitel DP RTU (Remote Terminal Unit) product(s). The Saitel DR RTU https://www.se.com/ww/en/product-country-selector/?pageType=product-range&sourceId=62685#overview is a field device, offering a solid and powerful platform for data acquisition, communication, automation and IED integration for distribution and transmission networks, generation sector and railway. The Saitel DP RTU https://www.se.com/ww/en/product-country-selector/?pageType=product-range&sourceId=61747 is a modular platform for medium voltage and low voltage public distribution and transmission network management. Failure to apply the remediations provided below may risk command injection attack, which could result in arbitrary code execution.
The severity of vulnerabilities was calculated using the CVSS Base metrics for 4.0 (CVSS v4.0 https://www.first.org/cvss/calculator/4.0). CVSS v3.1 will be still evaluated until the adoption of CVSS v4.0 by the industry. The severity was calculated without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer’s environment.
Customers should use appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric's Customer Care Center https://www.se.com/us/en/work/support/contacts.jsp if you need assistance removing a patch.

{
  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Public",
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\n\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices https://www.se.com/us/en/download/document/7EN52-0390/ document.",
        "title": "General Security Recommendations"
      },
      {
        "category": "general",
        "text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\n\nFor further information related to cybersecurity in Schneider Electric\u0027s products, visit the company\u0027s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
        "title": "For More Information"
      },
      {
        "category": "legal_disclaimer",
        "text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND.  SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
        "title": "LEGAL DISCLAIMER"
      },
      {
        "category": "general",
        "text": "Schneider\u0027s purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and\r\nsustainability for all. We call this Life Is On.\n\nOur mission is to be the trusted partner in Sustainability and Efficiency.\n\nWe are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart\r\nindustries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep\r\ndomain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation,\r\nsoftware and services, delivering digital twins to enable profitable growth for our customers.\n\nWe are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries\r\nto ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our\r\nmeaningful purpose of a sustainable future for all. \n\n www.se.com",
        "title": "About Schneider Electric"
      },
      {
        "category": "summary",
        "text": "Schneider Electric is aware of vulnerabilities in its Saitel DR \u0026 Saitel DP RTU (Remote Terminal Unit)\r\nproduct(s). \n\nThe Saitel DR RTU https://www.se.com/ww/en/product-country-selector/?pageType=product-range\u0026sourceId=62685#overview is a field device, offering a solid and powerful platform for data acquisition, communication, \r\nautomation and IED integration for distribution and transmission networks, generation sector and railway.\n\nThe Saitel DP RTU https://www.se.com/ww/en/product-country-selector/?pageType=product-range\u0026sourceId=61747 is a modular platform for medium voltage and low voltage public distribution and \r\ntransmission network management.\n\nFailure to apply the remediations provided below may risk command injection attack, which could result in \r\narbitrary code execution. ",
        "title": "Overview"
      },
      {
        "category": "other",
        "text": "The severity of vulnerabilities was calculated using the CVSS Base metrics for 4.0 (CVSS v4.0 https://www.first.org/cvss/calculator/4.0). CVSS v3.1 \nwill be still evaluated until the adoption of CVSS v4.0 by the industry. The severity was calculated without \nincorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score \nthe CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as \nthe presence of mitigations in that environment. Environmental metrics may refine the relative severity posed \nby the vulnerabilities described in this document within a customer\u2019s environment."
      },
      {
        "category": "other",
        "text": "Customers should use appropriate patching methodologies when applying these patches to their systems. We \nstrongly recommend the use of back-ups and evaluating the impact of these patches in a Test and \nDevelopment environment or on an offline infrastructure. Contact Schneider Electric\u0027s Customer Care Center https://www.se.com/us/en/work/support/contacts.jsp if you need assistance removing a patch. "
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "cpcert@se.com",
      "name": "Schneider Electric CPCERT",
      "namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
    },
    "references": [
      {
        "category": "self",
        "summary": "Saitel DR \u0026 Saitel DP Remote Terminal Unit - SEVD-2025-252-02 PDF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-252-02\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-252-02.pdf"
      },
      {
        "category": "self",
        "summary": "Saitel DR \u0026 Saitel DP Remote Terminal Unit - SEVD-2025-252-02 CSAF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-252-02\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2025-252-02.json"
      },
      {
        "category": "external",
        "summary": "Recommended Cybersecurity Best Practices",
        "url": "https://www.se.com/us/en/download/document/7EN52-0390/"
      }
    ],
    "title": "Saitel DR \u0026 Saitel DP Remote Terminal Unit",
    "tracking": {
      "current_release_date": "2025-09-09T04:00:00.000Z",
      "generator": {
        "date": "2025-09-05T09:57:52.871Z",
        "engine": {
          "name": "Schneider Electric CSAF Generator",
          "version": "1.2"
        }
      },
      "id": "SEVD-2025-252-02",
      "initial_release_date": "2025-09-09T04:00:00.000Z",
      "revision_history": [
        {
          "date": "2025-09-09T04:00:00.000Z",
          "number": "1.0.0",
          "summary": "Original Release"
        }
      ],
      "status": "final",
      "version": "1.0.0"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=11.06.29",
                "product": {
                  "name": "Schneider Electric Saitel DR RTU Versions 11.06.29 and prior",
                  "product_id": "1"
                }
              },
              {
                "category": "product_version",
                "name": "11.06.30",
                "product": {
                  "name": "Schneider Electric Saitel DR RTU Version 11.06.30",
                  "product_id": "2"
                }
              }
            ],
            "category": "product_name",
            "name": "Saitel DR RTU"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=11.06.33",
                "product": {
                  "name": "Schneider Electric Saitel DP RTU Versions 11.06.33 and prior",
                  "product_id": "3"
                }
              },
              {
                "category": "product_version",
                "name": "11.06.34",
                "product": {
                  "name": "Schneider Electric Saitel DP RTU Version 11.06.34",
                  "product_id": "4"
                }
              }
            ],
            "category": "product_name",
            "name": "Saitel DP RTU"
          }
        ],
        "category": "vendor",
        "name": "Schneider Electric"
      }
    ]
  },
  "vulnerabilities": [
    {
      "acknowledgments": [
        {
          "names": [
            "Robin Senn",
            "Sebastian Krause"
          ],
          "organization": "GAI NetConsult GmbH"
        }
      ],
      "cve": "CVE-2025-9996",
      "cwe": {
        "id": "CWE-78",
        "name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
      },
      "notes": [
        {
          "category": "description",
          "text": "CWE-78: Improper Neutralization of Special Elements used in an OS Command vulnerability exists that could \r\ncause the execution of any shell command when executing a netstat command using BLMon Console in an \r\nSSH session.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4"
        ],
        "known_affected": [
          "1",
          "3"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "HUe Firmware version 11.06.30 of Saitel DR includes a fix for this \r\nvulnerability and is available for download here:\r\n\u2022 https://www.se.com/ww/en/product-country-selector/?pageType=product-range\u0026sourceId=62685\r\n\r\nA reboot is needed to complete the firmware upgrade.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "system"
          },
          "url": "https://www.se.com/ww/en/product-country-selector/?pageType=product-range\u0026sourceId=62685"
        },
        {
          "category": "vendor_fix",
          "details": "Firmware SM_CPU866e version 11.06.34 of Saitel DP includes a fix for this \r\nvulnerability and is available for download here:\r\n\u2022 https://www.se.com/ww/en/product-country-selector/?pageType=product-range\u0026sourceId=61747\r\n\r\nA reboot is needed to complete the firmware upgrade.",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "system"
          },
          "url": "https://www.se.com/ww/en/product-country-selector/?pageType=product-range\u0026sourceId=61747"
        },
        {
          "category": "mitigation",
          "details": "If customers choose not to apply the remediation provided above, they should immediately apply the following \r\nmitigations to reduce the risk of exploit: \r\n\n* Restrict access to BLMon by assigning permissions only to a limited set of user roles. \n\n* Ensure users are assigned the least privileged role that still allows them to perform their designated \r\ntasks.\r\n\n* Implement firewall rules to restrict SSH connections to the device.",
          "product_ids": [
            "1",
            "3"
          ],
          "restart_required": {
            "category": "none"
          }
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "LOCAL",
            "availabilityImpact": "LOW",
            "baseScore": 6.6,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "LOW",
            "privilegesRequired": "LOW",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:L/A:L",
            "version": "3.1"
          },
          "products": [
            "1",
            "3"
          ]
        }
      ],
      "title": "CVE-2025-9996"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Robin Senn",
            "Sebastian Krause"
          ],
          "organization": "GAI NetConsult GmbH"
        }
      ],
      "cve": "CVE-2025-9997",
      "cwe": {
        "id": "CWE-78",
        "name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
      },
      "notes": [
        {
          "category": "description",
          "text": "CWE-78: Improper Neutralization of Special Elements used in an OS Command vulnerability exists that could \r\ncause command injection in BLMon that is executed in the operating system console when in a SSH session.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4"
        ],
        "known_affected": [
          "1",
          "3"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "HUe Firmware version 11.06.30 of Saitel DR includes a fix for this \r\nvulnerability and is available for download here:\r\n\u2022 https://www.se.com/ww/en/product-country-selector/?pageType=product-range\u0026sourceId=62685\r\n\r\nA reboot is needed to complete the firmware upgrade.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "system"
          },
          "url": "https://www.se.com/ww/en/product-country-selector/?pageType=product-range\u0026sourceId=62685"
        },
        {
          "category": "vendor_fix",
          "details": "Firmware SM_CPU866e version 11.06.34 of Saitel DP includes a fix for this \r\nvulnerability and is available for download here:\r\n\u2022 https://www.se.com/ww/en/product-country-selector/?pageType=product-range\u0026sourceId=61747\r\n\r\nA reboot is needed to complete the firmware upgrade.",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "system"
          },
          "url": "https://www.se.com/ww/en/product-country-selector/?pageType=product-range\u0026sourceId=61747"
        },
        {
          "category": "mitigation",
          "details": "If customers choose not to apply the remediation provided above, they should immediately apply the following \r\nmitigations to reduce the risk of exploit: \r\n\n* Restrict access to BLMon by assigning permissions only to a limited set of user roles. \n\n* Ensure users are assigned the least privileged role that still allows them to perform their designated \r\ntasks.\r\n\n* Implement firewall rules to restrict SSH connections to the device.",
          "product_ids": [
            "1",
            "3"
          ],
          "restart_required": {
            "category": "none"
          }
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "LOCAL",
            "availabilityImpact": "LOW",
            "baseScore": 6.6,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "LOW",
            "privilegesRequired": "LOW",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:L/A:L",
            "version": "3.1"
          },
          "products": [
            "1",
            "3"
          ]
        }
      ],
      "title": "CVE-2025-9997"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.