SEVD-2023-318-01

Vulnerability from csaf_se - Published: 2023-11-14 00:00 - Updated: 2023-12-12 00:00
Summary
PowerLogic ION8650, PowerLogic ION8800

Notes

General Security Recommendations
We strongly recommend the following industry cybersecurity best practices. https://www.se.com/us/en/download/document/7EN52-0390/ * Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. * Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. * Place all controllers in locked cabinets and never leave them in the “Program” mode. * Never connect programming software to any network other than the network intended for that device. * Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. * Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. * Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. * When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment. We provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries. We are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values. www.se.com
Overview
Schneider Electric is aware of multiple vulnerabilities in its PowerLogic ION8650 and PowerLogic ION8800 products. The PowerLogic products are revenue and power quality meters for utility electrical network monitoring. Failure to apply the mitigations provided below may risk an attacker with administrative privileges installing compromised firmware on the device, resulting in modified device behavior, or modifying webpages on the device in a malicious way, which could result in other viewers of that webpage being exposed to a cross-site scripting attack. December 2023 Update: We have added supplementary information in the vulnerability details and mitigations for CVE-2023-5984.

{
  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Public",
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
        "title": "General Security Recommendations"
      },
      {
        "category": "general",
        "text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
        "title": "For More Information"
      },
      {
        "category": "legal_disclaimer",
        "text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND.  SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
        "title": "LEGAL DISCLAIMER"
      },
      {
        "category": "general",
        "text": "At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.\n\nWe provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.\n\nWe are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.\n\nwww.se.com ",
        "title": "About Schneider Electric"
      },
      {
        "category": "summary",
        "text": "Schneider Electric is aware of multiple vulnerabilities in its PowerLogic ION8650 and\nPowerLogic ION8800 products.\nThe PowerLogic products are revenue and power quality meters for utility electrical network\nmonitoring.\nFailure to apply the mitigations provided below may risk an attacker with administrative\nprivileges installing compromised firmware on the device, resulting in modified device behavior,\nor modifying webpages on the device in a malicious way, which could result in other viewers of\nthat webpage being exposed to a cross-site scripting attack.\n\nDecember 2023 Update: We have added supplementary information in the vulnerability details\nand mitigations for CVE-2023-5984.",
        "title": "Overview"
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "cpcert@se.com",
      "name": "Schneider Electric CPCERT",
      "namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
    },
    "references": [
      {
        "category": "self",
        "summary": "PowerLogic ION8650, PowerLogic ION8800 - SEVD-2023-318-01 PDF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-318-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2023-318-01.pdf"
      },
      {
        "category": "self",
        "summary": "PowerLogic ION8650, PowerLogic ION8800 - SEVD-2023-318-01 CSAF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-318-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2023-318-01.json"
      },
      {
        "category": "self",
        "summary": "Recommended Cybersecurity Best Practices",
        "url": "https://www.se.com/us/en/download/document/7EN52-0390/"
      }
    ],
    "title": "PowerLogic ION8650, PowerLogic ION8800",
    "tracking": {
      "current_release_date": "2023-12-12T00:00:00.000Z",
      "generator": {
        "date": "2023-12-12T00:00:00.000Z",
        "engine": {
          "name": "Schneider Electric CSAF Generator",
          "version": "1.1"
        }
      },
      "id": "SEVD-2023-318-01",
      "initial_release_date": "2023-11-14T00:00:00.000Z",
      "revision_history": [
        {
          "date": "2023-11-14T07:13:17.000Z",
          "number": "1.0.0",
          "summary": "Original Release"
        },
        {
          "date": "2023-12-12T00:00:00.000Z",
          "number": "1.1.0",
          "summary": "We have added supplementary information in the vulnerability details and mitigations for CVE-2023-5984"
        }
      ],
      "status": "final",
      "version": "1.1.0"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "Schneider Electric PowerLogic ION8650 All Versions",
                  "product_id": "1"
                }
              }
            ],
            "category": "product_name",
            "name": "PowerLogic ION8650"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "Schneider Electric PowerLogic ION8800 All Versions",
                  "product_id": "2"
                }
              }
            ],
            "category": "product_name",
            "name": "PowerLogic ION8800"
          }
        ],
        "category": "vendor",
        "name": "Schneider Electric"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2023-5984",
      "cwe": {
        "id": "CWE-494",
        "name": "Download of Code Without Integrity Check"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-494 Download of Code Without Integrity Check vulnerability exists that could allow modified firmware to be uploaded when an authorized admin user begins a firmware update procedure which could result in full control over the device.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1",
          "2"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "If you are upgrading your device, ensure you download the firmware from SE.com using the official links: (ION 8650, ION 8800) - https://www.se.com/us/en/product-range/61053-powerlogic-ion8650-series/ and https://www.se.com/nz/en/product-range/1463-powerlogic-power-quality-meters-ion8800/ .",
          "product_ids": [
            "1",
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ca/en/product-range/61053-ion8650/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.2,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 7.2,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "temporalScore": 7.2,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "1",
            "2"
          ]
        }
      ],
      "title": " CVE-2023-5984"
    },
    {
      "cve": "CVE-2023-5985",
      "cwe": {
        "id": "CWE-79",
        "name": "Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027)"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-79 Improper Neutralization of Input During Web Page Generation vulnerability\r\nexists that could cause compromise of a user\u2019s browser when an attacker with admin privileges \r\nhas modified system values.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1",
          "2"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "CVE-2023-5985\r\nEnsure that the device firmware is up to date, and the web service is disabled if not required for operation.",
          "product_ids": [
            "1",
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ca/en/product-range/61053-ion8650/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "NONE",
            "baseScore": 4.8,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "LOW",
            "integrityImpact": "LOW",
            "privilegesRequired": "HIGH",
            "scope": "CHANGED",
            "userInteraction": "REQUIRED",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:R/S:C/C:L/I:L/A:N",
            "version": "3.1"
          },
          "products": [
            "1",
            "2"
          ]
        }
      ],
      "title": "CVE-2023-5985"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…