SEVD-2023-101-04

Vulnerability from csaf_se - Published: 2023-04-11 14:09 - Updated: 2024-06-11 00:00
Summary
Easy UPS Online Monitoring Software

Notes

General Security Recommendations
We strongly recommend the following industry cybersecurity best practices. https://www.se.com/us/en/download/document/7EN52-0390/ * Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. * Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. * Place all controllers in locked cabinets and never leave them in the “Program” mode. * Never connect programming software to any network other than the network intended for that device. * Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. * Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. * Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. * When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
Note regarding vulnerability details
The severity of vulnerabilities was calculated using the CVSS Base metrics in version 3.1 (CVSS v3.1) without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer’s environment
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment. We provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries. We are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values. www.se.com
Overview
Schneider Electric is aware of multiple vulnerabilities in its Easy UPS Online Monitoring Software, known as APC Easy UPS Online Monitoring Software, and Schneider Electric UPS Online Monitoring Software known as Schneider SP Series UPS Online Monitoring Software in China. The Easy UPS Online Monitoring Software is used to configure and manage Easy UPS products. Failure to apply the remediations provided below may risk remote code execution, escalation of privileges, or authentication bypass, which could result in execution of malicious web code or loss of device functionality. June 2024 Update: Vulnerability description for CVE-2023-29412 has been updated. CWE-78 is correct, but the initial description didn’t match with this CWE ID. Remediation instructions were updated to clarify support status.

{
  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Public",
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
        "title": "General Security Recommendations"
      },
      {
        "category": "general",
        "text": "The severity of vulnerabilities was calculated using the CVSS Base metrics in version 3.1 (CVSS v3.1) without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer\u2019s environment",
        "title": "Note regarding vulnerability details"
      },
      {
        "category": "general",
        "text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
        "title": "For More Information"
      },
      {
        "category": "legal_disclaimer",
        "text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND.  SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
        "title": "LEGAL DISCLAIMER"
      },
      {
        "category": "general",
        "text": "At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.\n\nWe provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.\n\nWe are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.\n\nwww.se.com ",
        "title": "About Schneider Electric"
      },
      {
        "category": "summary",
        "text": "Schneider Electric is aware of multiple vulnerabilities in its Easy UPS Online Monitoring Software, known as APC Easy UPS Online Monitoring Software, and Schneider Electric UPS Online Monitoring Software known as Schneider SP Series UPS Online Monitoring Software in China.\n\nThe Easy UPS Online Monitoring Software is used to configure and manage Easy UPS products.\n\nFailure to apply the remediations provided below may risk remote code execution, escalation of privileges, or authentication bypass, which could result in execution of malicious web code or loss of device functionality.\n\nJune 2024 Update: Vulnerability description for CVE-2023-29412 has been updated. CWE-78 is correct, but the initial description didn\u2019t match with this CWE ID. Remediation instructions were updated to clarify support status.",
        "title": "Overview"
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "cpcert@se.com",
      "name": "Schneider Electric CPCERT",
      "namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
    },
    "references": [
      {
        "category": "self",
        "summary": "Easy UPS Online Monitoring Software - SEVD-2023-101-04 PDF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-101-04\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2023-101-04.pdf"
      },
      {
        "category": "self",
        "summary": "Easy UPS Online Monitoring Software - SEVD-2023-101-04 CSAF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-101-04\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2023-101-04.json"
      },
      {
        "category": "external",
        "summary": "Recommended Cybersecurity Best Practices",
        "url": "https://www.se.com/us/en/download/document/7EN52-0390/"
      }
    ],
    "title": "Easy UPS Online Monitoring Software",
    "tracking": {
      "current_release_date": "2024-06-11T00:00:00.000Z",
      "generator": {
        "date": "2024-06-11T00:00:00.000Z",
        "engine": {
          "name": "Schneider Electric CSAF Generator",
          "version": "1.2"
        }
      },
      "id": "SEVD-2023-101-04",
      "initial_release_date": "2023-04-11T14:09:13.000Z",
      "revision_history": [
        {
          "date": "2023-04-11T14:09:13.000Z",
          "number": "1.0.0",
          "summary": "Original Release"
        },
        {
          "date": "2023-04-19T14:09:00.000Z",
          "number": "2.0.0",
          "summary": "The document has been updated to reflect the APC Easy UPS Online Monitoring Software and Schneider Electric Easy UPS Online Monitoring Software remediation is for Windows 10 only. A mitigation for APC Easy UPS Online Monitoring Software and Schneider Electric Easy UPS Online Monitoring Software for Windows 10, 11 Windows Server 2016, 2019, and 2022 has been added."
        },
        {
          "date": "2023-06-13T14:09:00.000Z",
          "number": "3.0.0",
          "summary": "A remediation is available that now includes all supported Windows versions."
        },
        {
          "date": "2024-06-11T00:00:00.000Z",
          "number": "4.0.0",
          "summary": "Vulnerability description for CVE-2023-29412 has been updated. CWE-78 is correct, but the initial description didn\u0027t match with this CWE ID.Remediation instructions were updated to clarify support status."
        }
      ],
      "status": "final",
      "version": "4.0.0"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=2.5-GA-01-22320",
                "product": {
                  "name": "APC Easy UPS Online Monitoring Software version 2.5-GA-01-22320 and prior",
                  "product_id": "1"
                }
              }
            ],
            "category": "product_name",
            "name": "Easy UPS Online Monitoring Software"
          }
        ],
        "category": "vendor",
        "name": "APC"
      },
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=2.5-GS-01-22320",
                "product": {
                  "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.5-GS-01-22320 and prior",
                  "product_id": "2"
                }
              },
              {
                "category": "product_version",
                "name": "2.6-GA-01-23116",
                "product": {
                  "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.6-GA-01-23116",
                  "product_id": "3"
                }
              },
              {
                "category": "product_version",
                "name": "2.6-GS-01-23116",
                "product": {
                  "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.6-GS-01-23116",
                  "product_id": "4"
                }
              }
            ],
            "category": "product_name",
            "name": "Easy UPS Online Monitoring Software"
          }
        ],
        "category": "vendor",
        "name": "Schneider Electric"
      },
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version",
                "name": "10",
                "product": {
                  "name": "Microsoft Windows 10",
                  "product_id": "5"
                }
              },
              {
                "category": "product_version",
                "name": "11",
                "product": {
                  "name": "Microsoft Windows 11",
                  "product_id": "6"
                }
              }
            ],
            "category": "product_name",
            "name": "Windows"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "2016",
                "product": {
                  "name": "Microsoft Windows Server 2016",
                  "product_id": "7"
                }
              },
              {
                "category": "product_version",
                "name": "2019",
                "product": {
                  "name": "Microsoft Windows Server 2019",
                  "product_id": "8"
                }
              },
              {
                "category": "product_version",
                "name": "2022",
                "product": {
                  "name": "Microsoft Windows Server 2022",
                  "product_id": "9"
                }
              }
            ],
            "category": "product_name",
            "name": "Windows Server"
          }
        ],
        "category": "vendor",
        "name": "Microsoft"
      }
    ],
    "relationships": [
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "APC Easy UPS Online Monitoring Software version 2.5-GA-01-22320 and prior installed on Microsoft Windows 10",
          "product_id": "10"
        },
        "product_reference": "1",
        "relates_to_product_reference": "5"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "APC Easy UPS Online Monitoring Software version 2.5-GA-01-22320 and prior installed on Microsoft Windows 11",
          "product_id": "11"
        },
        "product_reference": "1",
        "relates_to_product_reference": "6"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "APC Easy UPS Online Monitoring Software version 2.5-GA-01-22320 and prior installed on Microsoft Windows Server 2016",
          "product_id": "12"
        },
        "product_reference": "1",
        "relates_to_product_reference": "7"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "APC Easy UPS Online Monitoring Software version 2.5-GA-01-22320 and prior installed on Microsoft Windows Server 2019",
          "product_id": "13"
        },
        "product_reference": "1",
        "relates_to_product_reference": "8"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "APC Easy UPS Online Monitoring Software version 2.5-GA-01-22320 and prior installed on Microsoft Windows Server 2022",
          "product_id": "14"
        },
        "product_reference": "1",
        "relates_to_product_reference": "9"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.5-GS-01-22320 and prior installed on Microsoft Windows 10",
          "product_id": "15"
        },
        "product_reference": "2",
        "relates_to_product_reference": "5"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.5-GS-01-22320 and prior installed on Microsoft Windows 11",
          "product_id": "16"
        },
        "product_reference": "2",
        "relates_to_product_reference": "6"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.5-GS-01-22320 and prior installed on Microsoft Windows Server 2016",
          "product_id": "17"
        },
        "product_reference": "2",
        "relates_to_product_reference": "7"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.5-GS-01-22320 and prior installed on Microsoft Windows Server 2019",
          "product_id": "18"
        },
        "product_reference": "2",
        "relates_to_product_reference": "8"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.5-GS-01-22320 and prior installed on Microsoft Windows Server 2022",
          "product_id": "19"
        },
        "product_reference": "2",
        "relates_to_product_reference": "9"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.6-GA-01-23116 installed on Microsoft Windows 10",
          "product_id": "20"
        },
        "product_reference": "3",
        "relates_to_product_reference": "5"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.6-GA-01-23116 installed on Microsoft Windows 11",
          "product_id": "21"
        },
        "product_reference": "3",
        "relates_to_product_reference": "6"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.6-GA-01-23116 installed on Microsoft Windows Server 2016",
          "product_id": "22"
        },
        "product_reference": "3",
        "relates_to_product_reference": "7"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.6-GA-01-23116 installed on Microsoft Windows Server 2019",
          "product_id": "23"
        },
        "product_reference": "3",
        "relates_to_product_reference": "8"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.6-GA-01-23116 installed on Microsoft Windows Server 2022",
          "product_id": "24"
        },
        "product_reference": "3",
        "relates_to_product_reference": "9"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.6-GS-01-23116 installed on Microsoft Windows 10",
          "product_id": "25"
        },
        "product_reference": "4",
        "relates_to_product_reference": "5"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.6-GS-01-23116 installed on Microsoft Windows 11",
          "product_id": "26"
        },
        "product_reference": "4",
        "relates_to_product_reference": "6"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.6-GS-01-23116 installed on Microsoft Windows Server 2016",
          "product_id": "27"
        },
        "product_reference": "4",
        "relates_to_product_reference": "7"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.6-GS-01-23116 installed on Microsoft Windows Server 2019",
          "product_id": "28"
        },
        "product_reference": "4",
        "relates_to_product_reference": "8"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Schneider Electric Easy UPS Online Monitoring Software version 2.6-GS-01-23116 installed on Microsoft Windows Server 2022",
          "product_id": "29"
        },
        "product_reference": "4",
        "relates_to_product_reference": "9"
      }
    ]
  },
  "vulnerabilities": [
    {
      "acknowledgments": [
        {
          "names": [
            "Esjay"
          ],
          "organization": "Trend Micro Zero Day Initiative"
        },
        {
          "names": [
            "Nicholas Miles"
          ],
          "organization": "Tenable Network Security"
        }
      ],
      "cve": "CVE-2023-29411",
      "cwe": {
        "id": "CWE-306",
        "name": "Missing Authentication for Critical Function"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-306: Missing Authentication for Critical Function vulnerability exists that could allow changes to administrative credentials, leading to potential remote code execution without requiring prior authentication on the Java RMI interface.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "20",
          "21",
          "22",
          "23",
          "24",
          "25",
          "26",
          "27",
          "28",
          "29"
        ],
        "known_affected": [
          "10",
          "11",
          "12",
          "13",
          "14",
          "15",
          "16",
          "17",
          "18",
          "19"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Version v2.6-GA-01-23116 of Schneider Electric Easy UPS Online \nMonitoring Software includes a fix for the vulnerabilities for Microsoft \nsupported versions of Windows (10, 11) and Windows Server (2016, \n2019, 2022) and is available for direct download here: \nhttps://download.schneider-electric.com/files?p_enDocType=Software+-\n+Release\u0026p_Doc_Ref=APC_install_APC_UPS_windows\nThe Easy UPS Online Monitoring Software has been discontinued \ncoinciding with the discontinuation of the Easy UPS Online SNMP Cards \n(APV9601, APVS9601) managed by this software.\nNote: The fix applies to all variants of UPS Online Monitoring Software.\nIt is recommended that customers currently using Easy UPS Online \nMonitoring Software to manage Easy UPS Online (SRV/SRVS) to \ntransition to PowerChute Serial Shutdown for serial/USB shutdown and \nmonitoring; and to PowerChute Network Shutdown for network shutdown \nand monitoring. For more information about PowerChute software,\nplease see the following:\nhttps://www.apc.com/pcss\nhttps://www.apc.com/pcns",
          "product_ids": [
            "10",
            "11",
            "12",
            "13",
            "14"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://download.schneider-electric.com/files?p_enDocType=Software+-+Release\u0026p_Doc_Ref=APC_install_APC_UPS_windows"
        },
        {
          "category": "vendor_fix",
          "details": "Version v2.6-GS-01-23116 of Schneider Electric Easy UPS Online \nMonitoring Software includes a fix for the vulnerabilities for Microsoft \nsupported versions of Windows (10, 11) Windows Server (2016, 2019, \n2022) and is available for direct download here:\nhttps://download.schneider-electric.com/files?p_enDocType=Software+-\n+Release\u0026p_Doc_Ref=APC_install_APC_UPS_windows\nThe Easy UPS Online Monitoring Software has been discontinued \ncoinciding with the discontinuation of the Easy UPS Online SNMP Cards \n(APV9601, APVS9601) managed by this software.\nNote: The fix applies to all variants of UPS Online Monitoring Software.\nIt is recommended that customers currently using Easy UPS Online \nMonitoring Software to manage Easy UPS Online (SRV/SRVS) to \ntransition to PowerChute Serial Shutdown for serial/USB shutdown and \nmonitoring; and to PowerChute Network Shutdown for network shutdown \nand monitoring. For more information about PowerChute software,\nplease see the following:\nhttps://www.apc.com/pcss\nhttps://www.apc.com/pcns",
          "product_ids": [
            "15",
            "16",
            "17",
            "18",
            "19"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://download.schneider-electric.com/files?p_enDocType=Software+-+Release\u0026p_Doc_Ref=APC_install_APC_UPS_windows"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "10",
            "11",
            "12",
            "13",
            "14",
            "15",
            "16",
            "17",
            "18",
            "19"
          ]
        }
      ],
      "title": "CVE-2023-29411"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Esjay"
          ],
          "organization": "Trend Micro Zero Day Initiative"
        }
      ],
      "cve": "CVE-2023-29412",
      "cwe": {
        "id": "CWE-78",
        "name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
      },
      "notes": [
        {
          "category": "description",
          "text": "CWE-78: Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027) vulnerability exists that could cause remote code execution when manipulating internal methods through Java RMI interface.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "20",
          "21",
          "22",
          "23",
          "24",
          "25",
          "26",
          "27",
          "28",
          "29"
        ],
        "known_affected": [
          "10",
          "11",
          "12",
          "13",
          "14",
          "15",
          "16",
          "17",
          "18",
          "19"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Version v2.6-GA-01-23116 of Schneider Electric Easy UPS Online \nMonitoring Software includes a fix for the vulnerabilities for Microsoft \nsupported versions of Windows (10, 11) and Windows Server (2016, \n2019, 2022) and is available for direct download here: \nhttps://download.schneider-electric.com/files?p_enDocType=Software+-\n+Release\u0026p_Doc_Ref=APC_install_APC_UPS_windows\nThe Easy UPS Online Monitoring Software has been discontinued \ncoinciding with the discontinuation of the Easy UPS Online SNMP Cards \n(APV9601, APVS9601) managed by this software.\nNote: The fix applies to all variants of UPS Online Monitoring Software.\nIt is recommended that customers currently using Easy UPS Online \nMonitoring Software to manage Easy UPS Online (SRV/SRVS) to \ntransition to PowerChute Serial Shutdown for serial/USB shutdown and \nmonitoring; and to PowerChute Network Shutdown for network shutdown \nand monitoring. For more information about PowerChute software,\nplease see the following:\nhttps://www.apc.com/pcss\nhttps://www.apc.com/pcns",
          "product_ids": [
            "10",
            "11",
            "12",
            "13",
            "14"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://download.schneider-electric.com/files?p_enDocType=Software+-+Release\u0026p_Doc_Ref=APC_install_APC_UPS_windows"
        },
        {
          "category": "vendor_fix",
          "details": "Version v2.6-GS-01-23116 of Schneider Electric Easy UPS Online \nMonitoring Software includes a fix for the vulnerabilities for Microsoft \nsupported versions of Windows (10, 11) Windows Server (2016, 2019, \n2022) and is available for direct download here:\nhttps://download.schneider-electric.com/files?p_enDocType=Software+-\n+Release\u0026p_Doc_Ref=APC_install_APC_UPS_windows\nThe Easy UPS Online Monitoring Software has been discontinued \ncoinciding with the discontinuation of the Easy UPS Online SNMP Cards \n(APV9601, APVS9601) managed by this software.\nNote: The fix applies to all variants of UPS Online Monitoring Software.\nIt is recommended that customers currently using Easy UPS Online \nMonitoring Software to manage Easy UPS Online (SRV/SRVS) to \ntransition to PowerChute Serial Shutdown for serial/USB shutdown and \nmonitoring; and to PowerChute Network Shutdown for network shutdown \nand monitoring. For more information about PowerChute software,\nplease see the following:\nhttps://www.apc.com/pcss\nhttps://www.apc.com/pcns",
          "product_ids": [
            "15",
            "16",
            "17",
            "18",
            "19"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://download.schneider-electric.com/files?p_enDocType=Software+-+Release\u0026p_Doc_Ref=APC_install_APC_UPS_windows"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "10",
            "11",
            "12",
            "13",
            "14",
            "15",
            "16",
            "17",
            "18",
            "19"
          ]
        }
      ],
      "title": "CVE-2023-29412"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Esjay"
          ],
          "organization": "Trend Micro Zero Day Initiative"
        }
      ],
      "cve": "CVE-2023-29413",
      "cwe": {
        "id": "CWE-306",
        "name": "Missing Authentication for Critical Function"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause Denial-of-Service when accessed by an unauthenticated user on the Schneider UPS Monitor service.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "20",
          "21",
          "22",
          "23",
          "24",
          "25",
          "26",
          "27",
          "28",
          "29"
        ],
        "known_affected": [
          "10",
          "11",
          "12",
          "13",
          "14",
          "15",
          "16",
          "17",
          "18",
          "19"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Version v2.6-GA-01-23116 of Schneider Electric Easy UPS Online \nMonitoring Software includes a fix for the vulnerabilities for Microsoft \nsupported versions of Windows (10, 11) and Windows Server (2016, \n2019, 2022) and is available for direct download here: \nhttps://download.schneider-electric.com/files?p_enDocType=Software+-\n+Release\u0026p_Doc_Ref=APC_install_APC_UPS_windows\nThe Easy UPS Online Monitoring Software has been discontinued \ncoinciding with the discontinuation of the Easy UPS Online SNMP Cards \n(APV9601, APVS9601) managed by this software.\nNote: The fix applies to all variants of UPS Online Monitoring Software.\nIt is recommended that customers currently using Easy UPS Online \nMonitoring Software to manage Easy UPS Online (SRV/SRVS) to \ntransition to PowerChute Serial Shutdown for serial/USB shutdown and \nmonitoring; and to PowerChute Network Shutdown for network shutdown \nand monitoring. For more information about PowerChute software,\nplease see the following:\nhttps://www.apc.com/pcss\nhttps://www.apc.com/pcns",
          "product_ids": [
            "10",
            "11",
            "12",
            "13",
            "14"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://download.schneider-electric.com/files?p_enDocType=Software+-+Release\u0026p_Doc_Ref=APC_install_APC_UPS_windows"
        },
        {
          "category": "vendor_fix",
          "details": "Version v2.6-GS-01-23116 of Schneider Electric Easy UPS Online \nMonitoring Software includes a fix for the vulnerabilities for Microsoft \nsupported versions of Windows (10, 11) Windows Server (2016, 2019, \n2022) and is available for direct download here:\nhttps://download.schneider-electric.com/files?p_enDocType=Software+-\n+Release\u0026p_Doc_Ref=APC_install_APC_UPS_windows\nThe Easy UPS Online Monitoring Software has been discontinued \ncoinciding with the discontinuation of the Easy UPS Online SNMP Cards \n(APV9601, APVS9601) managed by this software.\nNote: The fix applies to all variants of UPS Online Monitoring Software.\nIt is recommended that customers currently using Easy UPS Online \nMonitoring Software to manage Easy UPS Online (SRV/SRVS) to \ntransition to PowerChute Serial Shutdown for serial/USB shutdown and \nmonitoring; and to PowerChute Network Shutdown for network shutdown \nand monitoring. For more information about PowerChute software,\nplease see the following:\nhttps://www.apc.com/pcss\nhttps://www.apc.com/pcns",
          "product_ids": [
            "15",
            "16",
            "17",
            "18",
            "19"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://download.schneider-electric.com/files?p_enDocType=Software+-+Release\u0026p_Doc_Ref=APC_install_APC_UPS_windows"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "10",
            "11",
            "12",
            "13",
            "14",
            "15",
            "16",
            "17",
            "18",
            "19"
          ]
        }
      ],
      "title": "CVE-2023-29413"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…