SEVD-2025-189-03
Vulnerability from csaf_se - Published: 2025-07-08 04:00 - Updated: 2025-07-08 04:00Summary
EcoStruxure™ Power Operation
Notes
General Security Recommendations
We strongly recommend the following industry cybersecurity best practices.
https://www.se.com/us/en/download/document/7EN52-0390/
* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
* Place all controllers in locked cabinets and never leave them in the “Program” mode.
* Never connect programming software to any network other than the network intended for that device.
* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.
For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.
For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
Schneider's purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and
sustainability for all. We call this Life Is On.
Our mission is to be the trusted partner in Sustainability and Efficiency.
We are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart
industries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep
domain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation,
software and services, delivering digital twins to enable profitable growth for our customers.
We are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries
to ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our
meaningful purpose of a sustainable future for all.
www.se.com
Overview
Schneider Electric is aware of multiple vulnerabilities disclosed in PostgreSQL.
Many vendors, including Schneider Electric, use PostgreSQL in their offers. PostgreSQL is a
database server that is used as a data store for multiple products.
Schneider Electric installs a version of PostgreSQL with its EcoStruxure™ Power Operation https://www.se.com/us/en/product-range/65405-ecostruxure-power-operation/?parent-subcategory-id=59326966&filter=business-4-low-voltage-products-and-systems#overview software.
EcoStruxure™ Power Operation (EPO) is an on-premises software offer that provides a single
platform to monitor and control medium and lower power systems.
Failure to apply the remediations and mitigations below could result in loss of system
functionality or unauthorized access to system functions.
Customers should use appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric’s Customer Care Center if you need assistance removing a patch.
Vulnerability Details
Vulnerability disclosed on PostgreSQL impact EcoStruxure™ Power Operation software.
The vulnerabilities are all transitive dependencies of PostgreSQL that are remediated in version
14.17.
• CVE-2023-50447
• CVE-2024-28219
• CVE-2022-45198
• CVE-2023-5217
• CVE-2023-35945
• CVE-2023-44487
Additional information about these vulnerabilities can be found on https://www.cve.org/
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Public",
"tlp": {
"label": "WHITE"
}
},
"lang": "en-US",
"notes": [
{
"category": "general",
"text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\n\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.",
"title": "General Security Recommendations"
},
{
"category": "general",
"text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
"title": "For More Information"
},
{
"category": "legal_disclaimer",
"text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
"title": "LEGAL DISCLAIMER"
},
{
"category": "general",
"text": "Schneider\u0027s purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and\r\nsustainability for all. We call this Life Is On.\n\nOur mission is to be the trusted partner in Sustainability and Efficiency.\n\nWe are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart\r\nindustries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep\r\ndomain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation,\r\nsoftware and services, delivering digital twins to enable profitable growth for our customers.\n\nWe are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries\r\nto ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our\r\nmeaningful purpose of a sustainable future for all. \n\n www.se.com",
"title": "About Schneider Electric"
},
{
"category": "summary",
"text": "Schneider Electric is aware of multiple vulnerabilities disclosed in PostgreSQL.\r\n\nMany vendors, including Schneider Electric, use PostgreSQL in their offers. PostgreSQL is a \r\ndatabase server that is used as a data store for multiple products.\r\n\nSchneider Electric installs a version of PostgreSQL with its EcoStruxure\u2122 Power Operation https://www.se.com/us/en/product-range/65405-ecostruxure-power-operation/?parent-subcategory-id=59326966\u0026filter=business-4-low-voltage-products-and-systems#overview software. \r\n\nEcoStruxure\u2122 Power Operation (EPO) is an on-premises software offer that provides a single \r\nplatform to monitor and control medium and lower power systems.\r\n\nFailure to apply the remediations and mitigations below could result in loss of system \r\nfunctionality or unauthorized access to system functions.",
"title": "Overview"
},
{
"category": "other",
"text": "Customers should use appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric\u2019s Customer Care Center if you need assistance removing a patch. "
},
{
"category": "details",
"text": "Vulnerability disclosed on PostgreSQL impact EcoStruxure\u2122 Power Operation software. \nThe vulnerabilities are all transitive dependencies of PostgreSQL that are remediated in version \n14.17. \n\u2022 CVE-2023-50447\n\u2022 CVE-2024-28219\n\u2022 CVE-2022-45198\n\u2022 CVE-2023-5217\n\u2022 CVE-2023-35945\n\u2022 CVE-2023-44487\n\nAdditional information about these vulnerabilities can be found on https://www.cve.org/",
"title": "Vulnerability Details"
}
],
"publisher": {
"category": "vendor",
"contact_details": "cpcert@se.com",
"name": "Schneider Electric CPCERT",
"namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
},
"references": [
{
"category": "self",
"summary": "EcoStruxure\u2122 Power Operation - SEVD-2025-189-03 PDF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-189-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-189-03.pdf"
},
{
"category": "self",
"summary": "EcoStruxure\u2122 Power Operation - SEVD-2025-189-03 CSAF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-189-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2025-189-03.json"
},
{
"category": "external",
"summary": "Recommended Cybersecurity Best Practices",
"url": "https://www.se.com/us/en/download/document/7EN52-0390/"
}
],
"title": "EcoStruxure\u2122 Power Operation",
"tracking": {
"current_release_date": "2025-07-08T04:00:00.000Z",
"generator": {
"date": "2025-07-07T16:42:48.096Z",
"engine": {
"name": "Schneider Electric CSAF Generator",
"version": "1.2"
}
},
"id": "SEVD-2025-189-03",
"initial_release_date": "2025-07-08T04:00:00.000Z",
"revision_history": [
{
"date": "2025-07-08T04:00:00.000Z",
"number": "1.0.0",
"summary": "Original Release"
}
],
"status": "final",
"version": "1.0.0"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c=CU6",
"product": {
"name": "Schneider Electric EcoStruxure\u2122 Power Operation (EPO) 2022 CU6 and prior",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "EcoStruxure\u2122 Power Operation (EPO) 2022"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c=CU1",
"product": {
"name": "Schneider Electric EcoStruxure\u2122 Power Operation (EPO) 2024 CU1 and prior",
"product_id": "2"
}
}
],
"category": "product_name",
"name": "EcoStruxure\u2122 Power Operation (EPO) 2024"
},
{
"branches": [
{
"category": "product_version",
"name": "CU2",
"product": {
"name": "Schneider Electric EcoStruxure\u2122 Power Operation 2024 CU2",
"product_id": "3"
}
}
],
"category": "product_name",
"name": "EcoStruxure\u2122 Power Operation 2024"
}
],
"category": "vendor",
"name": "Schneider Electric"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2023-50447",
"notes": [
{
"category": "description",
"text": "Pillow through 10.1.0 allows PIL.ImageMath.eval Arbitrary Code Execution via the environment parameter, a different vulnerability than CVE-2022-22817 (which was about the expression parameter).",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"3"
],
"known_affected": [
"1",
"2"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "EcoStruxure\u2122 Power Operation 2024 CU2 includes a fix for \nthis vulnerability and is available for download here:\nhttps://community.se.com/t5/EcoStruxure-Power\u0002Operation/v2024-Release-amp-Updates-Install\u0002Procedure/m-p/478928/thread-id/6997#M699",
"product_ids": [
"2"
],
"restart_required": {
"category": "none"
},
"url": "https://community.se.com/t5/EcoStruxure-Power-Operation/v2024-Release-amp-Updates-Install-Procedure/m-p/478928/thread-id/6997#M6997"
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided above, they should immediately \napply the following mitigations to reduce the risk of exploit: \n\u2022 If waveform analysis and ETAP simulation features are not used, uninstall PostgreSQL\nOR\n\u2022 For those customers using waveform analysis and ETAP simulation features, we \nrecommend all deployments of EPO only accept connections from localhost in \nPostgresSQL. Contact customer care for information on how to modify PostgreSQL.\nFurther, we recommend you manually uninstall PostgreSQL 14.10 and update to \nPostgreSQL 14.17 or higher.",
"product_ids": [
"2"
],
"restart_required": {
"category": "none"
}
},
{
"category": "mitigation",
"details": "Schneider Electric is establishing a remediation plan for all \nfuture versions of EcoStruxure\u2122 Power Operation 2022\nthat will include a fix for these vulnerabilities. We will \nupdate this document when the remediation is available. \nUntil then, customers should immediately apply the \nfollowing mitigations to reduce the risk of exploit:\n\u2022 Upgrade to EPO 2024 and apply CU2.\nOR\n\u2022 If waveform analysis and ETAP simulation features \nare not used, uninstall PostgreSQL\nOR\n\u2022 For those customers using waveform analysis and \nETAP simulation features, we recommend all \ndeployments of EPO only accept connections from \nlocalhost in PostgresSQL. Contact customer care \nfor information on how to modify PostgreSQL. \nFurther, we recommend you manually uninstall \nPostgreSQL 14.10 and update to PostgreSQL 14.17\nor higher.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "HIGH",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.1,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1",
"2"
]
}
],
"title": "CVE-2023-50447"
},
{
"cve": "CVE-2024-28219",
"notes": [
{
"category": "description",
"text": "In _imagingcms.c in Pillow before 10.3.0, a buffer overflow exists because strcpy is used instead of strncpy.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"3"
],
"known_affected": [
"1",
"2"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "EcoStruxure\u2122 Power Operation 2024 CU2 includes a fix for \nthis vulnerability and is available for download here:\nhttps://community.se.com/t5/EcoStruxure-Power\u0002Operation/v2024-Release-amp-Updates-Install\u0002Procedure/m-p/478928/thread-id/6997#M699",
"product_ids": [
"2"
],
"restart_required": {
"category": "none"
},
"url": "https://community.se.com/t5/EcoStruxure-Power-Operation/v2024-Release-amp-Updates-Install-Procedure/m-p/478928/thread-id/6997#M6997"
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided above, they should immediately \napply the following mitigations to reduce the risk of exploit: \n\u2022 If waveform analysis and ETAP simulation features are not used, uninstall PostgreSQL\nOR\n\u2022 For those customers using waveform analysis and ETAP simulation features, we \nrecommend all deployments of EPO only accept connections from localhost in \nPostgresSQL. Contact customer care for information on how to modify PostgreSQL.\nFurther, we recommend you manually uninstall PostgreSQL 14.10 and update to \nPostgreSQL 14.17 or higher.",
"product_ids": [
"2"
],
"restart_required": {
"category": "none"
}
},
{
"category": "mitigation",
"details": "Schneider Electric is establishing a remediation plan for all \nfuture versions of EcoStruxure\u2122 Power Operation 2022\nthat will include a fix for these vulnerabilities. We will \nupdate this document when the remediation is available. \nUntil then, customers should immediately apply the \nfollowing mitigations to reduce the risk of exploit:\n\u2022 Upgrade to EPO 2024 and apply CU2.\nOR\n\u2022 If waveform analysis and ETAP simulation features \nare not used, uninstall PostgreSQL\nOR\n\u2022 For those customers using waveform analysis and \nETAP simulation features, we recommend all \ndeployments of EPO only accept connections from \nlocalhost in PostgresSQL. Contact customer care \nfor information on how to modify PostgreSQL. \nFurther, we recommend you manually uninstall \nPostgreSQL 14.10 and update to PostgreSQL 14.17\nor higher.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "HIGH",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 6.7,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1",
"2"
]
}
],
"title": "CVE-2024-28219"
},
{
"cve": "CVE-2022-45198",
"notes": [
{
"category": "description",
"text": "Pillow before 9.2.0 performs Improper Handling of Highly Compressed GIF Data (Data Amplification).",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"3"
],
"known_affected": [
"1",
"2"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "EcoStruxure\u2122 Power Operation 2024 CU2 includes a fix for \nthis vulnerability and is available for download here:\nhttps://community.se.com/t5/EcoStruxure-Power\u0002Operation/v2024-Release-amp-Updates-Install\u0002Procedure/m-p/478928/thread-id/6997#M699",
"product_ids": [
"2"
],
"restart_required": {
"category": "none"
},
"url": "https://community.se.com/t5/EcoStruxure-Power-Operation/v2024-Release-amp-Updates-Install-Procedure/m-p/478928/thread-id/6997#M6997"
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided above, they should immediately \napply the following mitigations to reduce the risk of exploit: \n\u2022 If waveform analysis and ETAP simulation features are not used, uninstall PostgreSQL\nOR\n\u2022 For those customers using waveform analysis and ETAP simulation features, we \nrecommend all deployments of EPO only accept connections from localhost in \nPostgresSQL. Contact customer care for information on how to modify PostgreSQL.\nFurther, we recommend you manually uninstall PostgreSQL 14.10 and update to \nPostgreSQL 14.17 or higher.",
"product_ids": [
"2"
],
"restart_required": {
"category": "none"
}
},
{
"category": "mitigation",
"details": "Schneider Electric is establishing a remediation plan for all \nfuture versions of EcoStruxure\u2122 Power Operation 2022\nthat will include a fix for these vulnerabilities. We will \nupdate this document when the remediation is available. \nUntil then, customers should immediately apply the \nfollowing mitigations to reduce the risk of exploit:\n\u2022 Upgrade to EPO 2024 and apply CU2.\nOR\n\u2022 If waveform analysis and ETAP simulation features \nare not used, uninstall PostgreSQL\nOR\n\u2022 For those customers using waveform analysis and \nETAP simulation features, we recommend all \ndeployments of EPO only accept connections from \nlocalhost in PostgresSQL. Contact customer care \nfor information on how to modify PostgreSQL. \nFurther, we recommend you manually uninstall \nPostgreSQL 14.10 and update to PostgreSQL 14.17\nor higher.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"1",
"2"
]
}
],
"title": "CVE-2022-45198"
},
{
"cve": "CVE-2023-5217",
"notes": [
{
"category": "description",
"text": "Heap buffer overflow in vp8 encoding in libvpx in Google Chrome prior to 117.0.5938.132 and libvpx 1.13.1 allowed a remote attacker to potentially exploit heap corruption via a crafted HTML page. (Chromium security severity: High)",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"3"
],
"known_affected": [
"1",
"2"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "EcoStruxure\u2122 Power Operation 2024 CU2 includes a fix for \nthis vulnerability and is available for download here:\nhttps://community.se.com/t5/EcoStruxure-Power\u0002Operation/v2024-Release-amp-Updates-Install\u0002Procedure/m-p/478928/thread-id/6997#M699",
"product_ids": [
"2"
],
"restart_required": {
"category": "none"
},
"url": "https://community.se.com/t5/EcoStruxure-Power-Operation/v2024-Release-amp-Updates-Install-Procedure/m-p/478928/thread-id/6997#M6997"
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided above, they should immediately \napply the following mitigations to reduce the risk of exploit: \n\u2022 If waveform analysis and ETAP simulation features are not used, uninstall PostgreSQL\nOR\n\u2022 For those customers using waveform analysis and ETAP simulation features, we \nrecommend all deployments of EPO only accept connections from localhost in \nPostgresSQL. Contact customer care for information on how to modify PostgreSQL.\nFurther, we recommend you manually uninstall PostgreSQL 14.10 and update to \nPostgreSQL 14.17 or higher.",
"product_ids": [
"2"
],
"restart_required": {
"category": "none"
}
},
{
"category": "mitigation",
"details": "Schneider Electric is establishing a remediation plan for all \nfuture versions of EcoStruxure\u2122 Power Operation 2022\nthat will include a fix for these vulnerabilities. We will \nupdate this document when the remediation is available. \nUntil then, customers should immediately apply the \nfollowing mitigations to reduce the risk of exploit:\n\u2022 Upgrade to EPO 2024 and apply CU2.\nOR\n\u2022 If waveform analysis and ETAP simulation features \nare not used, uninstall PostgreSQL\nOR\n\u2022 For those customers using waveform analysis and \nETAP simulation features, we recommend all \ndeployments of EPO only accept connections from \nlocalhost in PostgresSQL. Contact customer care \nfor information on how to modify PostgreSQL. \nFurther, we recommend you manually uninstall \nPostgreSQL 14.10 and update to PostgreSQL 14.17\nor higher.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1",
"2"
]
}
],
"title": "CVE-2023-5217"
},
{
"cve": "CVE-2023-35945",
"notes": [
{
"category": "description",
"text": "Envoy is a cloud-native high-performance edge/middle/service proxy. Envoy\u2019s HTTP/2 codec may leak a header map and bookkeeping structures upon receiving `RST_STREAM` immediately followed by the `GOAWAY` frames from an upstream server. In nghttp2, cleanup of pending requests due to receipt of the `GOAWAY` frame skips de-allocation of the bookkeeping structure and pending compressed header. The error return [code path] is taken if connection is already marked for not sending more requests due to `GOAWAY` frame. The clean-up code is right after the return statement, causing memory leak. Denial of service through memory exhaustion. This vulnerability was patched in versions(s) 1.26.3, 1.25.8, 1.24.9, 1.23.11.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"3"
],
"known_affected": [
"1",
"2"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "EcoStruxure\u2122 Power Operation 2024 CU2 includes a fix for \nthis vulnerability and is available for download here:\nhttps://community.se.com/t5/EcoStruxure-Power\u0002Operation/v2024-Release-amp-Updates-Install\u0002Procedure/m-p/478928/thread-id/6997#M699",
"product_ids": [
"2"
],
"restart_required": {
"category": "none"
},
"url": "https://community.se.com/t5/EcoStruxure-Power-Operation/v2024-Release-amp-Updates-Install-Procedure/m-p/478928/thread-id/6997#M6997"
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided above, they should immediately \napply the following mitigations to reduce the risk of exploit: \n\u2022 If waveform analysis and ETAP simulation features are not used, uninstall PostgreSQL\nOR\n\u2022 For those customers using waveform analysis and ETAP simulation features, we \nrecommend all deployments of EPO only accept connections from localhost in \nPostgresSQL. Contact customer care for information on how to modify PostgreSQL.\nFurther, we recommend you manually uninstall PostgreSQL 14.10 and update to \nPostgreSQL 14.17 or higher.",
"product_ids": [
"2"
],
"restart_required": {
"category": "none"
}
},
{
"category": "mitigation",
"details": "Schneider Electric is establishing a remediation plan for all \nfuture versions of EcoStruxure\u2122 Power Operation 2022\nthat will include a fix for these vulnerabilities. We will \nupdate this document when the remediation is available. \nUntil then, customers should immediately apply the \nfollowing mitigations to reduce the risk of exploit:\n\u2022 Upgrade to EPO 2024 and apply CU2.\nOR\n\u2022 If waveform analysis and ETAP simulation features \nare not used, uninstall PostgreSQL\nOR\n\u2022 For those customers using waveform analysis and \nETAP simulation features, we recommend all \ndeployments of EPO only accept connections from \nlocalhost in PostgresSQL. Contact customer care \nfor information on how to modify PostgreSQL. \nFurther, we recommend you manually uninstall \nPostgreSQL 14.10 and update to PostgreSQL 14.17\nor higher.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"1",
"2"
]
}
],
"title": "CVE-2023-35945"
},
{
"cve": "CVE-2023-44487",
"notes": [
{
"category": "description",
"text": "The HTTP/2 protocol allows a denial of service (server resource consumption) because request cancellation can reset many streams quickly, as exploited in the wild in August through October 2023.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"3"
],
"known_affected": [
"1",
"2"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "EcoStruxure\u2122 Power Operation 2024 CU2 includes a fix for \nthis vulnerability and is available for download here:\nhttps://community.se.com/t5/EcoStruxure-Power\u0002Operation/v2024-Release-amp-Updates-Install\u0002Procedure/m-p/478928/thread-id/6997#M699",
"product_ids": [
"2"
],
"restart_required": {
"category": "none"
},
"url": "https://community.se.com/t5/EcoStruxure-Power-Operation/v2024-Release-amp-Updates-Install-Procedure/m-p/478928/thread-id/6997#M6997"
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided above, they should immediately \napply the following mitigations to reduce the risk of exploit: \n\u2022 If waveform analysis and ETAP simulation features are not used, uninstall PostgreSQL\nOR\n\u2022 For those customers using waveform analysis and ETAP simulation features, we \nrecommend all deployments of EPO only accept connections from localhost in \nPostgresSQL. Contact customer care for information on how to modify PostgreSQL.\nFurther, we recommend you manually uninstall PostgreSQL 14.10 and update to \nPostgreSQL 14.17 or higher.",
"product_ids": [
"2"
],
"restart_required": {
"category": "none"
}
},
{
"category": "mitigation",
"details": "Schneider Electric is establishing a remediation plan for all \nfuture versions of EcoStruxure\u2122 Power Operation 2022\nthat will include a fix for these vulnerabilities. We will \nupdate this document when the remediation is available. \nUntil then, customers should immediately apply the \nfollowing mitigations to reduce the risk of exploit:\n\u2022 Upgrade to EPO 2024 and apply CU2.\nOR\n\u2022 If waveform analysis and ETAP simulation features \nare not used, uninstall PostgreSQL\nOR\n\u2022 For those customers using waveform analysis and \nETAP simulation features, we recommend all \ndeployments of EPO only accept connections from \nlocalhost in PostgresSQL. Contact customer care \nfor information on how to modify PostgreSQL. \nFurther, we recommend you manually uninstall \nPostgreSQL 14.10 and update to PostgreSQL 14.17\nor higher.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"1",
"2"
]
}
],
"title": "CVE-2023-44487"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.