SEVD-2025-014-08
Vulnerability from csaf_se - Published: 2025-01-14 00:00 - Updated: 2025-01-14 00:00Summary
Power Logic HDPM6000 High-Density Metering System
Notes
General Security Recommendations
We strongly recommend the following industry cybersecurity best practices.
https://www.se.com/us/en/download/document/7EN52-0390/
* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
* Place all controllers in locked cabinets and never leave them in the “Program” mode.
* Never connect programming software to any network other than the network intended for that device.
* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.
For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.
For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.
We provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.
We are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.
www.se.com
Overview
Schneider Electric is aware of multiple vulnerabilities in its Power Logic HDPM6000 High-Density Metering
System product.
The HDPM6000 products are high-density, multi-circuit busway and panelboard power meters for cost and
network management in large and critical power applications.
Failure to apply the remediation provided below may risk a low privileged user gaining higher level access,
which could allow for modification of system configuration parameters or an unauthenticated user causing data
corruption or denial of service to the devices web interface via a specially crafted Modbus protocol write
operation.
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Public",
"tlp": {
"label": "WHITE"
}
},
"lang": "en-US",
"notes": [
{
"category": "general",
"text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
"title": "General Security Recommendations"
},
{
"category": "general",
"text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
"title": "For More Information"
},
{
"category": "legal_disclaimer",
"text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
"title": "LEGAL DISCLAIMER"
},
{
"category": "general",
"text": "At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.\n\nWe provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.\n\nWe are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.\n\nwww.se.com ",
"title": "About Schneider Electric"
},
{
"category": "summary",
"text": "Schneider Electric is aware of multiple vulnerabilities in its Power Logic HDPM6000 High-Density Metering \r\nSystem product. \r\nThe HDPM6000 products are high-density, multi-circuit busway and panelboard power meters for cost and \r\nnetwork management in large and critical power applications. \r\nFailure to apply the remediation provided below may risk a low privileged user gaining higher level access, \r\nwhich could allow for modification of system configuration parameters or an unauthenticated user causing data \r\ncorruption or denial of service to the devices web interface via a specially crafted Modbus protocol write \r\noperation.",
"title": "Overview"
}
],
"publisher": {
"category": "vendor",
"contact_details": "cpcert@se.com",
"name": "Schneider Electric CPCERT",
"namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
},
"references": [
{
"category": "self",
"summary": "Power Logic HDPM6000 High-Density Metering System - SEVD-2025-014-08 PDF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-014-08\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-014-08.pdf"
},
{
"category": "self",
"summary": "Power Logic HDPM6000 High-Density Metering System - SEVD-2025-014-08 CSAF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-014-08\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2025-014-08.json"
},
{
"category": "external",
"summary": "Recommended Cybersecurity Best Practices",
"url": "https://www.se.com/us/en/download/document/7EN52-0390/"
}
],
"title": "Power Logic HDPM6000 High-Density Metering System",
"tracking": {
"current_release_date": "2025-01-14T00:00:00.000Z",
"generator": {
"date": "2025-01-14T00:00:00Z",
"engine": {
"name": "Schneider Electric CSAF Generator",
"version": "1.2"
}
},
"id": "SEVD-2025-014-08",
"initial_release_date": "2025-01-14T00:00:00.000Z",
"revision_history": [
{
"date": "2025-01-14T00:00:00.000Z",
"number": "1.0.0",
"summary": "Original Release"
}
],
"status": "final",
"version": "1.0.0"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version",
"name": "v0.62.7",
"product": {
"name": "Schneider Electric Power Logic HDPM6000 Version 0.62.7 only",
"product_id": "1",
"product_identification_helper": {
"model_numbers": [
"HDPM6000"
]
}
}
}
],
"category": "product_name",
"name": "Power Logic"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c=0.62.7",
"product": {
"name": "Schneider Electric Power Logic HDPM6000 Versions 0.62.7 and prior",
"product_id": "2",
"product_identification_helper": {
"model_numbers": [
"HDPM6000"
]
}
}
}
],
"category": "product_name",
"name": "Power Logic"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003e=0.62.11",
"product": {
"name": "Schneider Electric Power Logic HDPM6000 Versions 0.62.11 and newer",
"product_id": "3",
"product_identification_helper": {
"model_numbers": [
"HDPM6000"
]
}
}
}
],
"category": "product_name",
"name": "Power Logic"
}
],
"category": "vendor",
"name": "Schneider Electric"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2024-10497",
"cwe": {
"id": "CWE-639",
"name": "Authorization Bypass Through User-Controlled Key"
},
"notes": [
{
"category": "description",
"text": "CWE-639: Authorization Bypass Through User-Controlled Key vulnerability exists that could allow an \r\nauthorized attacker to modify values outside those defined by their privileges (Elevation of Privileges) when the \r\nattacker sends modified HTTPS requests to the device.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"3"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Version v0.62.11 and newer of HDPM6000 includes a fix for \r\nthese vulnerabilities and is available for download here:\r\n\u2022 https://www.se.com/ww/en/product-range/8297113-\r\npowerlogic-hdpm6000/ - software-and-firmware\r\n\u2022 A device restart will occur as part of the firmware update \r\nprocess if conducted through the web user interface. If \r\nthe upgrade is performed using the HDPM6000 Manager \r\nsoftware, the device will need to be restarted manually to \r\napply the update.",
"product_ids": [
"1"
],
"restart_required": {
"category": "machine"
},
"url": "https://www.se.com/ww/en/product-range/8297113-powerlogic-hdpm6000/-software-and-firmware"
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided \r\nabove, they should immediately apply the following mitigations \r\nto reduce the risk of exploit:\r\n\u2022 Ensure that the device is not accessible via the HTTPS \r\nprotocol outside the local network segment by applying \r\nappropriate firewalls configuration and controls, and that \r\naccess to the network segment is protected and \r\ncontrolled.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2024-10497"
},
{
"cve": "CVE-2024-10498",
"cwe": {
"id": "CWE-119",
"name": "Improper Restriction of Operations within the Bounds of a Memory Buffer"
},
"notes": [
{
"category": "description",
"text": "CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that \r\ncould allow an unauthorized attacker to modify configuration values outside of the normal range when the \r\nattacker sends specific Modbus write packets to the device which could result in invalid data or loss of web\r\ninterface functionality.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"3"
],
"known_affected": [
"2"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Version v0.62.11 and newer of HDPM6000 includes a fix for \r\nthese vulnerabilities and is available for download here:\r\n\u2022 https://www.se.com/ww/en/product-range/8297113-\r\npowerlogic-hdpm6000/ - software-and-firmware\r\n\u2022 A device restart will occur as part of the firmware update \r\nprocess if conducted through the web user interface. If \r\nthe upgrade is performed using the HDPM6000 Manager \r\nsoftware, the device will need to be restarted manually to \r\napply the update.",
"product_ids": [
"2"
],
"restart_required": {
"category": "machine"
},
"url": "https://www.se.com/ww/en/product-range/8297113-powerlogic-hdpm6000/-software-and-firmware"
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided \r\nabove, they should immediately apply the following mitigations \r\nto reduce the risk of exploit:\r\n\u2022 Ensure that the device is not accessible via the Modbus \r\nprotocol outside the local network segment by applying \r\nappropriate firewalls configuration and controls, and that access to the network segment is protected and \r\ncontrolled.",
"product_ids": [
"2"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "LOW",
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"integrityImpact": "LOW",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L",
"version": "3.1"
},
"products": [
"2"
]
}
],
"title": "CVE-2024-10498"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Loading…
Loading…