SEVD-2024-254-01

Vulnerability from csaf_se - Published: 2024-09-10 00:00 - Updated: 2025-07-08 04:00
Summary
Vijeo Designer

Notes

General Security Recommendations
We strongly recommend the following industry cybersecurity best practices. https://www.se.com/us/en/download/document/7EN52-0390/ * Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. * Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. * Place all controllers in locked cabinets and never leave them in the “Program” mode. * Never connect programming software to any network other than the network intended for that device. * Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. * Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. * Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. * When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
Schneider's purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and sustainability for all. We call this Life Is On. Our mission is to be the trusted partner in Sustainability and Efficiency. We are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart industries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep domain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation, software and services, delivering digital twins to enable profitable growth for our customers. We are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries to ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our meaningful purpose of a sustainable future for all. www.se.com
Overview
Schneider Electric is aware of a vulnerability in its Vijeo Designer product. The Vijeo Designer https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/ product is HMI Configuration Software compatible with Harmony and Magelis HMI. Vijeo Designer software offers functions such as multimedia capabilities and remote access for more efficiency. Failure to apply the remediations provided below may risk privilege escalation, which could result in unauthorized access to workstation resources. July 2025 Update: A remediation is now available for EcoStruxure™ Machine Expert (with Vijeo Designer optional component installed).
The severity of vulnerabilities was calculated using the CVSS Base metrics in version 3.1 (CVSS v3.1) without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer's environment.
Customers should use appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric’s Customer Care Center if you need assistance removing a patch.

{
  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Public",
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\n\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
        "title": "General Security Recommendations"
      },
      {
        "category": "general",
        "text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
        "title": "For More Information"
      },
      {
        "category": "legal_disclaimer",
        "text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND.  SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
        "title": "LEGAL DISCLAIMER"
      },
      {
        "category": "general",
        "text": "Schneider\u0027s purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and\r\nsustainability for all. We call this Life Is On.\n\nOur mission is to be the trusted partner in Sustainability and Efficiency.\n\nWe are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart\r\nindustries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep\r\ndomain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation,\r\nsoftware and services, delivering digital twins to enable profitable growth for our customers.\n\nWe are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries\r\nto ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our\r\nmeaningful purpose of a sustainable future for all. \n\n www.se.com",
        "title": "About Schneider Electric"
      },
      {
        "category": "summary",
        "text": "Schneider Electric is aware of a vulnerability in its Vijeo Designer product.\n\n The Vijeo Designer https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/ product is HMI Configuration Software compatible with Harmony and Magelis HMI. Vijeo Designer software offers functions such as multimedia capabilities and remote access for more efficiency.\n\n Failure to apply the remediations provided below may risk privilege escalation, which could result in unauthorized access to workstation resources.\n\n July 2025 Update: A remediation is now available for EcoStruxure\u2122 Machine Expert (with Vijeo Designer optional component installed).",
        "title": "Overview"
      },
      {
        "category": "other",
        "text": "The severity of vulnerabilities was calculated using the CVSS Base metrics in version 3.1 (CVSS v3.1) without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer\u0027s environment."
      },
      {
        "category": "other",
        "text": "Customers should use appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric\u2019s Customer Care Center if you need assistance removing a patch. "
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "cpcert@se.com",
      "name": "Schneider Electric CPCERT",
      "namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
    },
    "references": [
      {
        "category": "self",
        "summary": "Vijeo Designer  - SEVD-2024-254-01 PDF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2024-254-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2024-254-01.pdf"
      },
      {
        "category": "self",
        "summary": "Vijeo Designer  - SEVD-2024-254-01 CSAF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2024-254-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2024-254-01.json"
      },
      {
        "category": "external",
        "summary": "Recommended Cybersecurity Best Practices",
        "url": "https://www.se.com/us/en/download/document/7EN52-0390/"
      }
    ],
    "title": "Vijeo Designer",
    "tracking": {
      "current_release_date": "2025-07-08T04:00:00.000Z",
      "generator": {
        "date": "2025-07-07T06:37:20.854Z",
        "engine": {
          "name": "Schneider Electric CSAF Generator",
          "version": "1.2"
        }
      },
      "id": "SEVD-2024-254-01",
      "initial_release_date": "2024-09-10T00:00:00.000Z",
      "revision_history": [
        {
          "date": "2024-09-10T00:00:00.000Z",
          "number": "1.0.0",
          "summary": "Original Release"
        },
        {
          "date": "2025-07-08T04:00:00.000Z",
          "number": "2.0.0",
          "summary": "A remediation is now available for EcoStruxure\u2122 Machine Expert (with Vijeo Designer optional component installed)."
        }
      ],
      "status": "final",
      "version": "2.0.0"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c6.3 SP1",
                "product": {
                  "name": "Schneider Electric Vijeo Designer Versions prior to V6.3 SP1",
                  "product_id": "1"
                }
              },
              {
                "category": "product_version",
                "name": "6.3 SP1",
                "product": {
                  "name": "Schneider Electric Vijeo Designer Version 6.3 SP1",
                  "product_id": "3"
                }
              },
              {
                "category": "product_version",
                "name": "6.3.2.16",
                "product": {
                  "name": "Schneider Electric Vijeo Designer Version 6.3.2.16",
                  "product_id": "4"
                }
              }
            ],
            "category": "product_name",
            "name": "Vijeo Designer "
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c2.3",
                "product": {
                  "name": "Schneider Electric EcoStruxure\u2122 Machine Expert Versions prior to v2.3",
                  "product_id": "2"
                }
              },
              {
                "category": "product_version",
                "name": "2.3",
                "product": {
                  "name": "Schneider Electric EcoStruxure\u2122 Machine Expert Version 2.3",
                  "product_id": "6"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure\u2122 Machine Expert"
          },
          {
            "category": "product_name",
            "name": "Vijeo Designer",
            "product": {
              "name": "Schneider Electric Vijeo Designer",
              "product_id": "8"
            }
          }
        ],
        "category": "vendor",
        "name": "Schneider Electric"
      }
    ],
    "relationships": [
      {
        "category": "optional_component_of",
        "full_product_name": {
          "name": "Schneider Electric Vijeo Designer optional component of Schneider Electric EcoStruxure\u2122 Machine Expert Versions prior to v2.3",
          "product_id": "5"
        },
        "product_reference": "8",
        "relates_to_product_reference": "2"
      },
      {
        "category": "optional_component_of",
        "full_product_name": {
          "name": "Schneider Electric Vijeo Designer Version 6.3.2.16 optional component of Schneider Electric EcoStruxure\u2122 Machine Expert Version 2.3",
          "product_id": "7"
        },
        "product_reference": "4",
        "relates_to_product_reference": "6"
      }
    ]
  },
  "vulnerabilities": [
    {
      "acknowledgments": [
        {
          "names": [
            "Charit Misra"
          ],
          "organization": "Applied Risk(DNV Cyber)"
        }
      ],
      "cve": "CVE-2024-8306",
      "cwe": {
        "id": "CWE-269",
        "name": "Improper Privilege Management"
      },
      "notes": [
        {
          "category": "description",
          "text": "CWE-269: Improper Privilege Management vulnerability exists that could cause unauthorized \r\naccess, loss of confidentiality, integrity and availability of the workstation when non-admin \r\nauthenticated user tries to perform privilege escalation by tampering with the binaries",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "3",
          "7"
        ],
        "known_affected": [
          "1",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:Limit authenticated user access to the workstation \r\nrunning Vijeo Designer and implement existing User \r\nAccount Control practices.\r\n\u2022 Remove the write permissions for \u201cEveryone\u201d on the \r\nfolder \u201cC:\\Program Files (x86)\\Schneider Electric\\Vijeo\u0002Designer 6.3\\Vijeo-Runtime\u201d\r\n\u2022 Follow workstation, network and site-hardening \r\nguidelines in the Recommended Cybersecurity Best \r\nPractices guide available for download here.",
          "product_ids": [
            "1",
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/7EN52-0390/"
        },
        {
          "category": "vendor_fix",
          "details": "Vijeo Designer version 6.3.2.16 delivered with EcoStruxure\u2122 Machine Expert v2.3 includes a fix for this vulnerability. EcoStruxure\u2122 Machine Expert v2.3 is available via the Schneider Electric Software Installer: https://www.se.com/ww/en/download/document/ESEMACS10_INSTALLER On the engineering workstation, install v2.3 of EcoStruxure\u2122 Machine Expert. ",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/ESEMACS10_INSTALLER"
        },
        {
          "category": "vendor_fix",
          "details": "Version V6.3 SP1 of Vijeo Designer includes a fix for this \r\nvulnerability and can be updated through the Schneider \r\nElectric Software Update (SESU) application.\r\nhttps://www.se.com/ww/en/product-range/1054-vijeo\u0002designer-hmi-software/#software-and-firmware\r\nOn the engineering workstation, update to v6.3 SP1 of \r\nVijeo Designer.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "LOCAL",
            "availabilityImpact": "HIGH",
            "baseScore": 7.8,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 7.8,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "LOW",
            "scope": "UNCHANGED",
            "temporalScore": 7.8,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "1",
            "5"
          ]
        }
      ],
      "title": "CVE-2024-8306"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.