SEVD-2023-283-01
Vulnerability from csaf_se - Published: 2023-10-10 12:00 - Updated: 2023-10-10 12:00Summary
SpaceLogic C-Bus Toolkit
Notes
General Security Recommendations
We strongly recommend the following industry cybersecurity best practices.
https://www.se.com/us/en/download/document/7EN52-0390/
* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
* Place all controllers in locked cabinets and never leave them in the “Program” mode.
* Never connect programming software to any network other than the network intended for that device.
* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.
For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.
For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.
We provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.
We are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.
www.se.com
Overview
Schneider Electric is aware of multiple vulnerabilities in its SpaceLogic C-Bus Toolkit products.
The SpaceLogic C-Bus Toolkit product is an application run on a personal computer to configure and commission C-Bus installations.
Failure to apply the remediations provided below may risk remote code execution, which could result in tampering of the SpaceLogic C-Bus home automation system.
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Public",
"tlp": {
"label": "WHITE"
}
},
"lang": "en-US",
"notes": [
{
"category": "general",
"text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
"title": "General Security Recommendations"
},
{
"category": "general",
"text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
"title": "For More Information"
},
{
"category": "legal_disclaimer",
"text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
"title": "LEGAL DISCLAIMER"
},
{
"category": "general",
"text": "At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.\n\nWe provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.\n\nWe are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.\n\nwww.se.com ",
"title": "About Schneider Electric"
},
{
"category": "summary",
"text": "Schneider Electric is aware of multiple vulnerabilities in its SpaceLogic C-Bus Toolkit products. \r\nThe SpaceLogic C-Bus Toolkit product is an application run on a personal computer to configure and commission C-Bus installations. \r\nFailure to apply the remediations provided below may risk remote code execution, which could result in tampering of the SpaceLogic C-Bus home automation system.",
"title": "Overview"
}
],
"publisher": {
"category": "vendor",
"contact_details": "cybersecurity@se.com",
"name": "Schneider Electric CPCERT",
"namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
},
"references": [
{
"category": "self",
"summary": "SpaceLogic C-Bus Toolkit - SEVD-2023-283-01 PDF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-283-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2023-283-01.pdf"
},
{
"category": "self",
"summary": "SpaceLogic C-Bus Toolkit - SEVD-2023-283-01 CSAF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-283-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2023-283-01.json"
},
{
"category": "self",
"summary": "Recommended Cybersecurity Best Practices",
"url": "https://www.se.com/us/en/download/document/7EN52-0390/"
}
],
"title": "SpaceLogic C-Bus Toolkit",
"tracking": {
"current_release_date": "2023-10-10T12:00:34.000Z",
"generator": {
"date": "2023-10-09T12:06:30Z",
"engine": {
"name": "Schneider Electric CSAF Generator",
"version": "1.1"
}
},
"id": "SEVD-2023-283-01",
"initial_release_date": "2023-10-10T12:00:34.000Z",
"revision_history": [
{
"date": "2023-10-10T12:00:34.000Z",
"number": "1",
"summary": "Original Release"
}
],
"status": "final",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c=1.16.3",
"product": {
"name": "Schneider Electric SpaceLogic C-Bus Toolkit V1.16.3 and prior",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "SpaceLogic C-Bus Toolkit"
},
{
"branches": [
{
"category": "product_version",
"name": "1.16.4",
"product": {
"name": "Schneider Electric SpaceLogic C-Bus Toolkit version 1.16.4",
"product_id": "2"
}
}
],
"category": "product_name",
"name": "SpaceLogic C-Bus Toolkit"
}
],
"category": "vendor",
"name": "Schneider Electric"
}
]
},
"vulnerabilities": [
{
"acknowledgments": [
{
"organization": "ZDI \u2013 Trend Micro"
}
],
"cve": "CVE-2023-5402",
"cwe": {
"id": "CWE-269",
"name": "Improper Privilege Management"
},
"notes": [
{
"category": "description",
"text": "A CWE-269: Improper Privilege Management vulnerability exists that could cause a remote \r\ncode execution when the transfer command is used over the network.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"2"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Version 1.16.4 of SpaceLogic C-Bus Toolkit includes a fix for this \r\nvulnerability and is available for download here:\r\nhttps://www.se.com/au/en/product-range/65976-spacelogic-cbus\u0002lighting-building-automation-system#software-and-firmware\r\nPlease reboot your PC after installation.\r\nVersion number can be seen by launching C-Bus Toolkit and \r\nselecting \u201cAbout\u2026\u201d option under the Help Menu",
"product_ids": [
"1"
],
"restart_required": {
"category": "system"
},
"url": "https://www.se.com/au/en/product-range/65976-spacelogic-cbus-lighting-building-automation-system/#software-and-firmware"
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided above, they should immediately \r\napply the following mitigation to reduce the risk of exploit:\r\n\u2022 Block TCP port 20023 to SpaceLogic C-Bus Toolkit by using the rules in the PC \r\nfirewall.\r\nBy doing this, the vulnerable commands could not then be used to compromise the PC \r\nby an external entity as the connection and ultimately the command will not be accepted \r\nby SpaceLogic C-Bus Toolkit.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2023-5402"
},
{
"acknowledgments": [
{
"organization": "ZDI \u2013 Trend Micro"
}
],
"cve": "CVE-2023-5399",
"cwe": {
"id": "CWE-22",
"name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)"
},
"notes": [
{
"category": "description",
"text": "A CWE-22: Improper Limitation of a Pathname to a Restricted Directory (\u0027Path \r\nTraversal\u0027) vulnerability exists that could cause tampering of files on the personal computer \r\nrunning C-Bus when using the File Command.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"2"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Version 1.16.4 of SpaceLogic C-Bus Toolkit includes a fix for this \r\nvulnerability and is available for download here:\r\nhttps://www.se.com/au/en/product-range/65976-spacelogic-cbus\u0002lighting-building-automation-system#software-and-firmware\r\nPlease reboot your PC after installation.\r\nVersion number can be seen by launching C-Bus Toolkit and \r\nselecting \u201cAbout\u2026\u201d option under the Help Menu",
"product_ids": [
"1"
],
"restart_required": {
"category": "system"
},
"url": "https://www.se.com/au/en/product-range/65976-spacelogic-cbus-lighting-building-automation-system/#software-and-firmware"
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided above, they should immediately \r\napply the following mitigation to reduce the risk of exploit:\r\n\u2022 Block TCP port 20023 to SpaceLogic C-Bus Toolkit by using the rules in the PC \r\nfirewall.\r\nBy doing this, the vulnerable commands could not then be used to compromise the PC \r\nby an external entity as the connection and ultimately the command will not be accepted \r\nby SpaceLogic C-Bus Toolkit.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": " CVE-2023-5399"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Loading…
Loading…