SEVD-2023-192-01

Vulnerability from csaf_se - Published: 2023-07-11 07:37 - Updated: 2023-07-11 07:37
Summary
​​StruxureWare Data Center Expert​

Notes

General Security Recommendations
We strongly recommend the following industry cybersecurity best practices. https://www.se.com/us/en/download/document/7EN52-0390/ * Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. * Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. * Place all controllers in locked cabinets and never leave them in the “Program” mode. * Never connect programming software to any network other than the network intended for that device. * Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. * Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. * Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. * When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment. We provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries. We are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values. www.se.com
Overview
Schneider Electric is aware of ​multiple vulnerabilities​ in its ​StruxureWare Data Center Expert (DCE) ​product. This product was recently renamed to EcoStruxure™ IT Data Center Expert. EcoStruxure™ IT Data Center Expert is a scalable monitoring software that collects, organizes, and distributes critical device information providing a comprehensive view of equipment. Failure to apply the remediations provided below may risk ​remote access and/or local privilege escalation​, which could result in loss of control and loss of availability of the appliance.

{
  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Public",
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
        "title": "General Security Recommendations"
      },
      {
        "category": "general",
        "text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
        "title": "For More Information"
      },
      {
        "category": "legal_disclaimer",
        "text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND.  SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
        "title": "LEGAL DISCLAIMER"
      },
      {
        "category": "general",
        "text": "At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.\n\nWe provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.\n\nWe are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.\n\nwww.se.com ",
        "title": "About Schneider Electric"
      },
      {
        "category": "summary",
        "text": "Schneider Electric is aware of \u200bmultiple vulnerabilities\u200b in its \u200bStruxureWare Data Center Expert (DCE) \u200bproduct. This product was recently renamed to EcoStruxure\u2122 IT Data Center Expert.   \r\n\r\nEcoStruxure\u2122 IT Data Center Expert is a scalable monitoring software that collects, organizes, and distributes critical device information providing a comprehensive view of equipment.  \r\nFailure to apply the remediations provided below may risk \u200bremote access and/or local privilege escalation\u200b, which could result in loss of control and loss of availability of the appliance.",
        "title": "Overview"
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "cybersecurity@se.com",
      "name": "Schneider Electric CPCERT",
      "namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
    },
    "references": [
      {
        "category": "self",
        "summary": "\u200b\u200bStruxureWare Data Center Expert\u200b - SEVD-2023-192-01 PDF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-192-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2023-192-01.pdf"
      },
      {
        "category": "self",
        "summary": "\u200b\u200bStruxureWare Data Center Expert\u200b - SEVD-2023-192-01 CSAF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-192-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2023-192-01.json"
      },
      {
        "category": "self",
        "summary": "Recommended Cybersecurity Best Practices",
        "url": "https://www.se.com/us/en/download/document/7EN52-0390/"
      }
    ],
    "title": "\u200b\u200bStruxureWare Data Center Expert\u200b",
    "tracking": {
      "current_release_date": "2023-07-11T07:37:38.000Z",
      "generator": {
        "date": "2023-07-06T07:45:24Z",
        "engine": {
          "name": "Schneider Electric CSAF Generator",
          "version": "1.1"
        }
      },
      "id": "SEVD-2023-192-01",
      "initial_release_date": "2023-07-11T07:37:38.000Z",
      "revision_history": [
        {
          "date": "2023-07-11T07:37:38.000Z",
          "number": "1",
          "summary": "Original Release"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=V7.9.3",
                "product": {
                  "name": "Schneider Electric StruxureWare Data Center Expert version V7.9.3 and prior",
                  "product_id": "1"
                }
              }
            ],
            "category": "product_name",
            "name": "StruxureWare Data Center Expert"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "V8.0",
                "product": {
                  "name": "Schneider Electric StruxureWare Data Center Expert version V8.0",
                  "product_id": "2"
                }
              }
            ],
            "category": "product_name",
            "name": "StruxureWare Data Center Expert"
          }
        ],
        "category": "vendor",
        "name": "Schneider Electric"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2023-37196",
      "cwe": {
        "id": "CWE-89",
        "name": "Improper Neutralization of Special Elements used in an SQL Command (\u0027SQL Injection\u0027)"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-89: Improper Neutralization of Special Elements used in an SQL Command (\u0027SQL Injection\u0027) vulnerability exists that could allow a user already authenticated on DCE to access unauthorized content, change, or delete content, or perform unauthorized actions when tampering with the alert settings of endpoints on DCE.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "2"
        ],
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "\u200b\u200b\u200bVersion \u200b8.0\u200b of EcoStruxure\u2122 IT Data Center Expert (Formerly StruxureWare Data Center Expert) includes fixes for these vulnerabilities and is available on request from Schneider Electric\u2019s Customer Care Center.\u200b\u200b ",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          }
        },
        {
          "category": "mitigation",
          "details": "If customers choose not to apply the remediation provided above, they should immediately apply the following general security recommendations to reduce the risk of exploit:  \r\nHarden the DCE instance according to the cybersecurity best practices documented in the Data Center Expert Security Handbook ",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://dcimsupport.ecostruxureit.com/hc/en-us/articles/360039289633-Data-Center-Expert-Security-Handbook"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 8.8,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 8.8,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "LOW",
            "scope": "UNCHANGED",
            "temporalScore": 8.8,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2023-37196\u200b"
    },
    {
      "cve": "CVE-2023-37197",
      "cwe": {
        "id": "CWE-89",
        "name": "Improper Neutralization of Special Elements used in an SQL Command (\u0027SQL Injection\u0027)"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-89: Improper Neutralization of Special Elements used in an SQL Command (\u0027SQL Injection\u0027) vulnerability exists that could allow a user already authenticated on DCE to access unauthorized content, change, or delete content, or perform unauthorized actions when tampering with the mass configuration settings of endpoints on DCE",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "2"
        ],
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "\u200b\u200b\u200bVersion \u200b8.0\u200b of EcoStruxure\u2122 IT Data Center Expert (Formerly StruxureWare Data Center Expert) includes fixes for these vulnerabilities and is available on request from Schneider Electric\u2019s Customer Care Center.\u200b\u200b ",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          }
        },
        {
          "category": "mitigation",
          "details": "If customers choose not to apply the remediation provided above, they should immediately apply the following general security recommendations to reduce the risk of exploit:  \r\nHarden the DCE instance according to the cybersecurity best practices documented in the Data Center Expert Security Handbook ",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://dcimsupport.ecostruxureit.com/hc/en-us/articles/360039289633-Data-Center-Expert-Security-Handbook"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 8.8,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 8.8,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "LOW",
            "scope": "UNCHANGED",
            "temporalScore": 8.8,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2023-37197"
    },
    {
      "cve": "CVE-2023-37198",
      "cwe": {
        "id": "CWE-94",
        "name": "Improper Control of Generation of Code (\u0027Code Injection\u0027)"
      },
      "notes": [
        {
          "category": "description",
          "text": "A\u202fCWE-94: Improper Control of Generation of Code (\u0027Code Injection\u0027)\u202fvulnerability exists\u202fthat could cause\u202fremote code execution\u202fwhen an admin user on DCE uploads or tampers with install packages.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "2"
        ],
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "\u200b\u200b\u200bVersion \u200b8.0\u200b of EcoStruxure\u2122 IT Data Center Expert (Formerly StruxureWare Data Center Expert) includes fixes for these vulnerabilities and is available on request from Schneider Electric\u2019s Customer Care Center.\u200b\u200b ",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          }
        },
        {
          "category": "mitigation",
          "details": "If customers choose not to apply the remediation provided above, they should immediately apply the following general security recommendations to reduce the risk of exploit:  \r\nHarden the DCE instance according to the cybersecurity best practices documented in the Data Center Expert Security Handbook ",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://dcimsupport.ecostruxureit.com/hc/en-us/articles/360039289633-Data-Center-Expert-Security-Handbook"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 6.8,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "REQUIRED",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:R/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2023-37198\u200b"
    },
    {
      "cve": "CVE-2023-37199",
      "cwe": {
        "id": "CWE-94",
        "name": "Improper Control of Generation of Code (\u0027Code Injection\u0027)"
      },
      "notes": [
        {
          "category": "description",
          "text": "A\u202fCWE-94: Improper Control of Generation of Code (\u0027Code Injection\u0027)\u202fvulnerability exists\u202fthat could cause\u202fremote code execution\u202fwhen an admin user on\u202fDCE tampers with backups which are then manually restored. ",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "2"
        ],
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "\u200b\u200b\u200bVersion \u200b8.0\u200b of EcoStruxure\u2122 IT Data Center Expert (Formerly StruxureWare Data Center Expert) includes fixes for these vulnerabilities and is available on request from Schneider Electric\u2019s Customer Care Center.\u200b\u200b ",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          }
        },
        {
          "category": "mitigation",
          "details": "If customers choose not to apply the remediation provided above, they should immediately apply the following general security recommendations to reduce the risk of exploit:  \r\nHarden the DCE instance according to the cybersecurity best practices documented in the Data Center Expert Security Handbook ",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://dcimsupport.ecostruxureit.com/hc/en-us/articles/360039289633-Data-Center-Expert-Security-Handbook"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 6.8,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "userInteraction": "REQUIRED",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:R/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2023-37199"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…