SEVD-2023-101-05

Vulnerability from csaf_se - Published: 2023-04-11 09:46 - Updated: 2024-08-13 00:00
Summary
Modicon PLCs (Programmable Logic Controllers) and PACs (Programmable Automation Controllers)

Notes

General Security Recommendations
We strongly recommend the following industry cybersecurity best practices. https://www.se.com/us/en/download/document/7EN52-0390/ * Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. * Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. * Place all controllers in locked cabinets and never leave them in the “Program” mode. * Never connect programming software to any network other than the network intended for that device. * Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. * Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. * Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. * When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
Note regarding vulnerability details
The severity of vulnerabilities was calculated using the CVSS Base metrics in version 3.1 (CVSS v3.1) without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer’s environment
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment. We provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries. We are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values. www.se.com
Overview
Schneider Electric is aware of multiple vulnerabilities in its Modicon PLCs (Programmable Logic Controllers) and PACs (Programmable Automation Controllers). Modicon PLCs (Programmable Logic Controllers) and PACs (Programmable Automation Controllers) control and monitor industrial operations in a sustainable, flexible, efficient, and protected way. Failure to apply the remediations and mitigations provided below may risk a denial of service of the controller, which could result in disrupted operations.
Note
Regarding vulnerability details: The severity of vulnerabilities was calculated using the CVSS Base metrics in version 3.1 (CVSS v3.1) without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer’s environment.

{
  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Public",
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
        "title": "General Security Recommendations"
      },
      {
        "category": "general",
        "text": "The severity of vulnerabilities was calculated using the CVSS Base metrics in version 3.1 (CVSS v3.1) without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer\u2019s environment",
        "title": "Note regarding vulnerability details"
      },
      {
        "category": "general",
        "text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
        "title": "For More Information"
      },
      {
        "category": "legal_disclaimer",
        "text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND.  SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
        "title": "LEGAL DISCLAIMER"
      },
      {
        "category": "general",
        "text": "At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.\n\nWe provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.\n\nWe are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.\n\nwww.se.com ",
        "title": "About Schneider Electric"
      },
      {
        "category": "summary",
        "text": "Schneider Electric is aware of multiple vulnerabilities in its Modicon PLCs (Programmable Logic Controllers) and PACs (Programmable Automation Controllers).\r\nModicon PLCs (Programmable Logic Controllers) and PACs (Programmable Automation Controllers) control and monitor industrial operations in a sustainable, flexible, efficient, and protected way. \r\nFailure to apply the remediations and mitigations provided below may risk a denial of service of the controller, which could result in disrupted operations.",
        "title": "Overview"
      },
      {
        "category": "general",
        "text": "Regarding vulnerability details: The severity of vulnerabilities was calculated using the CVSS Base metrics in version 3.1 (CVSS v3.1) without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer\u2019s environment.",
        "title": "Note"
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "cpcert@se.com",
      "name": "Schneider Electric CPCERT",
      "namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
    },
    "references": [
      {
        "category": "self",
        "summary": "Modicon PLCs (Programmable Logic Controllers) and PACs (Programmable Automation Controllers)  - SEVD-2023-101-05 PDF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-101-05\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2023-101-05.pdf"
      },
      {
        "category": "self",
        "summary": "Modicon PLCs (Programmable Logic Controllers) and PACs (Programmable Automation Controllers)  - SEVD-2023-101-05 CSAF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-101-05\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2023-101-05.json"
      },
      {
        "category": "external",
        "summary": "Recommended Cybersecurity Best Practices",
        "url": "https://www.se.com/us/en/download/document/7EN52-0390/"
      }
    ],
    "title": "Modicon PLCs (Programmable Logic Controllers) and PACs (Programmable Automation Controllers) ",
    "tracking": {
      "current_release_date": "2024-08-13T00:00:00.000Z",
      "generator": {
        "date": "2024-08-13T00:00:00.000Z",
        "engine": {
          "name": "Schneider Electric CSAF Generator",
          "version": "1.2"
        }
      },
      "id": "SEVD-2023-101-05",
      "initial_release_date": "2023-04-11T09:46:26.000Z",
      "revision_history": [
        {
          "date": "2023-04-11T09:46:26.000Z",
          "number": "1.0.0",
          "summary": "Original Release"
        },
        {
          "date": "2024-03-12T04:36:25.000Z",
          "number": "2.0.0",
          "summary": "A remediation is available for Modicon MC80."
        },
        {
          "date": "2024-05-14T00:00:00.000Z",
          "number": "3.0.0",
          "summary": "A remediation is now available on Modicon Momentum Unity M1E Processor."
        },
        {
          "date": "2024-08-13T00:00:00.000Z",
          "number": "4.0.0",
          "summary": "A remediation is available for Modicon M580 CPU Safety (page 2)."
        }
      ],
      "status": "final",
      "version": "4.0.0"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c SV3.51",
                "product": {
                  "name": "Schneider Electric Modicon M340 CPU versions prior to SV3.51",
                  "product_id": "1"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M340 CPU"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c4.10",
                "product": {
                  "name": "Schneider Electric Modicon M580 CPU versions prior to  V4.10",
                  "product_id": "2"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M580 CPU"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c SV4.21",
                "product": {
                  "name": "Schneider Electric Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) Versions prior to SV4.21",
                  "product_id": "3",
                  "product_identification_helper": {
                    "model_numbers": [
                      "BMEP58*S",
                      "BMEH58*S"
                    ]
                  }
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M580 CPU Safety"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003csv2.70",
                "product": {
                  "name": "Schneider Electric Modicon Momentum Unity M1E Processor all versions prior to sv2.70",
                  "product_id": "4"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon Momentum Unity M1E Processor "
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "SV2.70",
                "product": {
                  "name": "Schneider Electric Modicon Momentum Unity M1E Processor SV2.70",
                  "product_id": "11"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon Momentum Unity M1E Processor "
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003cSV2.0",
                "product": {
                  "name": "Schneider Electric Modicon MC80 versions prior to SV2.0",
                  "product_id": "5"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon MC80"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "Schneider Electric Legacy Modicon Quantum all versions",
                  "product_id": "6"
                }
              }
            ],
            "category": "product_name",
            "name": "Legacy Modicon Quantum "
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "Schneider Electric Legacy Modicon Premium CPUs all versions",
                  "product_id": "7"
                }
              }
            ],
            "category": "product_name",
            "name": "Legacy Modicon Premium CPUs"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "SV4.10",
                "product": {
                  "name": "Schneider Electric Modicon M580 SV4.10",
                  "product_id": "8"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M580"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "SV3.51",
                "product": {
                  "name": "Schneider Electric Modicon M340 SV3.51",
                  "product_id": "9"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M340"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "SV2.0",
                "product": {
                  "name": "Schneider Electric Modicon MC80 (BMKC80)",
                  "product_id": "10"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon MC80 (BMKC80)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "SV4.21",
                "product": {
                  "name": "Schneider Electric Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) SV4.21",
                  "product_id": "12",
                  "product_identification_helper": {
                    "model_numbers": [
                      "BMEP58*S",
                      "BMEH58*S"
                    ]
                  }
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M580 CPU Safety"
          }
        ],
        "category": "vendor",
        "name": "Schneider Electric"
      }
    ]
  },
  "vulnerabilities": [
    {
      "acknowledgments": [
        {
          "names": [
            "Sun Yue"
          ],
          "organization": "Chinese Academy of Sciences"
        }
      ],
      "cve": "CVE-2023-25619",
      "cwe": {
        "id": "CWE-754",
        "name": "Improper Check for Unusual or Exceptional Conditions"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that\r\ncould cause denial of service of the controller when communicating over the Modbus TCP \r\nprotocol",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "8",
          "9",
          "10",
          "11",
          "12"
        ],
        "known_affected": [
          "1",
          "2",
          "3",
          "4",
          "5",
          "7"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Firmware SV4.10 includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/BMEx58x0x0_SV04.10",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/BMEx58x0x0_SV04.10"
        },
        {
          "category": "vendor_fix",
          "details": "Firmware SV3.51 includes a fix for these vulnerabilities and is available for download here: \r\nhttps://www.se.com/ww/en/product-range/1468-modicon\u0002m340/#software-and-firmware",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/1468-modicon-m340/#software-and-firmware"
        },
        {
          "category": "vendor_fix",
          "details": "Firmware sv2.0 includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/BMKC80_Firmware_upgrade/",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/BMKC80_Firmware_upgrade/"
        },
        {
          "category": "vendor_fix",
          "details": "Firmware SV4.21 includes a fix for these vulnerabilities and is \r\navailable for download here: \r\nhttps://www.se.com/ww/en/product-range/62098-modicon-m580-epac-controller/#software-and-firmware\r\n Important: customer needs to use version of EcoStruxure\u2122 \r\nControl Expert V16.0 HF001 minimum to connect with the latest \r\nversion of M580 CPU Safety. The software is available for \r\ndownload here: tps://www.se.com/ww/en/product-range/548-ecostruxurecontrol-expert-unity-pro/#software-and-firmware",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/62098-modicon-m580-epac-controller/#software-and-firmware"
        },
        {
          "category": "mitigation",
          "details": "\u2022 Setup an application password in the project properties. \r\n\u2022 Setup network segmentation and implement a firewall to block all unauthorized access \r\nto port 502/TCP. \r\nFor Modicon Controllers, when loading a project file through EcoStruxure\u2122 Control Expert, \r\nensure the following: \r\n\u2022 Enable the file encryption feature for all new projects. \r\n\u2022 Encrypt project files when stored and restrict the access to only trusted users. \r\n\u2022 When exchanging files over the network, use secure communication protocols. \r\n\u2022 Only open project files received from trusted source, and it is recommended to share \r\nproject files only when configured with the encryption feature.",
          "product_ids": [
            "1",
            "2"
          ],
          "restart_required": {
            "category": "none"
          }
        },
        {
          "category": "mitigation",
          "details": "\u2022 Configure the Access Control List following the \r\nrecommendations of the user manuals \u201cModicon M340 for \r\nEthernet Communications Modules and Processors User \r\nManual\u201d in chapter \u201cMessaging Configuration Parameters\u201d: \r\nhttps://www.se.com/ww/en/download/document/31007131K010\r\n00/\r\n\u2022 Setup a secure communication according to the following \r\nguideline \u201cModicon Controllers Platform Cyber Security \r\nReference Manual,\u201d in chapter \u201cSetup secured \r\ncommunications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO000000199\r\n9/\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 \r\nfrom Belden to establish VPN connections for M340 \u0026 M580 \r\narchitectures. For more details refer to the chapter \u201cHow to \r\nprotect M580 and M340 architectures with EAGLE40 using \r\nVPN\u201d: \r\nhttps://www.se.com/ww/en/download/document/EIO000000199\r\n9/\r\n\u2022 Ensure the M340 CPU is running with the memory protection \r\nactivated by configuring the input bit to a physical input, for more \r\ndetails refer to the following guideline \u201cModicon Controllers \r\nPlatform Cyber Security Reference Manual\u201d, \u201cCPU Memory \r\nProtection section\u201d: https://www.schneider\u0002electric.com/en/download/document/EIO0000001999/",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          }
        },
        {
          "category": "mitigation",
          "details": "\u2022 Configure the Access Control List following the \r\nrecommendations of the user manuals: \u201cModicon M580, \r\nHardware, Reference Manual\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO000000157\r\n8/\r\n\u2022 Setup a secure communication according to the following \r\nguideline \u201cModicon Controllers Platform Cyber Security \r\nReference Manual,\u201d in chapter \u201cSetup secured \r\ncommunications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO000000199\r\n9/\r\n\u2022 use a BMENOC module and follow the instructions to \r\nconfigure IPSEC feature as described in the guideline \r\n\u201cModicon M580 - BMENOC03.1 Ethernet \r\nCommunications Schneider Electric Security Notification \r\nModule, Installation and Configuration Guide\u201d in the \r\nchapter \u201cConfiguring IPSEC communications\u201d: \r\nhttps://www.se.com/ww/en/download/document/HRB626\r\n65/ \r\nOR\r\n\u2022 Use a BMENUA0100 module and follow the instructions to \r\nconfigure IPSEC feature as described in the chapter \r\n\u201cConfiguring the BMENUA0100 Cybersecurity Settings\u201d:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 \r\nfrom Belden to establish VPN connections for M340 \u0026 M580 \r\narchitectures. For more details refer to the chapter \u201cHow to \r\nprotect M580 and M340 architectures with EAGLE40 using \r\nVPN\u201d: \r\nhttps://www.se.com/ww/en/download/document/EIO000000199\r\n9/ \r\n\u2022 Ensure the M580 CPU is running with the memory protection \r\nactivated by configuring the input bit to a physical input, for more \r\ndetails refer to the following guideline \u201cModicon Controllers \r\nPlatform Cyber Security Reference Manual\u201d, \u201cCPU Memory \r\nProtection section\u201d: \r\nhttps://www.schneider\u0002electric.com/en/download/document/EIO0000001999/\r\n\u2022 NOTE: The CPU memory protection cannot be \r\nconfigured with M580 Hot Standby CPUs. In such \r\ncases, use IPsec encrypted communication.\r\n",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          }
        },
        {
          "category": "mitigation",
          "details": "If customers choose not to apply the remediation then they are encouraged to immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Configure the Access Control List following the \r\nrecommendations of the user manuals: \u201cModicon M580, \r\nHardware, Reference Manual\u201d\r\nhttps://www.se.com/ww/en/download/document/EIO000000157\r\n8/\r\n\u2022 Setup a secure communication according to the following \r\nguideline \u201cModicon Controllers Platform Cyber Security \r\nReference Manual,\u201d in chapter \u201cSetup secured \r\ncommunications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO000000199\r\n9/\r\n\u2022 use a BMENOC module and follow the instructions to \r\nconfigure IPSEC feature as described in the guideline \r\n\u201cModicon M580 - BMENOC03.1 Ethernet \r\nCommunications Schneider Electric Security Notification \r\nModule, Installation and Configuration Guide\u201d in the \r\nchapter \u201cConfiguring IPSEC communications\u201d: \r\nhttps://www.se.com/ww/en/download/document/HRB626\r\n65/ \r\nOR\r\n\u2022 Use a BMENUA0100 module and follow the instructions to \r\nconfigure IPSEC feature as described in the chapter \r\n\u201cConfiguring the BMENUA0100 Cybersecurity Settings\u201d:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 \r\nfrom Belden to establish VPN connections for M340 \u0026 M580 \r\narchitectures. For more details refer to the chapter \u201cHow to \r\nprotect M580 and M340 architectures with EAGLE40 using \r\nVPN\u201d: \r\nhttps://www.se.com/ww/en/download/document/EIO000000199\r\n9/ \r\n\u2022 Ensure the M580 CPU is running with the memory protection \r\nactivated by configuring the input bit to a physical input, for more \r\ndetails refer to the following guideline \u201cModicon Controllers \r\nPlatform Cyber Security Reference Manual\u201d, \u201cCPU Memory \r\nProtection section\u201d: https://www.schneider\u0002electric.com/en/download/document/EIO0000001999/ . \u2022 NOTE: The CPU memory protection cannot be configured with M580 Hot Standby CPUs. In such cases, use IPsec encrypted communication. To further reduce the attack surface on Modicon M580 CPU Safety: \u2022 Ensure the CPU is running in Safety mode and maintenance input is configured to maintain this Safety mode during operation \u2013 refer to the document Modicon M580 - Safety System Planning Guide - in the chapter \u201cOperating Mode Transitions\u201d:https://www.se.com/ww/en/download/document/QGH60283",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          }
        },
        {
          "category": "vendor_fix",
          "details": "Firmware sv2.70 includes a fix for these vulnerabilities and is available for download here: https://www.se.com/ww/en/product-range/535-modiconmomentum/-software-and-firmware",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/535-modiconmomentum/-software-and-firmware"
        },
        {
          "category": "mitigation",
          "details": "Schneider Electric is establishing a remediation plan for all future \r\nversions of Modicon MC80 controllers that will include a fix for these\r\nvulnerabilities. We will update this document when the remediation is \r\navailable. Until then, customers should immediately apply the following \r\nmitigations to reduce the risk of exploit:\r\n\u2022 Configure the Access Control List following the \r\nrecommendations of the user manuals:\r\n\u2022 \u201cModicon MC80 Programmable Logic Controller (PLC) \r\nmanual\u201d in the chapter \u201cAccess Control List (ACL)\u201d: \r\nhttps://www.se.com/ww/en/download/document/EIO000\r\n0002071/ \r\n\u2022 Setup a secure communication according to the \r\nfollowing guideline \u201cModicon Controllers Platform Cyber \r\nSecurity Reference Manual,\u201d in chapter \u201cSetup secured \r\ncommunications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO000\r\n0001999",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          }
        },
        {
          "category": "mitigation",
          "details": "Schneider Electric\u2019s Modicon Premium \u0026 Quantum controllers have \r\nreached their end of life and are no longer commercially available. They \r\nhave been replaced by the Modicon M580 ePAC controller, our most \r\ncurrent product offer. \r\nCustomers should strongly consider migrating to the Modicon M580 \r\nePAC. Please contact your local Schneider Electric technical support for \r\nmore information. \r\nTo mitigate the risks users should immediately: \r\n\u2022 Configure the Access Control List following the \r\nrecommendations of the user manual \u201cPremium and Atrium \r\nusing EcoStruxure\u2122 Control Expert \u2013 Ethernet Network \r\nModules, User Manual\u201d in chapters \u201cConnection configuration \r\nparameters / TCP/IP Services Configuration Parameters / \r\nConnection Configuration Parameters\u201d:\r\nhttps://www.se.com/ww/en/download/document/35006192K010\r\n00",
          "product_ids": [
            "7"
          ],
          "restart_required": {
            "category": "none"
          }
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "1",
            "2",
            "3",
            "4",
            "5",
            "7"
          ]
        }
      ],
      "title": "CVE-2023-25619"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Sun Yue"
          ],
          "organization": "Chinese Academy of Sciences"
        }
      ],
      "cve": "CVE-2023-25620",
      "cwe": {
        "id": "CWE-754",
        "name": "Improper Check for Unusual or Exceptional Conditions"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that\r\ncould cause denial of service of the controller when a malicious project file is loaded onto the \r\ncontroller by an authenticated user. ",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "8",
          "9",
          "10",
          "11",
          "12"
        ],
        "known_affected": [
          "1",
          "2",
          "3",
          "4",
          "5",
          "6",
          "7"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Firmware SV4.10 includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/BMEx58x0x0_SV04.10",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/BMEx58x0x0_SV04.10"
        },
        {
          "category": "vendor_fix",
          "details": "Firmware SV3.51 includes a fix for these vulnerabilities and is available for download here: \r\nhttps://www.se.com/ww/en/product-range/1468-modicon\u0002m340/#software-and-firmware",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/1468-modicon-m340/#software-and-firmware"
        },
        {
          "category": "vendor_fix",
          "details": "Firmware sv2.0 includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/BMKC80_Firmware_upgrade/",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/BMKC80_Firmware_upgrade/"
        },
        {
          "category": "vendor_fix",
          "details": "Firmware SV4.21 includes a fix for these vulnerabilities and is \r\navailable for download here: \r\nhttps://www.se.com/ww/en/product-range/62098-modicon-m580-epac-controller/#software-and-firmware\r\n Important: customer needs to use version of EcoStruxure\u2122 \r\nControl Expert V16.0 HF001 minimum to connect with the latest \r\nversion of M580 CPU Safety. The software is available for \r\ndownload here: tps://www.se.com/ww/en/product-range/548-ecostruxurecontrol-expert-unity-pro/#software-and-firmware",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/62098-modicon-m580-epac-controller/#software-and-firmware"
        },
        {
          "category": "vendor_fix",
          "details": "Firmware sv2.70 includes a fix for these vulnerabilities and is available for download here: https://www.se.com/ww/en/product-range/535-modiconmomentum/-software-and-firmware",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/535-modiconmomentum/-software-and-firmware"
        },
        {
          "category": "mitigation",
          "details": "\u2022 Setup an application password in the project properties. \r\n\u2022 Setup network segmentation and implement a firewall to block all unauthorized access \r\nto port 502/TCP. \r\nFor Modicon Controllers, when loading a project file through EcoStruxure\u2122 Control Expert, \r\nensure the following: \r\n\u2022 Enable the file encryption feature for all new projects. \r\n\u2022 Encrypt project files when stored and restrict the access to only trusted users. \r\n\u2022 When exchanging files over the network, use secure communication protocols. \r\n\u2022 Only open project files received from trusted source, and it is recommended to share \r\nproject files only when configured with the encryption feature.",
          "product_ids": [
            "1",
            "2"
          ],
          "restart_required": {
            "category": "none"
          }
        },
        {
          "category": "mitigation",
          "details": "\u2022 Configure the Access Control List following the \r\nrecommendations of the user manuals \u201cModicon M340 for \r\nEthernet Communications Modules and Processors User \r\nManual\u201d in chapter \u201cMessaging Configuration Parameters\u201d: \r\nhttps://www.se.com/ww/en/download/document/31007131K010\r\n00/\r\n\u2022 Setup a secure communication according to the following \r\nguideline \u201cModicon Controllers Platform Cyber Security \r\nReference Manual,\u201d in chapter \u201cSetup secured \r\ncommunications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO000000199\r\n9/\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 \r\nfrom Belden to establish VPN connections for M340 \u0026 M580 \r\narchitectures. For more details refer to the chapter \u201cHow to \r\nprotect M580 and M340 architectures with EAGLE40 using \r\nVPN\u201d: \r\nhttps://www.se.com/ww/en/download/document/EIO000000199\r\n9/\r\n\u2022 Ensure the M340 CPU is running with the memory protection \r\nactivated by configuring the input bit to a physical input, for more \r\ndetails refer to the following guideline \u201cModicon Controllers \r\nPlatform Cyber Security Reference Manual\u201d, \u201cCPU Memory \r\nProtection section\u201d: https://www.schneider\u0002electric.com/en/download/document/EIO0000001999/",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          }
        },
        {
          "category": "mitigation",
          "details": "\u2022 Configure the Access Control List following the \r\nrecommendations of the user manuals: \u201cModicon M580, \r\nHardware, Reference Manual\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO000000157\r\n8/\r\n\u2022 Setup a secure communication according to the following \r\nguideline \u201cModicon Controllers Platform Cyber Security \r\nReference Manual,\u201d in chapter \u201cSetup secured \r\ncommunications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO000000199\r\n9/\r\n\u2022 use a BMENOC module and follow the instructions to \r\nconfigure IPSEC feature as described in the guideline \r\n\u201cModicon M580 - BMENOC03.1 Ethernet \r\nCommunications Schneider Electric Security Notification \r\nModule, Installation and Configuration Guide\u201d in the \r\nchapter \u201cConfiguring IPSEC communications\u201d: \r\nhttps://www.se.com/ww/en/download/document/HRB626\r\n65/ \r\nOR\r\n\u2022 Use a BMENUA0100 module and follow the instructions to \r\nconfigure IPSEC feature as described in the chapter \r\n\u201cConfiguring the BMENUA0100 Cybersecurity Settings\u201d:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 \r\nfrom Belden to establish VPN connections for M340 \u0026 M580 \r\narchitectures. For more details refer to the chapter \u201cHow to \r\nprotect M580 and M340 architectures with EAGLE40 using \r\nVPN\u201d: \r\nhttps://www.se.com/ww/en/download/document/EIO000000199\r\n9/ \r\n\u2022 Ensure the M580 CPU is running with the memory protection \r\nactivated by configuring the input bit to a physical input, for more \r\ndetails refer to the following guideline \u201cModicon Controllers \r\nPlatform Cyber Security Reference Manual\u201d, \u201cCPU Memory \r\nProtection section\u201d: \r\nhttps://www.schneider\u0002electric.com/en/download/document/EIO0000001999/\r\n\u2022 NOTE: The CPU memory protection cannot be \r\nconfigured with M580 Hot Standby CPUs. In such \r\ncases, use IPsec encrypted communication.\r\n",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          }
        },
        {
          "category": "mitigation",
          "details": "If customers choose not to apply the remediation then they are encouraged to immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Configure the Access Control List following the \r\nrecommendations of the user manuals: \u201cModicon M580, \r\nHardware, Reference Manual\u201d\r\nhttps://www.se.com/ww/en/download/document/EIO000000157\r\n8/\r\n\u2022 Setup a secure communication according to the following \r\nguideline \u201cModicon Controllers Platform Cyber Security \r\nReference Manual,\u201d in chapter \u201cSetup secured \r\ncommunications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO000000199\r\n9/\r\n\u2022 use a BMENOC module and follow the instructions to \r\nconfigure IPSEC feature as described in the guideline \r\n\u201cModicon M580 - BMENOC03.1 Ethernet \r\nCommunications Schneider Electric Security Notification \r\nModule, Installation and Configuration Guide\u201d in the \r\nchapter \u201cConfiguring IPSEC communications\u201d: \r\nhttps://www.se.com/ww/en/download/document/HRB626\r\n65/ \r\nOR\r\n\u2022 Use a BMENUA0100 module and follow the instructions to \r\nconfigure IPSEC feature as described in the chapter \r\n\u201cConfiguring the BMENUA0100 Cybersecurity Settings\u201d:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 \r\nfrom Belden to establish VPN connections for M340 \u0026 M580 \r\narchitectures. For more details refer to the chapter \u201cHow to \r\nprotect M580 and M340 architectures with EAGLE40 using \r\nVPN\u201d: \r\nhttps://www.se.com/ww/en/download/document/EIO000000199\r\n9/ \r\n\u2022 Ensure the M580 CPU is running with the memory protection \r\nactivated by configuring the input bit to a physical input, for more \r\ndetails refer to the following guideline \u201cModicon Controllers \r\nPlatform Cyber Security Reference Manual\u201d, \u201cCPU Memory \r\nProtection section\u201d: https://www.schneider\u0002electric.com/en/download/document/EIO0000001999/ . \u2022 NOTE: The CPU memory protection cannot be configured with M580 Hot Standby CPUs. In such cases, use IPsec encrypted communication. To further reduce the attack surface on Modicon M580 CPU Safety: \u2022 Ensure the CPU is running in Safety mode and maintenance input is configured to maintain this Safety mode during operation \u2013 refer to the document Modicon M580 - Safety System Planning Guide - in the chapter \u201cOperating Mode Transitions\u201d:https://www.se.com/ww/en/download/document/QGH60283",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          }
        },
        {
          "category": "vendor_fix",
          "details": "Firmware sv2.70 includes a fix for these vulnerabilities and is available for download here: https://www.se.com/ww/en/product-range/535-modiconmomentum/-software-and-firmware",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/535-modiconmomentum/-software-and-firmware"
        },
        {
          "category": "mitigation",
          "details": "Schneider Electric is establishing a remediation plan for all future \r\nversions of Modicon MC80 controllers that will include a fix for these\r\nvulnerabilities. We will update this document when the remediation is \r\navailable. Until then, customers should immediately apply the following \r\nmitigations to reduce the risk of exploit:\r\n\u2022 Configure the Access Control List following the \r\nrecommendations of the user manuals:\r\n\u2022 \u201cModicon MC80 Programmable Logic Controller (PLC) \r\nmanual\u201d in the chapter \u201cAccess Control List (ACL)\u201d: \r\nhttps://www.se.com/ww/en/download/document/EIO000\r\n0002071/ \r\n\u2022 Setup a secure communication according to the \r\nfollowing guideline \u201cModicon Controllers Platform Cyber \r\nSecurity Reference Manual,\u201d in chapter \u201cSetup secured \r\ncommunications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO000\r\n0001999",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          }
        },
        {
          "category": "mitigation",
          "details": "Schneider Electric\u2019s Modicon Premium \u0026 Quantum controllers have \r\nreached their end of life and are no longer commercially available. They \r\nhave been replaced by the Modicon M580 ePAC controller, our most \r\ncurrent product offer. \r\nCustomers should strongly consider migrating to the Modicon M580 \r\nePAC. Please contact your local Schneider Electric technical support for \r\nmore information. \r\nTo mitigate the risks users should immediately: \r\n\u2022 Configure the Access Control List following the \r\nrecommendations of the user manual \u201cPremium and Atrium \r\nusing EcoStruxure\u2122 Control Expert \u2013 Ethernet Network \r\nModules, User Manual\u201d in chapters \u201cConnection configuration \r\nparameters / TCP/IP Services Configuration Parameters / \r\nConnection Configuration Parameters\u201d:\r\nhttps://www.se.com/ww/en/download/document/35006192K010\r\n00",
          "product_ids": [
            "6",
            "7"
          ],
          "restart_required": {
            "category": "none"
          }
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 6.5,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "LOW",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "1",
            "2",
            "3",
            "4",
            "5",
            "6",
            "7"
          ]
        }
      ],
      "title": "CVE-2023-25620"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…