SEVD-2021-222-02

Vulnerability from csaf_se - Published: 2021-08-01 07:25 - Updated: 2022-07-12 18:30
Summary
AT&T Labs Compressor (XMilI) and Decompressor (XDemill) used by EcoStruxureTM Control Expert, EcoStruxureTM Process Expert and SCADAPack RemoteConnect™ for x70

Notes

General Security Recommendations
We strongly recommend the following industry cybersecurity best practices. https://www.se.com/us/en/download/document/7EN52-0390/ * Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. * Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. * Place all controllers in locked cabinets and never leave them in the “Program” mode. * Never connect programming software to any network other than the network intended for that device. * Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. * Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. * Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. * When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment. We provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries. We are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values. www.se.com
Overview
Schneider Electric is aware of multiple vulnerabilities on AT&T Labs’ Compressor (XMilI) and decompressor (XDemill) third party components used by EcoStruxure Control Expert, EcoStruxure Process Expert and SCADAPack RemoteConnect™ for x70. Failure to apply the mitigations provided below may lead to the execution of a malicious file, which could result in code execution with elevated privileges on the engineering workstation. For an attack to be successful, an attacker requires access to the engineering workstation and then needs to trick a valid user to run a script or load a malicious project file. July 2022 Update: A release is available for SCADAPack RemoteConnect™ R2.7.3 that addresses workstation vulnerabilities related to the issues listed below.

{
  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Public",
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
        "title": "General Security Recommendations"
      },
      {
        "category": "general",
        "text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
        "title": "For More Information"
      },
      {
        "category": "legal_disclaimer",
        "text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND.  SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
        "title": "LEGAL DISCLAIMER"
      },
      {
        "category": "general",
        "text": "At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.\n\nWe provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.\n\nWe are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.\n\nwww.se.com ",
        "title": "About Schneider Electric"
      },
      {
        "category": "summary",
        "text": "Schneider Electric is aware of multiple vulnerabilities on AT\u0026T Labs\u2019 Compressor (XMilI) and decompressor (XDemill) third party components used by EcoStruxure Control Expert, EcoStruxure Process Expert and SCADAPack RemoteConnect\u2122 for x70.\r\nFailure to apply the mitigations provided below may lead to the execution of a malicious file, which could result in code execution with elevated privileges on the engineering workstation. For an attack to be successful, an attacker requires access to the engineering workstation and then needs to trick a valid user to run a script or load a malicious project file.\r\nJuly 2022 Update: A release is available for SCADAPack RemoteConnect\u2122 R2.7.3 that addresses workstation vulnerabilities related to the issues listed below.",
        "title": "Overview"
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "cybersecurity@se.com",
      "name": "Schneider Electric CPCERT",
      "namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
    },
    "references": [
      {
        "category": "self",
        "summary": "AT\u0026T Labs Compressor (XMilI) and Decompressor (XDemill) used by EcoStruxureTM Control Expert, EcoStruxureTM Process Expert and SCADAPack RemoteConnect\u2122 for x70 - SEVD-2021-222-02 CSAF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-222-02\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2021-222-02.json"
      },
      {
        "category": "self",
        "summary": "Recommended Cybersecurity Best Practices",
        "url": "https://www.se.com/us/en/download/document/7EN52-0390/"
      }
    ],
    "title": "AT\u0026T Labs Compressor (XMilI) and Decompressor (XDemill) used by EcoStruxureTM Control Expert, EcoStruxureTM Process Expert and SCADAPack RemoteConnect\u2122 for x70",
    "tracking": {
      "current_release_date": "2022-07-12T18:30:00.000Z",
      "generator": {
        "date": "2022-07-06T12:52:13.537Z",
        "engine": {
          "name": "Schneider Electric CSAF Generator",
          "version": "1.1"
        }
      },
      "id": "SEVD-2021-222-02",
      "initial_release_date": "2021-08-01T07:25:51.000Z",
      "revision_history": [
        {
          "date": "2021-08-01T07:25:51.000Z",
          "number": "1.0.0",
          "summary": "Original Release"
        },
        {
          "date": "2022-03-08T07:25:51.000Z",
          "number": "2.0.0",
          "summary": "Remediation update"
        },
        {
          "date": "2022-03-09T07:25:51.000Z",
          "number": "2.1.0",
          "summary": "Recently released versions of EcoStruxure\u2122 Control Expert and EcoStruxure\u2122 Process Expert previously communicated to address these vulnerabilities were found to not fully address the issues as stated in a previous update of this notification. Customers are encouraged to follow the mitigations provided below."
        },
        {
          "date": "2022-04-12T07:25:51.000Z",
          "number": "3.0.0",
          "summary": "Added remediation for EcoStruxure\u2122 Control Expert V15.1 HF001 and EcoStruxure\u2122 Process Expert V2021. Schneider Electric is establishing a remediation plan for future versions of SCADAPack RemoteConnect for x70. Added CVE-2022-26507."
        },
        {
          "date": "2022-07-12T18:30:00.000Z",
          "number": "4.0.0",
          "summary": "Added remediation for SCADAPack RemoteConnect\u2122 for x70."
        }
      ],
      "status": "final",
      "version": "4.0.0"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c15.1 HF001",
                "product": {
                  "name": "Schneider Electric EcoStruxure\u2122 Control Expert \u003c15.1 HF001",
                  "product_id": "1"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure\u2122 Control Expert"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "15.1 HF001",
                "product": {
                  "name": "Schneider Electric EcoStruxure\u2122 Control Expert 15.1 HF001",
                  "product_id": "2"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure\u2122 Control Expert"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c2021",
                "product": {
                  "name": "Schneider Electric EcoStruxure\u2122 Process Expert \u003c2021",
                  "product_id": "3"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure\u2122 Process Expert"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "2021",
                "product": {
                  "name": "Schneider Electric EcoStruxure\u2122 Process Expert 2021",
                  "product_id": "4"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure\u2122 Process Expert"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003cR2.7.3",
                "product": {
                  "name": "Schneider Electric SCADAPack RemoteConnect\u2122 for x70 \u003cR2.7.3",
                  "product_id": "5"
                }
              }
            ],
            "category": "product_name",
            "name": "SCADAPack RemoteConnect\u2122 for x70"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "R2.7.3",
                "product": {
                  "name": "Schneider Electric SCADAPack RemoteConnect\u2122 for x70 R2.7.3",
                  "product_id": "6"
                }
              }
            ],
            "category": "product_name",
            "name": "SCADAPack RemoteConnect\u2122 for x70"
          }
        ],
        "category": "vendor",
        "name": "Schneider Electric"
      }
    ]
  },
  "vulnerabilities": [
    {
      "acknowledgments": [
        {
          "names": [
            "Carl Hurd"
          ],
          "organization": "Cisco Talos"
        }
      ],
      "cve": "CVE-2021-21810",
      "notes": [
        {
          "category": "description",
          "text": "The vulnerabilities reported on XDemill and XMilI are triggered through the execution of a malicious script on the engineering workstation, or when loading a specially crafted project file into the engineering tool. The successful exploitation of these vulnerabilities may lead to code execution with elevated privileges on the engineering workstation. "
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4",
          "6"
        ],
        "known_affected": [
          "1",
          "3",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "V15.1 HF001 of EcoStruxure\u2122 Control Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Control Expert or Unity Pro\r\n\u2022 Customers using Unity Pro should strongly consider migrating to EcoStruxure Control Expert.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/"
        },
        {
          "category": "vendor_fix",
          "details": "V2021 of EcoStruxure\u2122 Process Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release\r\nIt is recommended to first read the ReadMe first document before proceeding with the software installation.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Process Expert",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release"
        },
        {
          "category": "vendor_fix",
          "details": "Version R2.7.3 of SCADAPack RemoteConnect\u2122 includes a fix for these vulnerabilities and is available for download here at the Schneider Electric Exchange:\r\nhttps://shop.exchange.se.com/en-US/apps/58663\r\nNote: Users no longer need to update the RemoteConnect\u2122 application when there is a Control Expert update.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022Store the project files in a secure storage and restrict theaccess to only trusted users\r\n\u2022When exchanging files over the network, use securecommunication channels\r\n\u2022Only open project files received from a trusted source\r\n\u2022Compute a hash of the project files and regularly check theconsistency of this hash to verify the integrity before usage\r\n\u2022Harden the workstation running SCADAPackRemoteConnect\u2122 for x70",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://shop.exchange.se.com/en-US/apps/58663"
        }
      ],
      "title": "CVE-2021-21810"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Carl Hurd"
          ],
          "organization": "Cisco Talos"
        }
      ],
      "cve": "CVE-2021-21825",
      "notes": [
        {
          "category": "description",
          "text": "The vulnerabilities reported on XDemill and XMilI are triggered through the execution of a malicious script on the engineering workstation, or when loading a specially crafted project file into the engineering tool. The successful exploitation of these vulnerabilities may lead to code execution with elevated privileges on the engineering workstation. "
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4",
          "6"
        ],
        "known_affected": [
          "1",
          "3",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "V15.1 HF001 of EcoStruxure\u2122 Control Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Control Expert or Unity Pro\r\n\u2022 Customers using Unity Pro should strongly consider migrating to EcoStruxure Control Expert.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/"
        },
        {
          "category": "vendor_fix",
          "details": "V2021 of EcoStruxure\u2122 Process Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release\r\nIt is recommended to first read the ReadMe first document before proceeding with the software installation.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Process Expert",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release"
        },
        {
          "category": "vendor_fix",
          "details": "Version R2.7.3 of SCADAPack RemoteConnect\u2122 includes a fix for these vulnerabilities and is available for download here at the Schneider Electric Exchange:\r\nhttps://shop.exchange.se.com/en-US/apps/58663\r\nNote: Users no longer need to update the RemoteConnect\u2122 application when there is a Control Expert update.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022Store the project files in a secure storage and restrict theaccess to only trusted users\r\n\u2022When exchanging files over the network, use securecommunication channels\r\n\u2022Only open project files received from a trusted source\r\n\u2022Compute a hash of the project files and regularly check theconsistency of this hash to verify the integrity before usage\r\n\u2022Harden the workstation running SCADAPackRemoteConnect\u2122 for x70",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://shop.exchange.se.com/en-US/apps/58663"
        }
      ],
      "title": "CVE-2021-21825"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Carl Hurd"
          ],
          "organization": "Cisco Talos"
        }
      ],
      "cve": "CVE-2021-21811",
      "notes": [
        {
          "category": "description",
          "text": "The vulnerabilities reported on XDemill and XMilI are triggered through the execution of a malicious script on the engineering workstation, or when loading a specially crafted project file into the engineering tool. The successful exploitation of these vulnerabilities may lead to code execution with elevated privileges on the engineering workstation. "
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4",
          "6"
        ],
        "known_affected": [
          "1",
          "3",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "V15.1 HF001 of EcoStruxure\u2122 Control Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Control Expert or Unity Pro\r\n\u2022 Customers using Unity Pro should strongly consider migrating to EcoStruxure Control Expert.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/"
        },
        {
          "category": "vendor_fix",
          "details": "V2021 of EcoStruxure\u2122 Process Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release\r\nIt is recommended to first read the ReadMe first document before proceeding with the software installation.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Process Expert",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release"
        },
        {
          "category": "vendor_fix",
          "details": "Version R2.7.3 of SCADAPack RemoteConnect\u2122 includes a fix for these vulnerabilities and is available for download here at the Schneider Electric Exchange:\r\nhttps://shop.exchange.se.com/en-US/apps/58663\r\nNote: Users no longer need to update the RemoteConnect\u2122 application when there is a Control Expert update.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022Store the project files in a secure storage and restrict theaccess to only trusted users\r\n\u2022When exchanging files over the network, use securecommunication channels\r\n\u2022Only open project files received from a trusted source\r\n\u2022Compute a hash of the project files and regularly check theconsistency of this hash to verify the integrity before usage\r\n\u2022Harden the workstation running SCADAPackRemoteConnect\u2122 for x70",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://shop.exchange.se.com/en-US/apps/58663"
        }
      ],
      "title": "CVE-2021-21811"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Carl Hurd"
          ],
          "organization": "Cisco Talos"
        }
      ],
      "cve": "CVE-2021-21826",
      "notes": [
        {
          "category": "description",
          "text": "The vulnerabilities reported on XDemill and XMilI are triggered through the execution of a malicious script on the engineering workstation, or when loading a specially crafted project file into the engineering tool. The successful exploitation of these vulnerabilities may lead to code execution with elevated privileges on the engineering workstation. "
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4",
          "6"
        ],
        "known_affected": [
          "1",
          "3",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "V15.1 HF001 of EcoStruxure\u2122 Control Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Control Expert or Unity Pro\r\n\u2022 Customers using Unity Pro should strongly consider migrating to EcoStruxure Control Expert.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/"
        },
        {
          "category": "vendor_fix",
          "details": "V2021 of EcoStruxure\u2122 Process Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release\r\nIt is recommended to first read the ReadMe first document before proceeding with the software installation.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Process Expert",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release"
        },
        {
          "category": "vendor_fix",
          "details": "Version R2.7.3 of SCADAPack RemoteConnect\u2122 includes a fix for these vulnerabilities and is available for download here at the Schneider Electric Exchange:\r\nhttps://shop.exchange.se.com/en-US/apps/58663\r\nNote: Users no longer need to update the RemoteConnect\u2122 application when there is a Control Expert update.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022Store the project files in a secure storage and restrict theaccess to only trusted users\r\n\u2022When exchanging files over the network, use securecommunication channels\r\n\u2022Only open project files received from a trusted source\r\n\u2022Compute a hash of the project files and regularly check theconsistency of this hash to verify the integrity before usage\r\n\u2022Harden the workstation running SCADAPackRemoteConnect\u2122 for x70",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://shop.exchange.se.com/en-US/apps/58663"
        }
      ],
      "title": "CVE-2021-21826"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Carl Hurd"
          ],
          "organization": "Cisco Talos"
        }
      ],
      "cve": "CVE-2021-21812",
      "notes": [
        {
          "category": "description",
          "text": "The vulnerabilities reported on XDemill and XMilI are triggered through the execution of a malicious script on the engineering workstation, or when loading a specially crafted project file into the engineering tool. The successful exploitation of these vulnerabilities may lead to code execution with elevated privileges on the engineering workstation. "
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4",
          "6"
        ],
        "known_affected": [
          "1",
          "3",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "V15.1 HF001 of EcoStruxure\u2122 Control Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Control Expert or Unity Pro\r\n\u2022 Customers using Unity Pro should strongly consider migrating to EcoStruxure Control Expert.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/"
        },
        {
          "category": "vendor_fix",
          "details": "V2021 of EcoStruxure\u2122 Process Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release\r\nIt is recommended to first read the ReadMe first document before proceeding with the software installation.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Process Expert",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release"
        },
        {
          "category": "vendor_fix",
          "details": "Version R2.7.3 of SCADAPack RemoteConnect\u2122 includes a fix for these vulnerabilities and is available for download here at the Schneider Electric Exchange:\r\nhttps://shop.exchange.se.com/en-US/apps/58663\r\nNote: Users no longer need to update the RemoteConnect\u2122 application when there is a Control Expert update.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022Store the project files in a secure storage and restrict theaccess to only trusted users\r\n\u2022When exchanging files over the network, use securecommunication channels\r\n\u2022Only open project files received from a trusted source\r\n\u2022Compute a hash of the project files and regularly check theconsistency of this hash to verify the integrity before usage\r\n\u2022Harden the workstation running SCADAPackRemoteConnect\u2122 for x70",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://shop.exchange.se.com/en-US/apps/58663"
        }
      ],
      "title": "CVE-2021-21812"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Carl Hurd"
          ],
          "organization": "Cisco Talos"
        }
      ],
      "cve": "CVE-2021-21827",
      "notes": [
        {
          "category": "description",
          "text": "The vulnerabilities reported on XDemill and XMilI are triggered through the execution of a malicious script on the engineering workstation, or when loading a specially crafted project file into the engineering tool. The successful exploitation of these vulnerabilities may lead to code execution with elevated privileges on the engineering workstation. "
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4",
          "6"
        ],
        "known_affected": [
          "1",
          "3",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "V15.1 HF001 of EcoStruxure\u2122 Control Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Control Expert or Unity Pro\r\n\u2022 Customers using Unity Pro should strongly consider migrating to EcoStruxure Control Expert.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/"
        },
        {
          "category": "vendor_fix",
          "details": "V2021 of EcoStruxure\u2122 Process Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release\r\nIt is recommended to first read the ReadMe first document before proceeding with the software installation.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Process Expert",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release"
        },
        {
          "category": "vendor_fix",
          "details": "Version R2.7.3 of SCADAPack RemoteConnect\u2122 includes a fix for these vulnerabilities and is available for download here at the Schneider Electric Exchange:\r\nhttps://shop.exchange.se.com/en-US/apps/58663\r\nNote: Users no longer need to update the RemoteConnect\u2122 application when there is a Control Expert update.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022Store the project files in a secure storage and restrict theaccess to only trusted users\r\n\u2022When exchanging files over the network, use securecommunication channels\r\n\u2022Only open project files received from a trusted source\r\n\u2022Compute a hash of the project files and regularly check theconsistency of this hash to verify the integrity before usage\r\n\u2022Harden the workstation running SCADAPackRemoteConnect\u2122 for x70",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://shop.exchange.se.com/en-US/apps/58663"
        }
      ],
      "title": "CVE-2021-21827"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Carl Hurd"
          ],
          "organization": "Cisco Talos"
        }
      ],
      "cve": "CVE-2021-21813",
      "notes": [
        {
          "category": "description",
          "text": "The vulnerabilities reported on XDemill and XMilI are triggered through the execution of a malicious script on the engineering workstation, or when loading a specially crafted project file into the engineering tool. The successful exploitation of these vulnerabilities may lead to code execution with elevated privileges on the engineering workstation. "
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4",
          "6"
        ],
        "known_affected": [
          "1",
          "3",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "V15.1 HF001 of EcoStruxure\u2122 Control Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Control Expert or Unity Pro\r\n\u2022 Customers using Unity Pro should strongly consider migrating to EcoStruxure Control Expert.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/"
        },
        {
          "category": "vendor_fix",
          "details": "V2021 of EcoStruxure\u2122 Process Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release\r\nIt is recommended to first read the ReadMe first document before proceeding with the software installation.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Process Expert",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release"
        },
        {
          "category": "vendor_fix",
          "details": "Version R2.7.3 of SCADAPack RemoteConnect\u2122 includes a fix for these vulnerabilities and is available for download here at the Schneider Electric Exchange:\r\nhttps://shop.exchange.se.com/en-US/apps/58663\r\nNote: Users no longer need to update the RemoteConnect\u2122 application when there is a Control Expert update.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022Store the project files in a secure storage and restrict theaccess to only trusted users\r\n\u2022When exchanging files over the network, use securecommunication channels\r\n\u2022Only open project files received from a trusted source\r\n\u2022Compute a hash of the project files and regularly check theconsistency of this hash to verify the integrity before usage\r\n\u2022Harden the workstation running SCADAPackRemoteConnect\u2122 for x70",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://shop.exchange.se.com/en-US/apps/58663"
        }
      ],
      "title": "CVE-2021-21813"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Carl Hurd"
          ],
          "organization": "Cisco Talos"
        }
      ],
      "cve": "CVE-2021-21828",
      "notes": [
        {
          "category": "description",
          "text": "The vulnerabilities reported on XDemill and XMilI are triggered through the execution of a malicious script on the engineering workstation, or when loading a specially crafted project file into the engineering tool. The successful exploitation of these vulnerabilities may lead to code execution with elevated privileges on the engineering workstation. "
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4",
          "6"
        ],
        "known_affected": [
          "1",
          "3",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "V15.1 HF001 of EcoStruxure\u2122 Control Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Control Expert or Unity Pro\r\n\u2022 Customers using Unity Pro should strongly consider migrating to EcoStruxure Control Expert.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/"
        },
        {
          "category": "vendor_fix",
          "details": "V2021 of EcoStruxure\u2122 Process Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release\r\nIt is recommended to first read the ReadMe first document before proceeding with the software installation.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Process Expert",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release"
        },
        {
          "category": "vendor_fix",
          "details": "Version R2.7.3 of SCADAPack RemoteConnect\u2122 includes a fix for these vulnerabilities and is available for download here at the Schneider Electric Exchange:\r\nhttps://shop.exchange.se.com/en-US/apps/58663\r\nNote: Users no longer need to update the RemoteConnect\u2122 application when there is a Control Expert update.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022Store the project files in a secure storage and restrict theaccess to only trusted users\r\n\u2022When exchanging files over the network, use securecommunication channels\r\n\u2022Only open project files received from a trusted source\r\n\u2022Compute a hash of the project files and regularly check theconsistency of this hash to verify the integrity before usage\r\n\u2022Harden the workstation running SCADAPackRemoteConnect\u2122 for x70",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://shop.exchange.se.com/en-US/apps/58663"
        }
      ],
      "title": "CVE-2021-21828"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Carl Hurd"
          ],
          "organization": "Cisco Talos"
        }
      ],
      "cve": "CVE-2021-21814",
      "notes": [
        {
          "category": "description",
          "text": "The vulnerabilities reported on XDemill and XMilI are triggered through the execution of a malicious script on the engineering workstation, or when loading a specially crafted project file into the engineering tool. The successful exploitation of these vulnerabilities may lead to code execution with elevated privileges on the engineering workstation. "
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4",
          "6"
        ],
        "known_affected": [
          "1",
          "3",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "V15.1 HF001 of EcoStruxure\u2122 Control Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Control Expert or Unity Pro\r\n\u2022 Customers using Unity Pro should strongly consider migrating to EcoStruxure Control Expert.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/"
        },
        {
          "category": "vendor_fix",
          "details": "V2021 of EcoStruxure\u2122 Process Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release\r\nIt is recommended to first read the ReadMe first document before proceeding with the software installation.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Process Expert",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release"
        },
        {
          "category": "vendor_fix",
          "details": "Version R2.7.3 of SCADAPack RemoteConnect\u2122 includes a fix for these vulnerabilities and is available for download here at the Schneider Electric Exchange:\r\nhttps://shop.exchange.se.com/en-US/apps/58663\r\nNote: Users no longer need to update the RemoteConnect\u2122 application when there is a Control Expert update.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022Store the project files in a secure storage and restrict theaccess to only trusted users\r\n\u2022When exchanging files over the network, use securecommunication channels\r\n\u2022Only open project files received from a trusted source\r\n\u2022Compute a hash of the project files and regularly check theconsistency of this hash to verify the integrity before usage\r\n\u2022Harden the workstation running SCADAPackRemoteConnect\u2122 for x70",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://shop.exchange.se.com/en-US/apps/58663"
        }
      ],
      "title": "CVE-2021-21814"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Carl Hurd"
          ],
          "organization": "Cisco Talos"
        }
      ],
      "cve": "CVE-2021-21829",
      "notes": [
        {
          "category": "description",
          "text": "The vulnerabilities reported on XDemill and XMilI are triggered through the execution of a malicious script on the engineering workstation, or when loading a specially crafted project file into the engineering tool. The successful exploitation of these vulnerabilities may lead to code execution with elevated privileges on the engineering workstation. "
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4",
          "6"
        ],
        "known_affected": [
          "1",
          "3",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "V15.1 HF001 of EcoStruxure\u2122 Control Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Control Expert or Unity Pro\r\n\u2022 Customers using Unity Pro should strongly consider migrating to EcoStruxure Control Expert.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/"
        },
        {
          "category": "vendor_fix",
          "details": "V2021 of EcoStruxure\u2122 Process Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release\r\nIt is recommended to first read the ReadMe first document before proceeding with the software installation.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Process Expert",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release"
        },
        {
          "category": "vendor_fix",
          "details": "Version R2.7.3 of SCADAPack RemoteConnect\u2122 includes a fix for these vulnerabilities and is available for download here at the Schneider Electric Exchange:\r\nhttps://shop.exchange.se.com/en-US/apps/58663\r\nNote: Users no longer need to update the RemoteConnect\u2122 application when there is a Control Expert update.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022Store the project files in a secure storage and restrict theaccess to only trusted users\r\n\u2022When exchanging files over the network, use securecommunication channels\r\n\u2022Only open project files received from a trusted source\r\n\u2022Compute a hash of the project files and regularly check theconsistency of this hash to verify the integrity before usage\r\n\u2022Harden the workstation running SCADAPackRemoteConnect\u2122 for x70",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://shop.exchange.se.com/en-US/apps/58663"
        }
      ],
      "title": "CVE-2021-21829"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Carl Hurd"
          ],
          "organization": "Cisco Talos"
        }
      ],
      "cve": "CVE-2021-21815",
      "notes": [
        {
          "category": "description",
          "text": "The vulnerabilities reported on XDemill and XMilI are triggered through the execution of a malicious script on the engineering workstation, or when loading a specially crafted project file into the engineering tool. The successful exploitation of these vulnerabilities may lead to code execution with elevated privileges on the engineering workstation. "
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4",
          "6"
        ],
        "known_affected": [
          "1",
          "3",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "V15.1 HF001 of EcoStruxure\u2122 Control Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Control Expert or Unity Pro\r\n\u2022 Customers using Unity Pro should strongly consider migrating to EcoStruxure Control Expert.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/"
        },
        {
          "category": "vendor_fix",
          "details": "V2021 of EcoStruxure\u2122 Process Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release\r\nIt is recommended to first read the ReadMe first document before proceeding with the software installation.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Process Expert",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release"
        },
        {
          "category": "vendor_fix",
          "details": "Version R2.7.3 of SCADAPack RemoteConnect\u2122 includes a fix for these vulnerabilities and is available for download here at the Schneider Electric Exchange:\r\nhttps://shop.exchange.se.com/en-US/apps/58663\r\nNote: Users no longer need to update the RemoteConnect\u2122 application when there is a Control Expert update.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022Store the project files in a secure storage and restrict theaccess to only trusted users\r\n\u2022When exchanging files over the network, use securecommunication channels\r\n\u2022Only open project files received from a trusted source\r\n\u2022Compute a hash of the project files and regularly check theconsistency of this hash to verify the integrity before usage\r\n\u2022Harden the workstation running SCADAPackRemoteConnect\u2122 for x70",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://shop.exchange.se.com/en-US/apps/58663"
        }
      ],
      "title": "CVE-2021-21815"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Carl Hurd"
          ],
          "organization": "Cisco Talos"
        }
      ],
      "cve": "CVE-2021-21830",
      "notes": [
        {
          "category": "description",
          "text": "The vulnerabilities reported on XDemill and XMilI are triggered through the execution of a malicious script on the engineering workstation, or when loading a specially crafted project file into the engineering tool. The successful exploitation of these vulnerabilities may lead to code execution with elevated privileges on the engineering workstation. "
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4",
          "6"
        ],
        "known_affected": [
          "1",
          "3",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "V15.1 HF001 of EcoStruxure\u2122 Control Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Control Expert or Unity Pro\r\n\u2022 Customers using Unity Pro should strongly consider migrating to EcoStruxure Control Expert.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/"
        },
        {
          "category": "vendor_fix",
          "details": "V2021 of EcoStruxure\u2122 Process Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release\r\nIt is recommended to first read the ReadMe first document before proceeding with the software installation.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Process Expert",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release"
        },
        {
          "category": "vendor_fix",
          "details": "Version R2.7.3 of SCADAPack RemoteConnect\u2122 includes a fix for these vulnerabilities and is available for download here at the Schneider Electric Exchange:\r\nhttps://shop.exchange.se.com/en-US/apps/58663\r\nNote: Users no longer need to update the RemoteConnect\u2122 application when there is a Control Expert update.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022Store the project files in a secure storage and restrict theaccess to only trusted users\r\n\u2022When exchanging files over the network, use securecommunication channels\r\n\u2022Only open project files received from a trusted source\r\n\u2022Compute a hash of the project files and regularly check theconsistency of this hash to verify the integrity before usage\r\n\u2022Harden the workstation running SCADAPackRemoteConnect\u2122 for x70",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://shop.exchange.se.com/en-US/apps/58663"
        }
      ],
      "title": "CVE-2021-21830"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Uri Katz"
          ],
          "organization": "Claroty Research"
        }
      ],
      "cve": "CVE-2022-26507",
      "notes": [
        {
          "category": "description",
          "text": "The vulnerabilities reported on XDemill and XMilI are triggered through the execution of a malicious script on the engineering workstation, or when loading a specially crafted project file into the engineering tool. The successful exploitation of these vulnerabilities may lead to code execution with elevated privileges on the engineering workstation. "
        }
      ],
      "product_status": {
        "fixed": [
          "2",
          "4",
          "6"
        ],
        "known_affected": [
          "1",
          "3",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "V15.1 HF001 of EcoStruxure\u2122 Control Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Control Expert or Unity Pro\r\n\u2022 Customers using Unity Pro should strongly consider migrating to EcoStruxure Control Expert.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/ControlExpert_V151_HF001/"
        },
        {
          "category": "vendor_fix",
          "details": "V2021 of EcoStruxure\u2122 Process Expert includes a fix for these vulnerabilities and is available for download here:\r\nhttps://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release\r\nIt is recommended to first read the ReadMe first document before proceeding with the software installation.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Store the project files in a secure storage and restrict the access to only trusted users\r\n\u2022 When exchanging files over the network, use secure communication channels\r\n\u2022 Only open project files received from a trusted source\r\n\u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage\r\n\u2022 Harden the workstation running EcoStruxure Process Expert",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/myschneider/documentsDownloadCenterDetail/in/en/EPE2021Release"
        },
        {
          "category": "vendor_fix",
          "details": "Version R2.7.3 of SCADAPack RemoteConnect\u2122 includes a fix for these vulnerabilities and is available for download here at the Schneider Electric Exchange:\r\nhttps://shop.exchange.se.com/en-US/apps/58663\r\nNote: Users no longer need to update the RemoteConnect\u2122 application when there is a Control Expert update.\r\nIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022Store the project files in a secure storage and restrict theaccess to only trusted users\r\n\u2022When exchanging files over the network, use securecommunication channels\r\n\u2022Only open project files received from a trusted source\r\n\u2022Compute a hash of the project files and regularly check theconsistency of this hash to verify the integrity before usage\r\n\u2022Harden the workstation running SCADAPackRemoteConnect\u2122 for x70",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://shop.exchange.se.com/en-US/apps/58663"
        }
      ],
      "title": "CVE-2022-26507"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…