SEVD-2020-161-05

Vulnerability from csaf_se - Published: 2020-06-09 00:00 - Updated: 2021-05-13 00:00
Summary
Easergy Builder

Notes

General Security Recommendations
We strongly recommend the following industry cybersecurity best practices. https://www.se.com/us/en/download/document/7EN52-0390/ * Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. * Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. * Place all controllers in locked cabinets and never leave them in the “Program” mode. * Never connect programming software to any network other than the network intended for that device. * Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. * Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. * Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. * When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment. We provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries. We are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values. www.se.com
Overview
Researchers from Rostelecom-Solar have made Schneider Electric aware of multiple vulnerabilities affecting the company’s Easergy Builder configuration tool. Schneider Electric has worked closely with Ilya Karpov and Evgeniy Druzhinin of Rostelecom-Solar to remediate the vulnerabilities and appreciates their collaboration and commitment to transparency. The vulnerabilities have been remediated via a free software update, which is available immediately by contacting Schneider Electric’s Customer Care Center. Access to the customer’s network is required for the majority of the disclosed vulnerabilities to be exploited. Therefore, if the customer’s network is well protected and monitored for intrusion, and care is taken to obtain software updates from a trusted source, the general risk of exploitation can be substantially minimized. Schneider Electric encourages customers to upgrade to the new software as soon as possible. The company further encourages customers to ensure any firmware files used to update the device are acquired from trusted sources; to operate the products on properly segmented control networks; to adequately secure any workstation that has been configured to have access to the product; and to follow the remediation and general security recommendations below.

{
  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Public",
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
        "title": "General Security Recommendations"
      },
      {
        "category": "general",
        "text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
        "title": "For More Information"
      },
      {
        "category": "legal_disclaimer",
        "text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND.  SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
        "title": "LEGAL DISCLAIMER"
      },
      {
        "category": "general",
        "text": "At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.\n\nWe provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.\n\nWe are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.\n\nwww.se.com ",
        "title": "About Schneider Electric"
      },
      {
        "category": "summary",
        "text": "Researchers from Rostelecom-Solar have made Schneider Electric aware of multiple \r\nvulnerabilities affecting the company\u2019s Easergy Builder configuration tool. Schneider Electric \r\nhas worked closely with Ilya Karpov and Evgeniy Druzhinin of Rostelecom-Solar to remediate \r\nthe vulnerabilities and appreciates their collaboration and commitment to transparency. The \r\nvulnerabilities have been remediated via a free software update, which is available immediately \r\nby contacting Schneider Electric\u2019s Customer Care Center. \r\nAccess to the customer\u2019s network is required for the majority of the disclosed vulnerabilities to \r\nbe exploited. Therefore, if the customer\u2019s network is well protected and monitored for intrusion, \r\nand care is taken to obtain software updates from a trusted source, the general risk of \r\nexploitation can be substantially minimized.\r\nSchneider Electric encourages customers to upgrade to the new software as soon as possible. \r\nThe company further encourages customers to ensure any firmware files used to update the \r\ndevice are acquired from trusted sources; to operate the products on properly segmented \r\ncontrol networks; to adequately secure any workstation that has been configured to have \r\naccess to the product; and to follow the remediation and general security recommendations \r\nbelow.",
        "title": "Overview"
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "cpcert@se.com",
      "name": "Schneider Electric CPCERT",
      "namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
    },
    "references": [
      {
        "category": "self",
        "summary": "Easergy Builder - SEVD-2020-161-05 PDF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2020-161-05\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2020-161-05_Easergy_Builder_Security_Notification_V1.1.pdf"
      },
      {
        "category": "self",
        "summary": "Easergy Builder - SEVD-2020-161-05 CSAF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2020-161-05\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2020-161-05.json"
      },
      {
        "category": "external",
        "summary": "Recommended Cybersecurity Best Practices",
        "url": "https://www.se.com/us/en/download/document/7EN52-0390/"
      }
    ],
    "title": "Easergy Builder",
    "tracking": {
      "current_release_date": "2021-05-13T00:00:00.000Z",
      "generator": {
        "date": "2021-05-13T00:00:00.000Z",
        "engine": {
          "name": "Schneider Electric CSAF Generator",
          "version": "1.2"
        }
      },
      "id": "SEVD-2020-161-05",
      "initial_release_date": "2020-06-09T00:00:00.000Z",
      "revision_history": [
        {
          "date": "2020-06-09T00:00:00.000Z",
          "number": "1.0.0",
          "summary": "Original Release"
        },
        {
          "date": "2021-05-13T00:00:00.000Z",
          "number": "1.1.0",
          "summary": "Updated CWE for CVE-2020-7515 and \r\nCVE-2020-7516"
        }
      ],
      "status": "final",
      "version": "1.1.0"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=1.4.7.2",
                "product": {
                  "name": "Schneider Electric Easergy Builder version 1.4.7.2 and prior",
                  "product_id": "1"
                }
              }
            ],
            "category": "product_name",
            "name": "Easergy Builder"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "1.6.3.0",
                "product": {
                  "name": "Schneider Electric Easergy Builder version 1.6.3.0",
                  "product_id": "2"
                }
              }
            ],
            "category": "product_name",
            "name": "Easergy Builder"
          }
        ],
        "category": "vendor",
        "name": "Schneider Electric"
      }
    ]
  },
  "vulnerabilities": [
    {
      "acknowledgments": [
        {
          "names": [
            "Evgeniy Druzhinin",
            "Ilya Karpov"
          ],
          "organization": "Rostelecom-Solar"
        }
      ],
      "cve": "CVE-2020-7514",
      "cwe": {
        "id": "CWE-327",
        "name": "Use of a Broken or Risky Cryptographic Algorithm"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-327: Use of a Broken or Risky Cryptographic Algorithm vulnerability exists which could \r\nallow an attacker access to the authorization credentials for a device and gain full access.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "2"
        ],
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "This vulnerability is fixed in Easergy Builder version 1.6.3.0 and is available from your Schneider \r\nElectric Customer Care Center.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/work/support/contacts.jsp"
        },
        {
          "category": "mitigation",
          "details": "Additionally, Schneider Electric recommends customers apply the following mitigations to further \r\nreduce risk:\r\n\u2022 Use a separate secure local network and use secure computer access controls\r\n",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          }
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "LOCAL",
            "availabilityImpact": "HIGH",
            "baseScore": 8.4,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 8.4,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 8.4,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2020-7514"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Evgeniy Druzhinin",
            "Ilya Karpov"
          ],
          "organization": "Rostelecom-Solar"
        }
      ],
      "cve": "CVE-2020-7515",
      "cwe": {
        "id": "CWE-798",
        "name": "Use of Hard-coded Credentials"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-798: Use of Hard-coded Credentials vulnerability exists which could allow an attacker to \r\ndecrypt a password.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "2"
        ],
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "This vulnerability is fixed in Easergy Builder version 1.6.3.0 and is available from your Schneider \r\nElectric Customer Care Center.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/work/support/contacts.jsp"
        },
        {
          "category": "mitigation",
          "details": "Additionally, Schneider Electric recommends customers apply the following mitigations to further \r\nreduce risk:\r\n\u2022 Use a separate secure local network and use secure computer access controls\r\n",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          }
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "LOCAL",
            "availabilityImpact": "HIGH",
            "baseScore": 8.4,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 8.4,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 8.4,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2020-7515"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Evgeniy Druzhinin",
            "Ilya Karpov"
          ],
          "organization": "Rostelecom-Solar"
        }
      ],
      "cve": "CVE-2020-7516",
      "cwe": {
        "id": "CWE-312",
        "name": "Cleartext Storage of Sensitive Information"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-312: Cleartext Storage of Sensitive Information vulnerability exists which could allow an \r\nattacker access to login credentials.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "2"
        ],
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "This vulnerability is fixed in Easergy Builder version 1.6.3.0 and is available from your Schneider \r\nElectric Customer Care Center.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/work/support/contacts.jsp"
        },
        {
          "category": "mitigation",
          "details": "Additionally, Schneider Electric recommends customers apply the following mitigations to further \r\nreduce risk:\r\n\u2022 Use a separate secure local network and use secure computer access controls\r\n",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          }
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "LOCAL",
            "availabilityImpact": "HIGH",
            "baseScore": 8.4,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 8.4,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 8.4,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2020-7516"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Evgeniy Druzhinin",
            "Ilya Karpov"
          ],
          "organization": "Rostelecom-Solar"
        }
      ],
      "cve": "CVE-2020-7517",
      "cwe": {
        "id": "CWE-312",
        "name": "Cleartext Storage of Sensitive Information"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-312: Cleartext Storage of Sensitive Information vulnerability exists which could allow an \r\nattacker to read user credentials.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "2"
        ],
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "This vulnerability is fixed in Easergy Builder version 1.6.3.0 and is available from your Schneider \r\nElectric Customer Care Center.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/work/support/contacts.jsp"
        },
        {
          "category": "mitigation",
          "details": "Additionally, Schneider Electric recommends customers apply the following mitigations to further \r\nreduce risk:\r\n\u2022 Use a separate secure local network and use secure computer access controls\r\n",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          }
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "LOCAL",
            "availabilityImpact": "NONE",
            "baseScore": 7.1,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 7.1,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "CHANGED",
            "temporalScore": 7.1,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N",
            "version": "3.0"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2020-7517"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Evgeniy Druzhinin",
            "Ilya Karpov"
          ],
          "organization": "Rostelecom-Solar"
        }
      ],
      "cve": "CVE-2020-7518",
      "cwe": {
        "id": "CWE-20",
        "name": "Improper Input Validation"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-20: Improper input validation vulnerability exists which could allow an attacker to modify \r\nproject configuration files.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "2"
        ],
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "This vulnerability is fixed in Easergy Builder version 1.6.3.0 and is available from your Schneider \r\nElectric Customer Care Center.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/work/support/contacts.jsp"
        },
        {
          "category": "mitigation",
          "details": "Additionally, Schneider Electric recommends customers apply the following mitigations to further \r\nreduce risk:\r\n\u2022 Use a separate secure local network and use secure computer access controls\r\n",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          }
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 8.2,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "environmentalScore": 8.2,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "LOW",
            "privilegesRequired": "NONE",
            "scope": "CHANGED",
            "temporalScore": 8.2,
            "temporalSeverity": "HIGH",
            "userInteraction": "REQUIRED",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:C/C:N/I:L/A:H",
            "version": "3.0"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2020-7518"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Evgeniy Druzhinin",
            "Ilya Karpov"
          ],
          "organization": "Rostelecom-Solar"
        }
      ],
      "cve": "CVE-2020-7519",
      "cwe": {
        "id": "CWE-521",
        "name": "Weak Password Requirements"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-521: Weak Password Requirements vulnerability exists which could allow an attacker to \r\ncompromise a user account. ",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "2"
        ],
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "This vulnerability is fixed in Easergy Builder version 1.6.3.0 and is available from your Schneider \r\nElectric Customer Care Center.",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/work/support/contacts.jsp"
        },
        {
          "category": "mitigation",
          "details": "Additionally, Schneider Electric recommends customers apply the following mitigations to further \r\nreduce risk:\r\n\u2022 Use a separate secure local network and use secure computer access controls\r\n",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          }
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "LOW",
            "baseScore": 7.3,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "LOW",
            "environmentalScore": 7.3,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "LOW",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 7.3,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L",
            "version": "3.0"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2020-7519"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…