ICSA-26-043-09
Vulnerability from csaf_cisa - Published: 2026-01-27 00:00 - Updated: 2026-02-12 07:00Summary
Hitachi Energy SuprOS
Notes
Summary
Hitachi Energy is aware of a vulnerability that affects the SuprOS product versions listed in this document. An attacker successfully exploiting this vulnerability can cause confidentiality, integrity and availability impacts. Please refer to the Recommended Immediate Actions for information about the mitigation/remediation.
Notice
The information in this document is subject to change without notice and should not be construed as a commitment by Hitachi Energy. Hitachi Energy provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall Hitachi Energy or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if Hitachi Energy or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from Hitachi Energy and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners.
Support
For additional information and support please contact your product provider or Hitachi Energy service organization. For contact information, see https://www.hitachienergy.com/contact-us/ for Hitachi Energy contact-centers.
General Mitigation Factors
It is highly recommended to deploy the product following the “SuprOS Security Deployment Guidelines” document. Customers should maintain their systems with products running on supported versions and follow maintenance releases. Recommended security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.
Legal Notice and Terms of Use
This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).
Advisory Conversion Disclaimer
This ICSA is a verbatim republication of Hitachi Energy PSIRT 8DBD000223 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Hitachi Energy PSIRT directly for any questions regarding this advisory.
Critical infrastructure sectors
Energy, Transportation Systems, Government Services and Facilities
Countries/areas deployed
Worldwide
Company headquarters location
Switzerland
Recommended Practices
CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities.
Recommended Practices
Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.
Recommended Practices
Locate control system networks and remote devices behind firewalls and isolate them from business networks.
Recommended Practices
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
{
"document": {
"acknowledgments": [
{
"organization": "Hitachi Energy",
"summary": "reported this vulnerability to CISA."
}
],
"aggregate_severity": {
"namespace": "https://www.first.org/cvss/specification-document",
"text": "HIGH"
},
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited",
"tlp": {
"label": "WHITE",
"url": "https://www.cisa.gov/news-events/news/traffic-light-protocol-tlp-definitions-and-usage"
}
},
"lang": "en-US",
"notes": [
{
"category": "summary",
"text": "Hitachi Energy is aware of a vulnerability that affects the SuprOS product versions listed in this document. An attacker successfully exploiting this vulnerability can cause confidentiality, integrity and availability impacts. Please refer to the Recommended Immediate Actions for information about the mitigation/remediation.",
"title": "Summary"
},
{
"category": "legal_disclaimer",
"text": "The information in this document is subject to change without notice and should not be construed as a commitment by Hitachi Energy. Hitachi Energy provides no warranty, express or implied, including warranties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall Hitachi Energy or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software described in this document, even if Hitachi Energy or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from Hitachi Energy and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners.",
"title": "Notice"
},
{
"category": "general",
"text": "For additional information and support please contact your product provider or Hitachi Energy service organization. For contact information, see https://www.hitachienergy.com/contact-us/ for Hitachi Energy contact-centers.",
"title": "Support"
},
{
"category": "general",
"text": "It is highly recommended to deploy the product following the \u201cSuprOS Security Deployment Guidelines\u201d document. Customers should maintain their systems with products running on supported versions and follow maintenance releases. Recommended security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.",
"title": "General Mitigation Factors"
},
{
"category": "legal_disclaimer",
"text": "This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy \u0026 Use policy (https://www.cisa.gov/privacy-policy).",
"title": "Legal Notice and Terms of Use"
},
{
"category": "other",
"text": "This ICSA is a verbatim republication of Hitachi Energy PSIRT 8DBD000223 from a direct conversion of the vendor\u0027s Common Security Advisory Framework (CSAF) advisory. This is republished to CISA\u0027s website as a means of increasing visibility and is provided \"as-is\" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Hitachi Energy PSIRT directly for any questions regarding this advisory.",
"title": "Advisory Conversion Disclaimer"
},
{
"category": "other",
"text": "Energy, Transportation Systems, Government Services and Facilities",
"title": "Critical infrastructure sectors"
},
{
"category": "other",
"text": "Worldwide",
"title": "Countries/areas deployed"
},
{
"category": "other",
"text": "Switzerland",
"title": "Company headquarters location"
},
{
"category": "general",
"text": "CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Locate control system networks and remote devices behind firewalls and isolate them from business networks.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
"title": "Recommended Practices"
}
],
"publisher": {
"category": "other",
"contact_details": "central@cisa.dhs.gov",
"name": "CISA",
"namespace": "https://www.cisa.gov/"
},
"references": [
{
"category": "self",
"summary": "ICS Advisory ICSA-26-043-09 JSON",
"url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2026/icsa-26-043-09.json"
},
{
"category": "self",
"summary": "Use of default credentials vulnerability in Hitachi Energy SuprOS product",
"url": "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000223\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=launch"
},
{
"category": "self",
"summary": "ICS Advisory ICSA-26-043-09 - Web Version",
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-26-043-09"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/topics/industrial-control-systems"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b"
}
],
"title": "Hitachi Energy SuprOS",
"tracking": {
"current_release_date": "2026-02-12T07:00:00.000000Z",
"generator": {
"date": "2026-02-11T23:15:52.864831Z",
"engine": {
"name": "CISA CSAF Generator",
"version": "1.5.0"
}
},
"id": "ICSA-26-043-09",
"initial_release_date": "2026-01-27T00:00:00.000000Z",
"revision_history": [
{
"date": "2026-01-27T00:00:00.000000Z",
"legacy_version": "Initial",
"number": "1",
"summary": "Initial public release"
},
{
"date": "2026-02-12T07:00:00.000000Z",
"legacy_version": "CISA Republication",
"number": "2",
"summary": "Initial CISA Republication of Hitachi Energy 8DBD000223 advisory"
}
],
"status": "final",
"version": "2"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "vers:SuprOS/\u003c=9.2.1",
"product": {
"name": "SuprOS 9.2.1 and below",
"product_id": "CSAFPID-0001"
}
},
{
"category": "product_version",
"name": "9.2.2.0",
"product": {
"name": "SuprOS 9.2.2.0",
"product_id": "CSAFPID-0002"
}
}
],
"category": "product_name",
"name": "SuprOS"
}
],
"category": "vendor",
"name": "Hitachi Energy"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2025-7740",
"cwe": {
"id": "CWE-1392",
"name": "Use of Default Credentials"
},
"notes": [
{
"category": "description",
"text": "A default credentials vulnerability exists in the SuprOS product. If exploited, this could allow an authenticated local attacker to gain access through an admin account created during product deployment."
}
],
"product_status": {
"known_affected": [
"CSAFPID-0001",
"CSAFPID-0002"
]
},
"references": [
{
"category": "external",
"summary": "NVD - CVE-2025-7740",
"url": "https://nvd.nist.gov/vuln/detail/CVE-2025-7740"
},
{
"category": "external",
"summary": "www.cve.org",
"url": "https://www.cve.org/CVERecord?id=CVE-2025-7740"
},
{
"category": "external",
"summary": "cwe.mitre.org",
"url": "https://cwe.mitre.org/data/definitions/1392.html"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Remove unwanted accounts and/or change the default passwords. Refer to the Secure Deployment Guidelines document as described in chapter 4.3",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "Upon clean install, change the root password",
"product_ids": [
"CSAFPID-0002"
]
},
{
"category": "mitigation",
"details": "If updated from previous version, remove unwanted accounts and/or change the default passwords. Refer to the Secure Deployment Guidelines document as described in chapter 4.3",
"product_ids": [
"CSAFPID-0002"
]
},
{
"category": "vendor_fix",
"details": "Hitachi Energy recommends that customers apply the update and take recommended actions at the earliest convenience",
"product_ids": [
"CSAFPID-0002",
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "While reviewing the recommended immediate actions, assess the risk exposure of affected products within the operational environment and update or upgrade if necessary",
"product_ids": [
"CSAFPID-0002",
"CSAFPID-0001"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "CHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0001",
"CSAFPID-0002"
]
}
],
"title": "CVE-2025-7740"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Loading…
Loading…