ICSA-18-137-01
Vulnerability from csaf_cisa - Published: 2018-05-17 00:00 - Updated: 2018-05-17 00:00Summary
GE PACSystems CPE305/310, CPE330, CPE400, RSTi-EP CPE 100, CPU320/CRU320, RXi
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of this vulnerability could cause the device to reboot and change its state, causing the device to become unavailable.
Critical infrastructure sectors
Critical Manufacturing
Countries/areas deployed
Worldwide
Company headquarters location
USA
Recommended Practices
NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
Recommended Practices
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
Recommended Practices
NCCIC also recommends that users take the following measures to protect themselves from social engineering attacks:
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Exploitability
No known public exploits specifically target this vulnerability.
{
"document": {
"acknowledgments": [
{
"names": [
"Younes Dragoni"
],
"organization": "Nozomi Networks",
"summary": "reporting the vulnerability to NCCIC"
}
],
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited",
"tlp": {
"label": "WHITE",
"url": "https://us-cert.cisa.gov/tlp/"
}
},
"lang": "en-US",
"notes": [
{
"category": "general",
"text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
"title": "CISA Disclaimer"
},
{
"category": "legal_disclaimer",
"text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
"title": "Legal Notice"
},
{
"category": "summary",
"text": "Successful exploitation of this vulnerability could cause the device to reboot and change its state, causing the device to become unavailable.",
"title": "Risk evaluation"
},
{
"category": "other",
"text": "Critical Manufacturing",
"title": "Critical infrastructure sectors"
},
{
"category": "other",
"text": "Worldwide",
"title": "Countries/areas deployed"
},
{
"category": "other",
"text": "USA",
"title": "Company headquarters location"
},
{
"category": "general",
"text": "NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "NCCIC also recommends that users take the following measures to protect themselves from social engineering attacks:",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
"title": "Recommended Practices"
},
{
"category": "other",
"text": "No known public exploits specifically target this vulnerability.",
"title": "Exploitability"
}
],
"publisher": {
"category": "coordinator",
"contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
"name": "CISA",
"namespace": "https://www.cisa.gov/"
},
"references": [
{
"category": "self",
"summary": "ICS Advisory ICSA-18-137-01 JSON",
"url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2018/icsa-18-137-01.json"
},
{
"category": "self",
"summary": "ICS Advisory ICSA-18-137-01 Web Version",
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-18-137-01"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-18-137-01"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/uscert/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
}
],
"title": "GE PACSystems CPE305/310, CPE330, CPE400, RSTi-EP CPE 100, CPU320/CRU320, RXi",
"tracking": {
"current_release_date": "2018-05-17T00:00:00.000000Z",
"generator": {
"engine": {
"name": "CISA CSAF Generator",
"version": "1.0.0"
}
},
"id": "ICSA-18-137-01",
"initial_release_date": "2018-05-17T00:00:00.000000Z",
"revision_history": [
{
"date": "2018-05-17T00:00:00.000000Z",
"legacy_version": "Initial",
"number": "1",
"summary": "ICSA-18-137-01 GE PACSystems CPE305/310, CPE330, CPE400, RSTi-EP CPE 100, CPU320/CRU320, RXi"
}
],
"status": "final",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version",
"name": "vers:all/*",
"product": {
"name": "PACSystems CPU320/CRU320 and RXi: all versions",
"product_id": "CSAFPID-0001"
}
}
],
"category": "product_name",
"name": "PACSystems CPU320/CRU320 and RXi"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c= 9.30",
"product": {
"name": "RX3i CPE 400: version 9.30 and prior",
"product_id": "CSAFPID-0002"
}
}
],
"category": "product_name",
"name": "RX3i CPE 400"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c= 9.20",
"product": {
"name": "PACSystems RX3i CPE305/310: version 9.20 and prior",
"product_id": "CSAFPID-0003"
}
}
],
"category": "product_name",
"name": "PACSystems RX3i CPE305/310"
},
{
"branches": [
{
"category": "product_version",
"name": "vers:all/*",
"product": {
"name": "PACSystems RSTi-EP CPE 100: all versions",
"product_id": "CSAFPID-0004"
}
}
],
"category": "product_name",
"name": "PACSystems RSTi-EP CPE 100"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c= 9.21",
"product": {
"name": "RX3i CPE330: version 9.21 and prior",
"product_id": "CSAFPID-0005"
}
}
],
"category": "product_name",
"name": "RX3i CPE330"
}
],
"category": "vendor",
"name": "General Electric (GE)"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2018-8867",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"category": "summary",
"text": "The device does not properly validate input, which could allow a remote attacker to send specially crafted packets causing the device to become unavailable.CVE-2018-8867 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).",
"title": "Vulnerability Summary"
}
],
"product_status": {
"known_affected": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005"
]
},
"references": [
{
"category": "external",
"summary": "web.nvd.nist.gov",
"url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-8867"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "IC695CPE305 - https://digitalsupport.ge.com/communities/en_US/Download/IC695CPE305-PACSystems-RX3i-CPU-DN - Upgrade Kit: CPE305_FW9_40_41G1733-MS10-000-A17.zip",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005"
],
"url": "https://digitalsupport.ge.com/communities/en_US/Download/IC695CPE305-PACSystems-RX3i-CPU-DN"
},
{
"category": "mitigation",
"details": "IC695CPE310 - https://digitalsupport.ge.com/communities/en_US/Download/IC695CPE310-PACSystems-RX3i-CPU-DN - Upgrade Kit: CPE310_FW9_40_41G1734-MS10-000-A17.zip",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005"
],
"url": "https://digitalsupport.ge.com/communities/en_US/Download/IC695CPE310-PACSystems-RX3i-CPU-DN"
},
{
"category": "mitigation",
"details": "IC695CPE330 - https://digitalsupport.ge.com/communities/en_US/Download/IC695CPE330-PACSystems-RX3i-CPU-DN - Upgrade Kit: CPE330_FW9_40_41G2016-FW01-000-A11.zip",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005"
],
"url": "https://digitalsupport.ge.com/communities/en_US/Download/IC695CPE330-PACSystems-RX3i-CPU-DN"
},
{
"category": "mitigation",
"details": "IC695CPE400 - https://digitalsupport.ge.com/communities/en_US/Download/IC695CPE400-PACSystems-RX3i-Rackless-CPU-with-Field-Agent - Upgrade Kit: CPE400_FW9_40_41G2376-FW01-000-A3.zip",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005"
],
"url": "https://digitalsupport.ge.com/communities/en_US/Download/IC695CPE400-PACSystems-RX3i-Rackless-CPU-with-Field-Agent"
},
{
"category": "mitigation",
"details": "For CPE100 the newest firmware can be obtained ",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005"
],
"url": "https://digitalsupport.ge.com/communities/en_US/Download/EPSCPE100-RSTi-EP-CPU-Firmware"
},
{
"category": "mitigation",
"details": "GE reports that CPU/CRU320 is end of life, and there is a direct upgrade path available to users.",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005"
]
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 7.5,
"baseSeverity": "HIGH",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.0"
},
"products": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005"
]
}
]
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Loading…
Loading…