icsa-18-032-02
Vulnerability from csaf_cisa
Published
2018-02-01 00:00
Modified
2018-02-01 00:00
Summary
3S-Smart Software Solutions GmbH CODESYS Web Server

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
ATTENTION: Remotely exploitable/low skill level to exploit.
Critical infrastructure sectors
Critical Manufacturing, Energy
Countries/areas deployed
Worldwide
Company headquarters location
Kempten, Germany
Recommended Practices
NCCIC recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should: Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet; Locate control system networks and remote devices behind firewalls, and isolate them from the business network; When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
Recommended Practices
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available in the NCCIC Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site.
Recommended Practices
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
Exploitability
No known public exploits specifically target this vulnerability.



{
  "document": {
    "acknowledgments": [
      {
        "names": [
          "Zhu WenZhe"
        ],
        "organization": "Istury IOT security lab",
        "summary": "reporting this vulnerability to NCCIC"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "ATTENTION: Remotely exploitable/low skill level to exploit.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Critical Manufacturing, Energy",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "Kempten, Germany",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "NCCIC recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should: Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet; Locate control system networks and remote devices behind firewalls, and isolate them from the business network; When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available in the NCCIC Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "other",
        "text": "No known public exploits specifically target this vulnerability.",
        "title": "Exploitability"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-18-032-02 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2018/icsa-18-032-02.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-18-032-02 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-18-032-02"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/"
      }
    ],
    "title": "3S-Smart Software Solutions GmbH CODESYS Web Server",
    "tracking": {
      "current_release_date": "2018-02-01T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-18-032-02",
      "initial_release_date": "2018-02-01T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2018-02-01T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "ICSA-18-032-02 3S-Smart Software Solutions GmbH CODESYS Web Server"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version",
                "name": "2.3",
                "product": {
                  "name": "CODESYS Web Server: Version 2.3",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "CODESYS Web Server"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c 1.1.9.19",
                "product": {
                  "name": "CODESYS Web Server: prior to V1.1.9.19",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "CODESYS Web Server"
          }
        ],
        "category": "vendor",
        "name": "3S-Smart Software Solutions GmbH"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2018-5440",
      "cwe": {
        "id": "CWE-121",
        "name": "Stack-based Buffer Overflow"
      },
      "notes": [
        {
          "category": "summary",
          "text": "A crafted request may cause a buffer overflow and could therefore execute arbitrary code on the web server or lead to a denial-of-service condition due to a crash in the web server. CVE-2018-5440 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-5440"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "This vulnerability will be fixed by patch V.1.1.9.19 for the CODESYS V2.3 web server for Windows. This will be part of the CODESYS setup V2.3.9.56. The release of this security patch was made available on January 30, 2018.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Currently, 3S-Smart Software Solutions GmbH has not identified any workarounds for this vulnerability.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Use controllers and devices only in a protected environment to minimize network exposure and ensure they are not accessible from outside.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Use firewalls to protect and separate the control system network from other networks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Use VPN (Virtual Private Networks) tunnels if remote access is required.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Protect both development and control systems from unauthorized access (e.g., by means of the operating system).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Protect both development and control system by using up-to-date virus detecting solutions.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "For additional information regarding the CODESYS products, or about the described vulnerability, please contact the 3S-Smart Software Solutions support team",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ],
          "url": "https://www.codesys.com/support-training/codesys-support.html"
        },
        {
          "category": "mitigation",
          "details": "For additional information find the CODESYS Security update",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ],
          "url": "https://customers.codesys.com/fileadmin/data/customers/security/2018/Advisory2018-01_LCDS-282.pdf"
        },
        {
          "category": "mitigation",
          "details": "For more information and general recommendations for protecting machines and manufacturing facilities, see the CODESYS Security whitepaper",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ],
          "url": "https://customers.codesys.com/fileadmin/data/customers/security/CODESYS-Security-Whitepaper.pdf"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.