ICSA-22-179-02
Vulnerability from csaf_cisa
Published
2022-06-28 00:00
Modified
2022-06-28 00:00
Summary
Omron SYSMAC CS/CJ/CP Series and NJ/NX Series
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could cause a denial-of-service condition and allow remote code execution.
Critical infrastructure sectors
Critical Manufacturing
Countries/areas deployed
Worldwide
Company headquarters location
Japan
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should: Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet; Locate control system networks and remote devices behind firewalls and isolate them from the business network; When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage atcisa.gov/ics. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage atcisa.gov/ics in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
Exploitability
No known public exploits specifically target these vulnerabilities.
{ "document": { "acknowledgments": [ { "names": [ "Daniel dos Santos", "Jos Wetzels" ], "organization": "Forescout Technologies", "summary": "reporting these vulnerabilities to CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of these vulnerabilities could cause a denial-of-service condition and allow remote code execution.", "title": "Risk evaluation" }, { "category": "other", "text": "Critical Manufacturing", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Japan", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should: Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet; Locate control system networks and remote devices behind firewalls and isolate them from the business network; When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage atcisa.gov/ics. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage atcisa.gov/ics in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "other", "text": "No known public exploits specifically target these vulnerabilities.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-22-179-02 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2022/icsa-22-179-02.json" }, { "category": "self", "summary": "ICS Advisory ICSA-22-179-02 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-179-02" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B" } ], "title": "Omron SYSMAC CS/CJ/CP Series and NJ/NX Series", "tracking": { "current_release_date": "2022-06-28T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-22-179-02", "initial_release_date": "2022-06-28T00:00:00.000000Z", "revision_history": [ { "date": "2022-06-28T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "Publication Date" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version", "name": "vers:all/*", "product": { "name": "CP1W-CIF41: All versions", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "CP1W-CIF41" }, { "branches": [ { "category": "product_version_range", "name": "\u003c 1.5", "product": { "name": "SYSMAC CJ2H: Versions prior to 1.5", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "SYSMAC CJ2H" }, { "branches": [ { "category": "product_version_range", "name": "\u003c 2.1", "product": { "name": "SYSMAC CJ2M: Versions prior to 2.1", "product_id": "CSAFPID-0003" } } ], "category": "product_name", "name": "SYSMAC CJ2M" }, { "branches": [ { "category": "product_version_range", "name": "\u003c 1.30", "product": { "name": "SYSMAC CP1E/CP1H: Versions prior to 1.30", "product_id": "CSAFPID-0004" } } ], "category": "product_name", "name": "SYSMAC CP1E/CP1H" }, { "branches": [ { "category": "product_version_range", "name": "\u003c 1.10", "product": { "name": "SYSMAC CP1L: Versions prior to 1.10", "product_id": "CSAFPID-0005" } } ], "category": "product_name", "name": "SYSMAC CP1L" }, { "branches": [ { "category": "product_version_range", "name": "\u003c 4.1", "product": { "name": "SYSMAC CS1: Versions prior to 4.1", "product_id": "CSAFPID-0006" } } ], "category": "product_name", "name": "SYSMAC CS1H/CJ1G" }, { "branches": [ { "category": "product_version_range", "name": "\u003c 9.6", "product": { "name": "SYSMAC CX-Programmer: Versions prior to 9.6", "product_id": "CSAFPID-0007" } } ], "category": "product_name", "name": "SYSMAC CX-Programmer" }, { "branches": [ { "category": "product_version_range", "name": "\u003c 1.49 (1.29 for NX7)", "product": { "name": "SYSMAC NJ/NX Series: Versions prior to 1.49 (1.29 for NX7)", "product_id": "CSAFPID-0008" } } ], "category": "product_name", "name": "SYSMAC NJ/NX Series" } ], "category": "vendor", "name": "Omron" } ] }, "vulnerabilities": [ { "cve": "CVE-2022-31204", "cwe": { "id": "CWE-319", "name": "Cleartext Transmission of Sensitive Information" }, "notes": [ { "category": "summary", "text": "Omron SYSMAC CS1/CJ1/CP1/CP2 series is vulnerable to a password used to restrict engineering operation is transmitted in plaintext. CVE-2022-31204 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-31204" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N" } ], "remediations": [ { "category": "mitigation", "details": "For CVE-2022-31204: Omron recommends users implement an extended password protection function in the following product versions: CS1: v.4.1 or later", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For CVE-2022-31204: Omron recommends users implement an extended password protection function in the following product versions: CJ2M: v2.1 or later", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For CVE-2022-31204: Omron recommends users implement an extended password protection function in the following product versions: CJ2H: v1.5 or later", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For CVE-2022-31204: Omron recommends users implement an extended password protection function in the following product versions: CP1E/CP1H: v1.30 or later", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For CVE-2022-31204: Omron recommends users implement an extended password protection function in the following product versions: CP1L: v1.10 or later", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For CVE-2022-31204: Omron recommends users implement an extended password protection function in the following product versions: CX-Programmer: v9.6 or higher", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 6.5, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-31205", "cwe": { "id": "CWE-256", "name": "Plaintext Storage of a Password" }, "notes": [ { "category": "summary", "text": "The CP1W-CIF41 Ethernet Option Board is vulnerable to a Web UI password that can be read from memory using the Omron FINS protocol. An attacker obtaining this password could change the network settings of the option board. CVE-2022-31205 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-31205" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N" } ], "remediations": [ { "category": "mitigation", "details": "For CVE-2022-31205: Omron recommends using different passwords between the CP1W-CIF41 Ethernet Option Board and CP1 PLC itself. The Web UI password will not grant access to the PLC.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 6.5, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-31207", "cwe": { "id": "CWE-345", "name": "Insufficient Verification of Data Authenticity" }, "notes": [ { "category": "summary", "text": "The logic that is downloaded to the PLC is not cryptographically authenticated, allowing an attacker to manipulate transmitted object code to an unprotected PLC without using the PLC protection password. An attacker could then execute arbitrary object code commands on the defined software logic for all versions of SYSMAC CS/CJ/CP series controllers and cause a denial-of-service condition. CVE-2022-31207 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-31207" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "For CVE-2022-31207: Omron recommends users of SYSMAC CS/CJ/CP Series to use the PLC protection password and enable protection against unauthorized write access to address. Also, there are hardware DIP switches on the PLC which can prevent unauthorized PLC program changes regardless of password.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 5.9, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.0/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-31206", "cwe": { "id": "CWE-347", "name": "Improper Verification of Cryptographic Signature" }, "notes": [ { "category": "summary", "text": "The logic that is downloaded to the PLC is not cryptographically authenticated, allowing an attacker to manipulate transmitted object code to the PLC and execute arbitrary machine code on the processor of the PLC\u0027s CPU module for SYSMAC NJ/NX series controllers. CVE-2022-31206 has been assigned to this vulnerability. A CVSS v3 base score of 4.4 has been assigned; the CVSS vector string is (AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:N).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-31206" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:N" } ], "remediations": [ { "category": "mitigation", "details": "For CVE-2022-31206: Omron intends to publish an update for SYSMAC NJ/NX in July 2022.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 4.4, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.0/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:N", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] } ] }
Loading…
Loading…
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.