Vulnerabilites related to Schneider Electric - Modicon M580 CPU (part numbers BMEP* and BMEH*, excluding M580 CPU Safety)
cve-2024-11425
Vulnerability from cvelistv5
Published
2025-01-17 09:00
Modified
2025-02-12 17:09
Severity ?
8.7 (High) - CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
7.5 (High) - CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
7.5 (High) - CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS score ?
Summary
CWE-131: Incorrect Calculation of Buffer Size vulnerability exists that could cause Denial-of-Service of the
product when an unauthenticated user is sending a crafted HTTPS packet to the webserver.
References
Impacted products
Vendor | Product | Version | |||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
▼ | Schneider Electric | Modicon M580 CPU (part numbers BMEP* and BMEH*, excluding M580 CPU Safety) |
Version: Versions prior to SV4.30 |
||||||||||||||||
|
{ "containers": { "adp": [ { "metrics": [ { "other": { "content": { "id": "CVE-2024-11425", "options": [ { "Exploitation": "none" }, { "Automatable": "yes" }, { "Technical Impact": "partial" } ], "role": "CISA Coordinator", "timestamp": "2025-01-17T13:22:26.095314Z", "version": "2.0.3" }, "type": "ssvc" } } ], "providerMetadata": { "dateUpdated": "2025-02-12T17:09:38.349Z", "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0", "shortName": "CISA-ADP" }, "title": "CISA ADP Vulnrichment" } ], "cna": { "affected": [ { "defaultStatus": "unaffected", "product": "Modicon M580 CPU (part numbers BMEP* and BMEH*, excluding M580 CPU Safety)", "vendor": "Schneider Electric", "versions": [ { "status": "affected", "version": "Versions prior to SV4.30" } ] }, { "defaultStatus": "unaffected", "product": "Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S)", "vendor": "Schneider Electric", "versions": [ { "status": "affected", "version": "Versions prior to SV4.21" } ] }, { "defaultStatus": "unaffected", "product": "BMENOR2200H", "vendor": "Schneider Electric", "versions": [ { "status": "affected", "version": "All Versions" } ] }, { "defaultStatus": "unaffected", "product": "EVLink Pro AC", "vendor": "Schneider Electric", "versions": [ { "status": "affected", "version": "Versions prior to v1.3.10" } ] } ], "descriptions": [ { "lang": "en", "supportingMedia": [ { "base64": false, "type": "text/html", "value": "CWE-131: Incorrect Calculation of Buffer Size vulnerability exists that could cause Denial-of-Service of the\nproduct when an unauthenticated user is sending a crafted HTTPS packet to the webserver.\n\n\u003cbr\u003e" } ], "value": "CWE-131: Incorrect Calculation of Buffer Size vulnerability exists that could cause Denial-of-Service of the\nproduct when an unauthenticated user is sending a crafted HTTPS packet to the webserver." } ], "metrics": [ { "cvssV4_0": { "Automatable": "NOT_DEFINED", "Recovery": "NOT_DEFINED", "Safety": "NOT_DEFINED", "attackComplexity": "LOW", "attackRequirements": "NONE", "attackVector": "NETWORK", "baseScore": 8.7, "baseSeverity": "HIGH", "privilegesRequired": "NONE", "providerUrgency": "NOT_DEFINED", "subAvailabilityImpact": "NONE", "subConfidentialityImpact": "NONE", "subIntegrityImpact": "NONE", "userInteraction": "NONE", "valueDensity": "NOT_DEFINED", "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N", "version": "4.0", "vulnAvailabilityImpact": "HIGH", "vulnConfidentialityImpact": "NONE", "vulnIntegrityImpact": "NONE", "vulnerabilityResponseEffort": "NOT_DEFINED" }, "format": "CVSS", "scenarios": [ { "lang": "en", "value": "GENERAL" } ] }, { "cvssV3_1": { "attackComplexity": "LOW", "attackVector": "NETWORK", "availabilityImpact": "HIGH", "baseScore": 7.5, "baseSeverity": "HIGH", "confidentialityImpact": "NONE", "integrityImpact": "NONE", "privilegesRequired": "NONE", "scope": "UNCHANGED", "userInteraction": "NONE", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "version": "3.1" }, "format": "CVSS", "scenarios": [ { "lang": "en", "value": "GENERAL" } ] } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-131", "description": "CWE-131 Incorrect Calculation of Buffer Size", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2025-01-17T09:00:32.335Z", "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb", "shortName": "schneider" }, "references": [ { "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-014-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-014-01.pdf" } ], "source": { "discovery": "UNKNOWN" }, "x_generator": { "engine": "Vulnogram 0.2.0" } } }, "cveMetadata": { "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb", "assignerShortName": "schneider", "cveId": "CVE-2024-11425", "datePublished": "2025-01-17T09:00:32.335Z", "dateReserved": "2024-11-19T15:35:20.847Z", "dateUpdated": "2025-02-12T17:09:38.349Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
cve-2023-6408
Vulnerability from cvelistv5
Published
2024-02-14 16:52
Modified
2024-08-02 08:28
Severity ?
EPSS score ?
Summary
CWE-924: Improper Enforcement of Message Integrity During Transmission in a
Communication Channel vulnerability exists that could cause a denial of service and loss of
confidentiality, integrity of controllers when conducting a Man in the Middle attack.
References
Impacted products
Vendor | Product | Version | ||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
▼ | Schneider Electric | Modicon M340 CPU (part numbers BMXP34*) |
Version: Versions prior to sv3.60 |
|||||||||||||||||||||
|
{ "containers": { "adp": [ { "affected": [ { "cpes": [ "cpe:2.3:o:schneider-electric:modicon_m580_bmeh582040c_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh582040_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh582040s_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh584040c_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh584040_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh584040s_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh586040c_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh586040_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh586040s_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmep581020_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmep581020h_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmep582020_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmep582020h_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmep582040h_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmep582040s_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmep583020_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmep583040_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmep584020_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmep584040_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmep584040s_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmep585040c_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmep585040_firmware:-:*:*:*:*:*:*:*" ], "defaultStatus": "unknown", "product": "modicon_m580_bmep585040_firmware", "vendor": "schneider-electric", "versions": [ { "lessThan": "4.20", "status": "affected", "version": "0", "versionType": "custom" } ] }, { "cpes": [ "cpe:2.3:o:schneider-electric:modicon_m340_bmxp341000_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m340_bmxp341000h_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m340_bmxp342000_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m340_bmxp3420102cl_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m340_bmxp3420102_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m340_bmx_p34-2010_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m340_bmxp342010_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m340_bmxp342020_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m340_bmxp342020h_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m340_bmxp3420302cl_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m340_bmxp3420302_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m340_bmxp3420302h_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m340_bmx_p34-2030_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m340_bmxp342030_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m340_bmxp342030h_firmware:-:*:*:*:*:*:*:*" ], "defaultStatus": "unknown", "product": "modicon_m340_bmxp342030h_firmware", "vendor": "schneider-electric", "versions": [ { "lessThan": "3.60", "status": "affected", "version": "0", "versionType": "custom" } ] }, { "cpes": [ "cpe:2.3:o:schneider-electric:modicon_m580_bmeh582040c_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh582040_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh582040s_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh584040c_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh584040_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh584040s_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh586040c_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh586040_firmware:-:*:*:*:*:*:*:*", "cpe:2.3:o:schneider-electric:modicon_m580_bmeh586040s_firmware:-:*:*:*:*:*:*:*" ], "defaultStatus": "unknown", "product": "modicon_m580_bmeh586040s_firmware", "vendor": "schneider-electric", "versions": [ { "lessThan": "*", "status": "affected", "version": "0", "versionType": "custom" } ] } ], "metrics": [ { "other": { "content": { "id": "CVE-2023-6408", "options": [ { "Exploitation": "none" }, { "Automatable": "no" }, { "Technical Impact": "total" } ], "role": "CISA Coordinator", "timestamp": "2024-07-17T19:15:41.696437Z", "version": "2.0.3" }, "type": "ssvc" } } ], "providerMetadata": { "dateUpdated": "2024-07-17T19:36:47.656Z", "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0", "shortName": "CISA-ADP" }, "title": "CISA ADP Vulnrichment" }, { "providerMetadata": { "dateUpdated": "2024-08-02T08:28:21.776Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_transferred" ], "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2024-044-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2024-044-01.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "defaultStatus": "unaffected", "product": "Modicon M340 CPU (part numbers BMXP34*)", "vendor": "Schneider Electric", "versions": [ { "status": "affected", "version": "Versions prior to sv3.60" } ] }, { "defaultStatus": "unaffected", "product": "Modicon M580 CPU (part numbers BMEP* and BMEH*, excluding M580 CPU Safety)", "vendor": "Schneider Electric", "versions": [ { "status": "affected", "version": "Versions prior to sv4.20" } ] }, { "defaultStatus": "unaffected", "product": "Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S)", "vendor": "Schneider Electric", "versions": [ { "status": "affected", "version": "All Versions" } ] }, { "defaultStatus": "unaffected", "product": "EcoStruxure Control Expert", "vendor": "Schneider Electric", "versions": [ { "status": "affected", "version": "Versions prior to v16.0" } ] }, { "defaultStatus": "unaffected", "product": "EcoStruxure Process Expert", "vendor": "Schneider Electric", "versions": [ { "status": "affected", "version": "Versions prior to v2023" } ] } ], "descriptions": [ { "lang": "en", "supportingMedia": [ { "base64": false, "type": "text/html", "value": "\n\nCWE-924: Improper Enforcement of Message Integrity During Transmission in a\nCommunication Channel vulnerability exists that could cause a denial of service and loss of\nconfidentiality, integrity of controllers when conducting a Man in the Middle attack.\n\n" } ], "value": "\nCWE-924: Improper Enforcement of Message Integrity During Transmission in a\nCommunication Channel vulnerability exists that could cause a denial of service and loss of\nconfidentiality, integrity of controllers when conducting a Man in the Middle attack.\n\n" } ], "metrics": [ { "cvssV3_1": { "attackComplexity": "HIGH", "attackVector": "NETWORK", "availabilityImpact": "HIGH", "baseScore": 8.1, "baseSeverity": "HIGH", "confidentialityImpact": "HIGH", "integrityImpact": "HIGH", "privilegesRequired": "NONE", "scope": "UNCHANGED", "userInteraction": "NONE", "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.1" }, "format": "CVSS", "scenarios": [ { "lang": "en", "value": "GENERAL" } ] } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-924", "description": "CWE-924 Improper Enforcement of Message Integrity During Transmission in a Communication Channel", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2024-02-14T16:52:24.805Z", "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb", "shortName": "schneider" }, "references": [ { "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2024-044-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2024-044-01.pdf" } ], "source": { "discovery": "UNKNOWN" }, "x_generator": { "engine": "Vulnogram 0.1.0-dev" } } }, "cveMetadata": { "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb", "assignerShortName": "schneider", "cveId": "CVE-2023-6408", "datePublished": "2024-02-14T16:52:24.805Z", "dateReserved": "2023-11-30T09:52:30.945Z", "dateUpdated": "2024-08-02T08:28:21.776Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }